18/24/30VL Unvented Gas Logs
CLEARANCES
The minimum clearance to any combustible item in front of this appliance should be no less
than 36 inches from the face of the fireplace in which this appliance is installed.
Any combustible mantel present on the fireplace facing of any fireplace in which this
appliance is installed must not extend more than 12 inches from the face of the fireplace.
Also, the combustible mantel must be at least 28 inches above the fireplace opening as
shown in Figure 2 unless a CABL/CABR fireplace canopy is installed as described.
If a combustible mantel is less than 28 inches above the fireplace opening of any fireplace
in which this appliance is installed, obtain a CABL/CABR fireplace canopy from your
appliance dealer and install it on the fireplace according to the instructions furnished with
the CABL/CABR fireplace canopy. For any fireplace in which this appliance and canopy
are both installed, the mantel extensions and corresponding mantel clearances are as
shown in Figure 2. The mantel must lie in or above the dashed line shown in Figure 2. (The
mantel extension is the distance the mantel extends from the fireplace facing. The mantel
clearance is the distance from the fireplace opening to the bottom of the mantel.)
Any other combustible or noncombustible extension or trim extending from the fireplace
facing of any fireplace in which this appliance is installed must comply with (1) local codes
or, in the absence of local codes, with the latest edition of ANSI/NFPA 211 if the fireplace
is an at-site masonry solid-fuel burning fireplace, or (2) the instructions provided by the
fireplace manufacturer if the fireplace is a prefabricated factory-built solid-fuel burning
fireplace or is a listed ventless firebox enclosure.
CLEARANCE TO COMBUSTIBLES
Front:
No less than 36 inches from the face of the fireplace in which the appliance is
installed.
Mantel:
Must not extend more than 12 inches from the face of the fireplace and must be
at least 28 inches above the fireplace opening (unless a CABL/CABR fireplace canopy is
installed.) Figure 2
12”
12”
8”
2
1
/
2
”
10”
16”
18”
LG568
mantel clearances
11/08
28"
Mantel
Clearance
Mantel Extension
Mantel
Extensions
Canopy
Mantel
Clearances
LG568
Minimum Mantel Clearances with
CABL/CABR Canopy
Minimum Mantel Clearance
Figure 2
Mantel Clearances