20
70D0005
TPB Gas Log Set
ELECTRICAL WIRING (MILLI-VOLT)
CONNECTING REMOTE RECEIVER
1. Set remote receiver. See instructions included in receiver kit.
2. Connect the two (2) 1/4" female connectors to the TP/TH and TH terminals on the control valve.
Figure 18 -
Installing Remote Receiver
Remote
Receiver
Remote
Wire
Connectors
A. COMPLETE MILLI-VOLT SYSTEM CHECk
(“A” Reading - Thermostat contacts CLOSED - Control knob “ON” - Main burner should turn
ON)
a. If the reading is more than 175 milli-volts and the automatic valve still does not come on, replace
the control.
b. If the closed circuit reading (“A” reading) is less than 175 milli-volts, determine cause for low read-
ing, proceed to Section B below.
B. Thermopile Output Reading Check
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate,
then check pilot voltage, 500 milli-volts minimum. If the minimum milli-volt reading is not obtainable,
replace pilot.
CHECkING SYSTEM OPERATION
The milli-volt system and individual com-
ponents may be checked with a milli-volt
meter having a 0-1000 mV range. Con-
duct each check shown in chart below by
connection meter test leads to terminals
as indicated.
CHECk
TEST
TO TEST
CONNECT
METER LEADS
TO TERMINALS
SWITCH OR
THERMOSTAT
CONTACTS
METER
READING
SHOULD BE
A
COMPLETE
SYSTEM
2 & 3
CLOSED
MINIMUM 175
B
THERMOPILE
OUTPUT
1 & 2
OPEN
MINIMUM 500
Note: Heat reduces battery life. You can protect the receiver and extend battery life by mounting
receiver in wall or other location outside the fireplace.
Remote
Wire
Connectors
Valve
NOTICE
Do not let wires
touch grate or
burner.