background image

28

360 DVS Series Direct Vent Fireplaces

10006326

NOTE:  Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.

SIT NOVA 820 MILLIVOLT VALVE

Troubleshooting the Gas Control System

WARNING:  REMOVE GLASS FRONT BEFORE DOING ANY GAS CONTROL SERVICE WORK.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

electrode at pilot.

pilot and push the red button again. If pilot will not
light, check the gap at electrode and pilot; it should
be 1/8" to have a strong spark.

B. Defective ignitor (Push Button)

Push piezo Ignitor Button. Check for spark at
electrode and pilot. If no spark to pilot, and electode
wire is properly connected, replace ignitor.

 2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermocouple/

  carefully following lighting

(thermocouple), remote wall

thermopile.  NOTE: This pilot burner assembly

  instructions.

switch.

utilizes both a thermocouple and a thermopile.
The thermocouple operates the main valve operation
(ON/ OFF). Clean and/or adjust pilot for maximum
flame impingement on thermopile and thermocouple.

B. Defective automatic valve

Turn valve knob to “Pilot.” Maintain flow to pilot;
millivolt meter should read greater than 10 mV. If
the reading is okay and the pilot does not stay on,
replace the gas valve. NOTE:  An interrupter block
(not supplied) must be used to conduct this test.

 3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connections

  main burner

Jumper wire across terminals at wall switch; if burner
comes on, replace defective wall switch. If okay,
jumper wires across wall switch wires at valve; if
burner comes on, wires are faulty or connections are
bad.

B. Thermopile may not be

1. Be sure wire connections from thermopile at

generating sufficient

gas valve terminals are tight and thermopile is

millivoltage.

fully inserted into pilot bracket.

2. One of the wall switch wires may be grounded.

Remove wall switch wires from valve terminals if
pilot now stays lit, trace wall switch wiring for
ground. May be grounded to fireplace or gas
supply.

3. Check thermopile with millivolt meter. Take

reading at thermopile terminals of gas valve—
should read 250-300 millivolts (minimum 150)
while holding valve knob depressed in pilot
position and wall switch “OFF.” Replace faulty
thermopile if reading is below specified minimum.

C. Plugged burner orifice.

Check burner orifices for debris and remove.

D. Defective automatic valve

Turn valve knob to “ON,” place wall switch to “ON” —

operator.

millivolt meter should read greater than 100 mV. If
the reading is okay and the burner does not come
on, replace the gas valve.

 4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

 problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

pilot safety to drop out.

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

terminal.

flue gases)

Содержание 360DVS2

Страница 1: ...ity of this or any other appliance If you smell gas 1 Open windows 2 Do not touch electrical switches 3 Do not try to light any appliance 4 Extinguish any open flame 5 Do not use any telephone in your...

Страница 2: ...ion 16 Below Grade Installation 19 Vertical Through the Roof Application Installation 20 Twist Lock Venting Components 22 Operating Instructions Glass Information 23 Louvre Removal 23 Window Frame Ass...

Страница 3: ...replace 10 The flow of combustion and ventilation air must not be obstructed in any way 11 When the fireplace is installed directly on carpeting vinyl tile or any combustible material other than wood...

Страница 4: ...ical Access Gas Line Access J J K J J Fireplace Dimensions 360DVS2 Rear Vent Configuration Top Vent Configuration Ref Rear Vent Configuration Top Vent Configuration A 38 968mm 38 968mm B 43 1099mm 43...

Страница 5: ...360DVS3 306DVSL 360DVSR Rear Vent Configuration Top Vent Configuration Ref Rear Vent Configuration Top Vent Configuration A 38 968mm 38 968mm B 40 1032mm 40 1032mm C 24 610mm 24 610mm D 24 610mm 24 6...

Страница 6: ...s Ref Rear Vent Configuration Top Vent Configuration ROD 24 610mm minus two times finishing material thickness to be even with face of unit ROH 38 981mm Not to be framed until unit is set in place due...

Страница 7: ...Configuration Model 360DVS3 360DVSL R 360DVS3 360DVSL R ROD See Note 1 See Note 2 See Note 1 See Note 2 ROH 38 981mm Not to be framed until unit is set in place due to 3 79mm allowance for flue collar...

Страница 8: ...nt to prevent discoloration Clearance to Combustibles A B C D E V W X Y Z Louvre Assembly Top Fireplace Top of Combustion Chamber Bottom of Door Trim Mantel Shelf Mantel from Top Ref or Breast Plate R...

Страница 9: ...h 360DVS2RN Nat Millivolt 38 000 26 600 360DVS2RP Prop Millivolt 38 000 28 500 360DVS2EN Nat 24V Hi Lo 38 000 26 600 360DVS2EP Prop 24V Hi Lo 38 000 28 500 360DVS3RN Nat Millivolt 38 000 26 600 360DV...

Страница 10: ...x 2 Remove the plug socket assembly from the EB 1 box 3 Feed the supply line in from the out through the electrical knockout 4 Connect the ground wire of the supply line to the green screw of the sock...

Страница 11: ...M Specialty Home Products must be used for this purpose NOTE When converting appliance to top vent ensure the insulation material referred to in step 3 is completely removed 4 Remove the 4 screws secu...

