38

UK | 9 Mounting

9.3 230 V electrical connection

PP 45 RC

 units  and 

RLS 45 O

 / 

RLS 45 K

 

controls are supplied with a 230 V mains volt-

age. Note the following safety instructions.

 

!

DANGER

Danger from electric shock. 

Before 

installing the electrics, shut down all supply 

circuits, switch off mains fuse, secure against 

being accidentally switched back on and 

position a visible warning sign. During oper-

ation, the board cover (PP 45 K and PP 45 

RC) and front cover of the internal housing 

must be mounted.

 

!

 

WARNING

Danger from burns/fire due to overload 

caused by incorrect connection or con-

necting too many units to an RLS 45 O/K.  

Connect units in accordance with wiring dia-

gram. Observe permissible number of venti-

lation units per room air control/power unit.

 

!

 

WARNING

Danger from electric shock if the 12V low 

voltage and 230 V are not disconnected 

or are insufficiently disconnected. 

Ensure 

a safety distance between 230 V and 12 V 

cables. Ensure minimum distance of 8 mm. 

 

!

 

WARNING

Danger of electric shock if the 230 V input 

of the PP 45 RC and the RLS 45 O/K con-

troller is incorrectly connected. 

Ensure a phase balance between all compo-

nents connected to the ventilation system.

 

!

 

WARNING

Danger of electric shock from installing 

the RLS 45 O/K inside the protective zone. 

No IP protection present (IP 00). 

The room 

air control may only be installed outside 

protective zones 0, 1 or 2. 

 

!

 

WARNING

Danger of electric shock if the ventilation 

units are installed within the protection 

zone.

 The units may only be installed in the 

specified protection zones in accordance with 

the IP degree of protection. Use 

PP 45 

only 

outside protections zones 0, 1 and 2. 

i

  When wiring several unit pairs/ventila- 

tion units, always use a deep/double  

recessed-mounted box (recessed-

 

mounted box provided by customer).

i

  Strip wires of connection cables suffi

-

ciently.

9.4  

PP 45 RC

 

Fitting slide-in module and 

internal cover

PP 45 RC

 units with 230 V.  

Note details in Chapter 9.3.

 

1.  Mount slide-in module and internal cover 

as described in Chapter 9.2, steps 1 to 11.

2.  Loosen screw for board cover, take off 

board cover. 

3.  Insert fan connection cable [9] directly on 

board. 

4.  Wire the 230 V power cable 

 Wiring 

diagrams in the appendix. 

5.  Fit board cover and screw down.
6.  Attach front cover of internal housing at 

top in two housing studs and swivel down 

until front cover engages on locking lever.

i

  Before putting on the front cover of 

the internal housing, the shutter must 

always be open. To do this, switch on 

PP 45 RC unit.

Содержание PushPull PP 45 O

Страница 1: ...steme Final mounting set instructions for PushPull ventilation system Notice de montage Gros uvre pour syst mes de ventilation PushPull UK FR PP 45 O PP 45 K PP 45 RC RLS 45 O RLS 45 K DS 45 RC F r Fa...

Страница 2: ...2...

Страница 3: ...3...

Страница 4: ...ss an USB Schnittstelle USB A Mini USB B Kabel verwenden Download mit QR Code oder unter www maico ventilatoren com Zubeh rkomponenten F r weiterf hrende Informationen zur Endmon tage von Zubeh rkompo...

Страница 5: ...en Anschl sse gem dem beigef gtem Verdrahtungsplan fachgerecht und sicher ausf hren k nnen und Risiken und Gef hrdungen durch Elektrizit t erkennen und vermeiden k nnen Weisen Sie nach erfolgreicher I...

Страница 6: ...n einheiten verursachen Es besteht Lebensge fahr zum Beispiel durch Kohlenstoffmonoxide L ftungsger t auf keinen Fall einsetzen wenn in der Nutzungseinheit eine raumluft abh ngige Feuerst tte an einer...

Страница 7: ...rieb ist nur mit Original Komponen ten zul ssig Ver nderungen und Umbauten an den Ger ten sind unzul ssig und entbinden den Herstel ler von jeglicher Gew hrleistung und Haftung Gefahr durch Stromschla...

Страница 8: ...abh ngigen Feuerst tten f r fl ssige oder gasf rmige Brennstoffe und der luftab saugenden Anlage durch Sicherheitseinrich tungen verhindert wird oder wenn die Abgasabf hrung der raumluft abh ngigen Fe...

Страница 9: ...nge 500 oder 800 mm Wandst rke min max 265 mm 490 bzw 790 mm Luftfilter au en Luftfilter innen G3 G2 F rdervolumen Ger t 42 m h Schutzklasse Schutzart II IP 00 Schalldruckpegel Abstand 1 m Freifeldbe...

Страница 10: ...RS 485 Bus K1 2 1 0 3 0 1 0 1 K2 3 1 0 3 0 1 0 1 K3 4 1 0 3 0 1 0 1 K4 5 1 0 3 0 1 0 1 K5 6 1 0 3 0 1 0 1 K6 1 1 0 3 0 1 0 1 K7 2 1 0 3 0 1 0 1 K8 3 1 0 3 0 1 0 1 K9 1 0 3 0 1 0 1 K10 2 0 3 0 1 0 1 K1...

Страница 11: ...K25 1 0 3 0 1 K26 2 0 3 0 1 K27 3 0 3 0 1 Zusatzfunktionen K25 Abluftbetrieb m glich bei 1x PPB 30 O RLS 45 O Zum Start die optionale Taste L ftungsstufe 2 Sekunden dr cken L ftungs ger t Sensor PP 4...

Страница 12: ...er PP 45 RC L ftungsger t Betriebsspannung f r PP 45 O K Ger te 12 V DC Geeignetes Befestigungsmaterial bauseitig bereitstellen Sensoren Fehlerhafte Messwerte bei un geeignetem Montageort St reinfl ss...

Страница 13: ...e 265 mm Einschub darf nicht aus Wandh lse hinausragen Die Profildichtung an der Au enseite des Einschubs dient zur Fixierung und Vermei dung von Fehlluft Die Motor Anschluss leitung darf in eingebaut...

Страница 14: ...Kompo nenten achten WARNUNG Gefahr durch Stromschlag bei Einbau der RLS 45 O K Steuerung innerhalb der Schutzzone Kein IP Schutz vorhanden IP 00 Installation der Raumluftsteuerung nur au erhalb der S...

Страница 15: ...LS 45 O oder RLS 45 K kann mit maximal 3 weiteren Leistungsteilen und oder baugleichen Slave Raumluftsteuerungen erweitert werden In einem PP 45 L ftungssystem lassen sich also maximal 4 Steuereinheit...

Страница 16: ...f r den Anschluss der Leitungen an der Raumluftsteuerung i Zus tzliche L ftungsger te sind bei Verwendung von Leistungsteilen PP 45 LT einsetzbar 4 Raumluftsteuerung in die UP Dose einset zen und mit...

Страница 17: ...gesetzt In funkgesteuerten Ger ten PP 45 RC wird der integrierte Feuchtesensor direkt in das L ftungsger t eingebaut F r Einbau und Ver drahtung eines externen Sensors Installati onsanleitung Einbau F...

Страница 18: ...folgt einschalten 1 Sicherstellen dass alle L ftungsger te und Systemkomponenten an den Raum luftsteuerungen angeschlossen sind 2 Warnschild am Sicherungskasten entfernen und Netzsicherung einschalten...

Страница 19: ...e LED den aktuell eingestellten Parameter Parameterwert ndern Hat man ein bestimmtes Untermen erreicht k nnen mit diesen Tasten die Parameter eingestellt werden Nach der nderung des Parameters blinken...

Страница 20: ...n1 Fan2 angeschlos senen Ger te ausgew hlt L ftungsstufen 1 2 L ftungsstufe 0 m glich L ftungsstufe 0 gesperrt Bei Einstellung L ftungsstufe 0 gesperrt k nnen die L ftungsger te an dieser Steuerung ni...

Страница 21: ...en kombiniert sind Zur Verf gung stehen der interne Sensor PP 45 HYI und die externen Sensoren PP 45 HY PP45 CO2 und PP 45 VOC ModBus Einstellungen 1 2 3 RS 485 inaktiv ModBus aktiv 9600 Baud ModBus a...

Страница 22: ...aar PP 45 oder 1 PPB 30 2 Ger tepaare PP 45 oder 2 PPB 30 3 Ger tepaare PP 45 oder 3 PPB 30 Ungerade Anzahl 3 Ger te PP 45 Ungerade Anzahl 5 Ger te PP 45 Hier wird die Anzahl der an der L fter schnitt...

Страница 23: ...n zul ssig 230 VAC Eingang 1 2 3 4 5 6 Einschlafmodus Sto l ftung Sicherheitsabschaltung Zuluftbetrieb ohne Nachlauf Zuluftbetrieb mit Nachlaufzeit 6 Min Zuluftbetrieb mit Nachlaufzeit 15 Min Zur Eins...

Страница 24: ...der RS 485 Schnittstelle angeschlossenen PPB30 K Ger te an ModBus Einstellungen 1 2 3 RS 485 inaktiv ModBus aktiv 9600 Baud ModBus aktiv 19200 Baud Mit diesem Einsteller wird der ModBus akiviert und d...

Страница 25: ...aktiv rote LED 1x Hier wird der interne Feuchtesen sor PP 45 HYI aktiviert Dieser Sensor ist optional nachr stbar nur im Masterger t und ist nicht im Lieferumfang enthalten Die orange Betriebs arten...

Страница 26: ...3x Reset Filterlaufzeit rote LED 4x Hier wird die Filterlaufzeit parametriert Werkseinstellung 6 Monate Die blaue Betriebs arten LED blinkt zyklisch je 4x Einzelraum l ftungs ger t 1 2 Paarweiser Betr...

Страница 27: ...1179 9200 4 Innenabdeckung komplett E059 1180 9000 5 Abdeckung Platinen PP 45 K PP 45 RC 0059 1182 0000 6 Einschub komplett E093 1425 0000 7 Ventilator komplett E093 1426 0000 8 Filterhalter 0059 117...

Страница 28: ...tilation unit 29 2 Specialist installer qualification 29 3 Intended use 29 4 Safety instructions and warnings 30 5 Standard application with a pair of units 32 6 Requirements of the installation site...

Страница 29: ...s and guidelines enables you to correctly and safely under take the electrical connections in accord ance with the wiring diagram provided and enables you to recognise and avoid risks and hazards asso...

Страница 30: ...connected to exhaust gas systems which themselves have multiple connections Risk of explosion Explosive gases and dusts may ignite and cause serious explosions or fire Never use ventilation unit in an...

Страница 31: ...edges e g stainless steel external covers Wear protective gloves Electric shock from water ingress if used in protection zones Units cont rols not suited for outdoor use Protect ventilation units cont...

Страница 32: ...ventilated fireplaces for liquid or gaseous fuels the fireplace or the ventilation system must be switched off if the safety device is triggered In the case of air ventilated fire places for solid fu...

Страница 33: ...kness min max 265 mm 490 or 790 mm Air filter outside Air filter inside G3 G2 Air volume unit 42 m h Protection class Degree of protection II IP 00 Sound pressure level distance 1 m free field conditi...

Страница 34: ...1 0 3 0 1 0 1 K3 4 1 0 3 0 1 0 1 K4 5 1 0 3 0 1 0 1 K5 6 1 0 3 0 1 0 1 K6 1 1 0 3 0 1 0 1 K7 2 1 0 3 0 1 0 1 K8 3 1 0 3 0 1 0 1 K9 1 0 3 0 1 0 1 K10 2 0 3 0 1 0 1 K11 3 0 3 0 1 0 1 K12 2 1 0 3 0 1 0...

Страница 35: ...3 0 3 0 1 Additional functions K25 Exhaust air mode possible with 1x PPB 30 O RLS 45 O To start press the optional ventilation level button for more than 2 seconds Ventilation unit sensor PP 45 RC PP...

Страница 36: ...t sunlight Disbalance may arise if the maximum stat ed cable lengths are exceeded Observe installation requirements relating to cable lengths and types 9 2 PP 45 O PP 45 K Fitting slide in module and...

Страница 37: ...when installed When sliding in the drawer ensure that the Oben Top sticker is facing upwards 11 Press fan connection cable into notch arrow so that it is fixed and not strained 12 With PP 45 O units 1...

Страница 38: ...nnected to the ventilation system WARNING Danger of electric shock from installing the RLS 45 O K inside the protective zone No IP protection present IP 00 The room air control may only be installed o...

Страница 39: ...K master room air control can have a maximum of 3 further power units and or slave room air controls of a similar design added to it A maximum of 4 control units can therefore be deployed in a PP 45 v...

Страница 40: ...LT power units 4 Insert room air control in the recessed mounted box and screw down to re cessed mounted box with 2 screws 5 Fit front panel Ensure that the sensor opening lies above the integrated P...

Страница 41: ...RLS 45 K 1 Install room air control as described before NOTICE Unit damage no function if the humidity sensor is installed incorrectly Do not bend pins Insert sensor up to stop in bush 2 Insert humidi...

Страница 42: ...and set the desired parameter value Addi tional information can be found in the online commissioning instructions download from www maico ventila toren com Here you can also download the com missionin...

Страница 43: ...button for 2 seconds The parameter value is now adopted The ventilation level LEDs light up perma nently again For PP45 RC 3 LEDs light up for a long period and go out Parameter value is adopted serv...

Страница 44: ...interface Fan1 Fan2 is selected here Ventilation levels 1 2 Ventilation level 0 possible Ventilation level 0 blocked With the ventilation level 0 blocked setting the ventilation units cannot be switc...

Страница 45: ...external sensors are connected combined The PP 45 HYI internal sensor and the PP 45 HY PP45 CO2 and PP 45 VOC external sensors are available ModBus settings 1 2 3 RS 485 inactive ModBus active 9600 b...

Страница 46: ...e pair PP 45 or 1 PPB 30 2 device pairs PP 45 or 2 PPB 30 3 device pairs PP 45 or 3 PPB 30 Odd number 3 devices PP 45 Odd number 5 devices PP 45 The number of units connected to the fan interface Fan1...

Страница 47: ...mode Intermittent ventilation Safety shutdown Supply air operation without overrun Supply air operation with overrun time of 6 min Supply air operation with overrun time of 15 min For setting an addi...

Страница 48: ...f PPB30 K units connected to the RS 485 interface here ModBus settings 1 2 3 RS 485 inactive ModBus active 9600 baud ModBus active 19200 baud This adjuster activates ModBus and sets the baud rate Noti...

Страница 49: ...nal humidity sensor is activated here This sen sor can be retrofitted as an option only in master unit and is not included in the scope of delivery The orange operating mode LED flashes three times pe...

Страница 50: ...lter runtime red LED four times Parameters for the filter run time are set here factory setting 6 months The blue operating mode LED flashes four times per cycle Single room ventilation unit 1 2 Opera...

Страница 51: ...rnal cover complete E059 1180 9000 5 PP 45 K PP 45 RC cover for boards 0059 1182 0000 6 Slide in module complete E093 1425 0000 7 Fan complete E093 1426 0000 8 Filter holder 0059 1176 0000 9 Honeycomb...

Страница 52: ...53 1 3 Appareil de ventilation PP 45 RC 53 2 Qualification de l installateur sp cialis 53 3 Utilisation conforme 53 4 Consignes de s curit et avertisse ments 54 5 Application standard par paires 57 6...

Страница 53: ...es en vigueur vous pouvez ex cuter de mani re comp tente et en toute s curit les branchements lectriques conform ment au plan de c blage fourni et si vous pouvez reconna tre et viter les risques et mi...

Страница 54: ...iples Le foyer d pendant de l air ambiant risque d amener des gaz d chappement dans d autres unit s d habitation ce qui repr sente un danger de mort d la pr sence de mo noxyde de carbone Ne jamais uti...

Страница 55: ...stallation erron e Si l appareil de ventilation n est pas mont correctement son exploitation peut tre non conforme Installer l appareil de ventilation uni quement conform ment aux directives de planif...

Страница 56: ...es d air ambiant qu apr s leur montage complet Avant de retirer le capot int rieur de l appareil de ventilation attendre l arr t des ventilateurs N utiliser les appareils de ventilation qu avec des fi...

Страница 57: ...emplacementdes filtres pr voir un espace de travail suffisant Ne pas percer les avant trous pour le mon tage des appareils et les points de fixation des capots ext rieurs et int rieurs dans les compos...

