15

STR Series Woodburning Fireplaces

7412961

MA81

rev. 8/5/97

1

���

"

Ref.

Combustible materials are

permitted within a shaded area

shown in Figure 23, titled

Minimum Wall Clearances.

*

* *

MA81

Fig. 22

  Combustible mantel clearances.

Face Plate

*12" (305 mm) from top of fireplace opening.
** 6" (159 mm) from top of fireplace opening. 
(Noncombustible material must separate the 
black face surround of the fireplace and any 
combustible mantel material)

FP721

STR/CVR

6/4/98

���

1/2"

*

12"

(305mm)

Min.

12"

(305mm)

Max.

1/2"

12"

(305mm)

Min.

12"

(305mm)

Max.

6“

(159mm)

Min.

FP721

Fig. 21

  Fireplace surround flush with finished wall.

Mantel Clearance - 
No Noncombustible Facing Material

Finished Wall

Standoff

2 x 4 Stud

Noncombustible Mate-

rial

Header
Ledge Bracket

Fireplace 

Front

Fireplace Opening

* Minimum width from top of sur-

round to bottom of screen rail

Combustible 

Mantel and Trim

Combustible 

Mantel and Trim

Standoff

Finished Wall

2 x 4 Stud

Noncombustible Mate-

rial

Header
Ledge Bracket

Fireplace 

Front

Fireplace Opening

Noncombustible Facing Material

Finished Wall

2 x 4 Stud

Must be sealed with

 noncombustible material

Fireplace 

Front

Mantel Clearance - 
with Noncombustible Facing Material

Содержание STR33

Страница 1: ...Fireplace For Models STR33 STR36 STR42 For use in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 7412961 12 08 Rev 19 Homeowner s Installation...

Страница 2: ...mbination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or ac cessory Any such action...

Страница 3: ...added note 9 21 99 Outside Air 14 12 C 12 G F B J 24 Total Unit Width Framing Width Will be 24 Minus 2 x Drywall Thickness 18 STR33 STR36 STR42 A 33 36 42 838mm 914mm 1067mm B 37 40 46 940mm 1016mm 1...

Страница 4: ...STR36 29 17 737 mm 435 mm STR42 35 17 889 mm 435 mm FP1545 Fig 3a Hearth dimensions FP701a STR Parts ID Gas Line Access Outer Dome Outside Air Access Ledge Brackets Header Standoffs Flue Damper Contro...

Страница 5: ...e and chase parts identi cation FP704 STR from FP528 7 28 98 Termination Cap Storm Collar Pan Flashing Draftstop Finish Wall Batt Insulation cut out around restop Firestop Ceiling Level Outer Dome Ref...

Страница 6: ...imney exit STR Series Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structur...

Страница 7: ...ey to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes thr...

Страница 8: ...HEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vert...

Страница 9: ...SK8 2 wall chimney systems STR Fireplaces use only model 11CF chimney system Straight Up Chimney Installation To locate the centerline of the ue put the replace in nal position and place a plumb bob f...

Страница 10: ...ves restop spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 12 in order to provide the required air space 1 38 mm with SK8 2 51 mm with Mo...

Страница 11: ...lace are noncombustible Eight 8 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and instal...

Страница 12: ...space to chimney pipe for ceiling thickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be made in framing to assure...

Страница 13: ...ost portion of chimney sections and any adjacent combustible sur faces Fig 20 Combustible surfaces include burnable materials such as ceiling members joists ooring combustible insulation and roof stru...

Страница 14: ...Firestop Spacers Finishing CAUTION All joints between the nished wall and the replace surround top sides must be sealed with non combustible material to prevent cold air leakage into the room Only no...

Страница 15: ...2 12 305mm Min 12 305mm Max 6 159mm Min FP721 Fig 21 Fireplace surround ush with nished wall Mantel Clearance No Noncombustible Facing Material Finished Wall Standoff 2 x 4 Stud Noncombustible Mate ri...

Страница 16: ...d for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM 126 K 27 1 2 inches thick 2 MHSC EH2416 K 458 1 inch thick required FP723 Fig 23 Minimum rebox dimensions fro...

Страница 17: ...material Fig 24 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension...

Страница 18: ...required X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness Safety Strips Must be Over lapped 1 2 Min Minimu...

Страница 19: ...OTE When installing an ANSI Z21 11 2 ventless ap pliance the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated le...

Страница 20: ...embly two per replace 3049122 3030126 3032112 5 Screen Assembly four per replace 7554338 7554338 7554340 6 Screen Pulls four per replace 5584139 5584139 5584139 7a Firebrick Hearth 3100103 3102103 310...

Страница 21: ...ssories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact MHSC 149 Cleveland Driv...

Страница 22: ...a square cap Adaptor required Square Termination Top housing with simulated brick pattern T20B Red Tan or Black Proper adapter must be used Includes ashing Adapter Required adapters for T20B top hous...

Страница 23: ...tact AIS SK SK8 with the chimney system FS2100 HT 11CF U S Chimney Components cont d Model Number Description Component Attic Insulation Shield Used to prevent insulation from coming in AIS SK SK8 con...

Страница 24: ...ect safe operation We do not warrant this replace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local build...

Отзывы: