14
Vermont Castings Majestic Products DV360/580 Series
20002261
Finished
Wall
Vent
Termination
Fig. 23 Side view of final unit location.
FP1005
Rear Wall Vent Installations
Step 1
Locate and cut the vent opening in the wall.
For combustible walls first frame in opening. (Fig. 21)
Combustible Walls: Cut a 10
³⁄₈
”H x 9
³⁄₈
” W (265mm x
240mm) hole through the exterior wall and frame as
shown. (Fig. 21)
Noncombustible Walls: Hole opening should be 7
¹⁄₂
”
(191mm) diameter.
Zero clearance sleeve is only required for
combustible walls.
Step 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (Maximum 12” / 305mm). As-
semble sleeve to its maximum opening (10
³⁄₈
” x 9
³ ₈
”)
and attach to firestop assembly. (Fig. 22)
Step 3
Measure the horizontal length requirement for the
venting including a 2” (51mm) overlap, i.e. from the
elbow to the outside wall face plus 2” (51mm). (Fig. 20)
Step 4
Install the 4” (102mm) vent to the appliance collar and
secure with 3 sheet metal screws. Install the 7”
(178mm) vent pipe to the appliance collar and secure
with 3 sheet metal screws. It is not necessary to seal
this connection. If a 45
°
elbow is being used attach the
elbow to the appliance in the same manner then attach
the venting to the elbow.
It is critical that there is no downward
slope away from the appliance when
connecting the vent or elbow.
Step 5
Guide the venting through the vent hole as you place
the appliance in its installed position. Guide the 4”
(102mm) and 7” (178mm) collar of the vent termination
into the outer ends of the venting. Do not force the
termination. If the vent pipes do not align with the
termination, remove and realign the venting at the
appliance flue collars. (Fig. 23) Attach the termination
to the wall as outlined in the instruction sheet supplied
with the termination.
Fig. 21 Locate vent opening on wall.
Framing
Detail
9
³⁄₈
"
(240 mm)
10
³⁄₈
"
(265 mm)
Fireplace Hearth
Rnd.
7
¹⁄₂
" Dia.
(190 mm)
Opening for Noncombustible Wall
Fireplace Hearth
VO584-100
Vent Opening for Combustible Wall
#8 Screws
(2)
Adjustable Zero Clearance Sleeve
Firestop
#8 Screws (2)
#8 Screws (2)
Adjustable Zero
Clearance Sleeve
Max. Length 12"
(305mm)
Fig. 22 Adjustable zero clearance sleeve.
ZCS101
Vertical Sidewall Applications
Since it is very important that the venting system
maintain its balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between
vertical and horizontal side wall venting, will help to
determine the various dimensions allowable.
Minimum clearance between vent pipes and com-
bustible materials is one inch (25mm) on top,
bottom and sides unless otherwise noted.