Locate, the Qwik
Pure
TripleGuard
™ Air Purifier in the center of the air flow of the duct,
that is midway between the sides of the duct.
The Qwik
Pure
TripleGuard
™ must be installed into the ductwork in a location that
cannot be viewed by anyone during routine operation of the system or during air
filter changing.
LOOKING DIRECTLY AT AN ILLUMINATED UNIT WILL CAUSE
DAMAGE TO EYES
. The
GREEN LED
indicates the unit is powered and operating
properly and the two
ORANGE LED
s indicate each UV-C bulb is operating properly.
There is never a need to look at the UV-C bulbs during operation.
Step 4.
Install the Mounting Bracket
If the Qwik
Pure
TripleGuard
™ unit is to be installed against a sheet metal surface,
skip to Step 5.
If the Qwik
Pure
TripleGuard
™ is to be installed into duct board, then the mounting
flange must be installed first, to provide a solid anchoring method for the Qwik
Pure
TripleGuard
™ unit.
a.
Prepare to cut an opening in the duct board for insertion of the Qwik
Pure
TripleGuard
™ unit.
1.
Position and hold the mounting flange against the duct board (studs pointing
toward the duct board), and orient to preferred mounting point.
2.
Apply enough pressure to cause the mounting plate studs to dent/mark the
duct board to allow accurate holes to be created.
3.
Remove the mounting flange temporarily. Locate the stud marks and use a drill,
a sharp pointed object, or the threaded studs of the mounting flange to punch
the holes in the duct board for the flange mounting studs.
4.
Align the mounting plate studs with the created holes and insert until the
mounting plate is flush with the duct board.
5.
Cut an opening along the inside opening of the flange as shown in Figure 1.
Before cutting, ensure the Qwik
Pure TripleGuard
™ will fit in the planned
space.
b.
Insert the mounting flange through the opening in the duct board,
locate the
mounting flange on the inside of the duct board
, align the mounting flange
studs to holes, push studs through and bolt the mounting flange to the duct board
using the center
¼-20
threaded studs, washers and
¼-20
nuts. Use a wrench to
tighten both threaded fastners so the duct board is slightly compressed and the
mounting flange is secure.
Qwik
Pure
TripleGuard
™
Industrial-Grade Air Sanitizer
X
9.1"
Figure 1