Страница 12: ...0VA TRANSFORMER 24 VAC HOT BLACK WHITE WALL SWITCH WHITE OFF 1 2 3 5 6 8 9 MV MV VP PV GRD 24V SENSE SPARK 24V ORANGE RED GREEN BLACK FP1225 Fig 12 Honeywell ignition module Your fireplace is approved...

Страница 13: ...regulator assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion...

Страница 14: ...lation code USA Installations The venting system must conform with local codes and or current National Fuel Gas Code ANSI Z223 1 NFPA 54 Only venting components manufactured by CFM Corporation can be...

Страница 15: ...nt graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system Fig 16 Sidewall vent graph Rear Wall Application When installed as a rear vent unit this appl...

Страница 16: ...d realign the venting at the appliance flue collars Attach the termination to the wall as outlined in the instruction sheet supplied with the termination Vertical Sidewall Application It is very impor...

Страница 17: ...elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizon...

Страница 18: ...again secure joints as described in Connecting Vent Pipes section STEP 5 Measure the horizontal length requirement including a 2 51mm overlap i e from the elbow to the outside wall face plus 2 51mm o...

Страница 19: ...runs if the vertical exceeds 24 610 mm 1 Establish vent hole through the wall Fig 24 2 Remove soil to depth of about 16 406mm below base of snorkel Install window well not supplied Refill hole with 12...

Страница 20: ...ntal length must be reduced by 18 457mm Example Maximum horizontal length Zero elbows 10 3m 1 x 45 elbows 8 2 6m 2 x 45 elbows 7 2 1m A minimum of an 8 ft 2 43 m vertical rise Two 2 sets of 45 elbow o...

Страница 21: ...til the venting is above the flashing Fig 34 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 32 11 Apply high temperature sealant to 4 and 7 collar...

Страница 22: ...ion 45 Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90 Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90 Elbow 7TDV90 Vertical Horizontal Offset Telescopic Ven...

Страница 23: ...edge of frame out slightly and lift window frame assembly up and away from the fireplace 7 To reinstall the window frame assembly reverse this procedure Front Window Frame Assembly 1 Remove the top a...

Страница 24: ...t into the underside For correct operation of the fireplace the logs must be correctly placed in the sequence described below 1 Unpack the logs from the shipping carton The logs are fragile handle the...

Страница 25: ...near the center of the gas control valve Fig 42 and Fig 43 L O HI Turn counterclockwise to decrease flame height Turn clockwise to increase flame height Fig 42 Flame adjustment knob for Honeywell valv...

Страница 26: ...ll around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do...

Страница 27: ...d do not try to repair it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call...

Страница 28: ...t supplied must be used to conduct this test 3 Pilot burning no gas to A Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wire across terminals at w...

Страница 29: ...RES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY...

Страница 30: ...ce Piezo Ignitor Supply Line Hooked Up Shutoff Valve Open PILOT STAYS LIT For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections Replace Thermopile Thermoco...

Страница 31: ...ed in the conversion kit Air Shutter Retaining Screws Air Shutters FP1447 Fig 46 Air shutter adjustment 8 SIT Top Convertible Pilot Gently lift off pilot hood from the pilot NOTE Do not remove the spr...

Страница 32: ...l gas used The only variations are in orifice sizes and component part numbers Your authorized service pro vider will ensure correct parts are used L O H I Regulator Cap Conversion Screw Pressure Regu...

Страница 33: ...hould be per formed by a qualified technician 1 Turn off pilot light at gas valve side 2 Let fireplace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal...

Страница 34: ...12 18 24 27 17 2 29 28 22 23 26 21 20 25 19 13 14 3a b 15a b 16a b 31a b 32 35 33 HI LO 34a b 25 36 37 30 1 1a 1b 1c 1d 1e 1f 1g CFM Specialty Home Products reserves the right to make changes in desi...

Страница 35: ...E with cable electrode 10001824 10001824 10001824 10001824 7 Pilot SIT Top Convertible 10002266 10002266 10002266 10002266 8 Pilot Hood SIT Top Convertible 10002385 10002385 10002385 10002385 Orifice...

Страница 36: ...ractory Lining vertical side wall N A N A 10006285 10006285 30 CR Bottom Kit w out Rear 10006257 10006257 10006257 10006257 Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174 Air Inlet...

Страница 37: ...wiring 4 The power supply may be connected in two ways Method A Route the 6 lead fitted to the unit to a conveniently located wall socket Method B The EB I receptacle box Pt ZA1200 may be hard wired...

Страница 38: ...mable 24 hour clock IMT Wall mounted thermostat control Decorative Trim Frame Kit The DV360TKMP Medium Trim Kit in polished brass is available for the 360DVS2 model only Each kit contains 4 polished b...

Страница 39: ...upon inspection the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisi...

Страница 40: ...83 84 65 360DVS3RP 62 4 83 84 65 360DVS3EN 62 4 83 84 65 360DVS3EP 62 4 83 84 65 360DVSLRN 62 4 83 84 65 306DVSLRP 62 4 83 84 65 360DVSLEN 62 4 83 84 65 360DVSLEP 62 4 83 84 65 360DVSRRN 62 4 83 84 65...

Отзывы: