33
Majestic • DBDV36IN, DBDV36IL, DBDV42IN, DBDV42IL Installation Manual • 2397-980 Rev. B • 5/16
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield
fi
restop(s). The wall shield
fi
restop maintains minimum clearances and prevents cold
air in
fi
ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
• SLP pipe - A wall shield
fi
restop must be placed on each
side of an interior wall. A minimum 1-1/2 in. (38 mm)
overlap of attached heat shields must be maintained.
• DVP pipe - A wall shield
fi
restop is required on one side
only on interior walls. If your local inspector requires a
wall shield
fi
restop on both sides, then both wall shield
fi
restops must have a heat shield (refer to Section
12.A.) attached to them.
• See Section 7.F. for information for regarding the instal-
lation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-com-
bustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield
fi
restop is only required on one side and no heat
shield is necessary.
Figure 5.3 Wall Penetration
A*
B*
10 in.
12 in.
C
D
10 in.
12 in.
ELBOW HEAT SHIELD
* Shows center of vent framing hole for top or rear venting. The center of the
hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.
A*
B*
C
D
DBDV36IN/IL
in.
42-3/4
27-7/8
41-3/4
26-7/8
mm
1086
708
1060
683
DBDV42IN/IL
in.
45-1/8
29-7/8
44-1/8
28-7/8
mm
1146
759
1111
733
WARNING! Risk of Fire!
Elbow heat shield required
when V
1
= 2 ft. or less. Clearances to combustibles
must be maintained. See Section 5.A.