Страница 58: ...485 K1 2 1 0 3 0 1 0 1 K2 3 1 0 3 0 1 0 1 K3 4 1 0 3 0 1 0 1 K4 5 1 0 3 0 1 0 1 K5 6 1 0 3 0 1 0 1 K6 1 1 0 3 0 1 0 1 K7 2 1 0 3 0 1 0 1 K8 3 1 0 3 0 1 0 1 K9 1 0 3 0 1 0 1 K10 2 0 3 0 1 0 1 K11 3 0...

Страница 59: ...onctions suppl mentaires K25 Mode Air sortant possible pour 1x PPB 30 O RLS 45 O Pour d marrer appuyer sur la touche optionnelle Niveau de ventilation pendant 2 secondes Appareil de ventilation d tect...

Страница 60: ...usqu au point neutre Connecteur du c ble de ventilateur PP 45 O Connecter les raccords enfi chables apr s l introduction du c ble selon le plan de c blage PP 45 K PP 45 RC C bler l entr e de commande...

Страница 61: ...per age du capot int rieur Annexe i L unit de ventilateur le caloporteur c ramique et les logements de filtres avec les deux filtres air ont d j t ins r s dans le module d insertion de l appareil l us...

Страница 62: ...45 RC et commandes RLS 45 O RLS 45 K sont aliment s en 230 V Respectez les consignes de s curit suivantes DANGER Risque d lectrocution Avant de proc der aux installations lectriques couper tous les c...

Страница 63: ...profonde ou double bo te d encastrement fournir par le client i D nuder suffisamment les fils des c bles de raccordement 9 4 PP 45 RC Pose du module d insertion et du capot int rieur Appareils PP 45...

Страница 64: ...e puissance et ou commandes d air ambiant esclaves de m me type Un syst me de ventilation PP 45 autorise ain si l utilisation de 4 commandes d air ambiant au maximum i On ne peut combiner que des com...

Страница 65: ...i bution s par i Recommandation avec plus de 2 appareils de ventilation monter la commande d air ambiant dans une bo te d interrupteurs fournir par le client Celle ci est assez vaste pour permettre le...

Страница 66: ...ontage du d tecteur d humidit PP 45 HYI Dans les syst mes c bl s le d tecteur d humidit est int gr la commande d air ambiant RLS 45 O ou RLS 45 K Dans les appareils commande radio PP 45 RC le d tecteu...

Страница 67: ...rvice D marrer le syst me de ventilation comme suit S assurer que tous les appareils de ventilation et composants du syst me sont raccord s aux commandes d air ambiant Retirer le panneau d avertisseme...

Страница 68: ...indique le param tre actuellement s lectionn Modification de param tres D s qu un sous menu donn est atteint les param tres peuvent tre r gl s avec ces touches Les LED de niveau de venti lation cligno...

Страница 69: ...ntilateur Fan1 Fan2 est s lectionn ici Niveaux de ven tilation 1 2 Niveau de ventilation 0 possible Niveau de ventilation 0 bloqu En cas de r glage Niveau de ventilation 0 bloqu les appareils de venti...

Страница 70: ...combien de d tecteurs in ternes et externes sont raccord s com bin s Le d tecteur interne PP 45 HYI et les d tecteurs externes PP 45 HY PP 45 CO2 et PP 45 VOC sont disponibles R glages ModBus 1 2 3 RS...

Страница 71: ...P 45 ou 1 PPB 30 2 paires d appareils PP 45 ou 2 PPB 30 3 paires d appareils PP 45 ou 3 PPB 30 Nombre impair 3 appareils PP 45 Nombre impair 5 appareils PP 45 Le nombre d appareils raccord s l interfa...

Страница 72: ...230 VCA 1 2 3 4 5 6 Mode de mise en veille Ventilation par coups Coupure de s curit Mode Air entrant sans temporisation Mode Air entrant avec temporisation 6 min Mode Air entrant avec temporisation 15...

Страница 73: ...raccord s l interface RS 485 R glages ModBus 1 2 3 RS 485 inactive ModBus actif 9600 bauds ModBus actif 19200 bauds Ce module de r glage permet d activer le ModBus et de r gler le taux de transfert A...

Страница 74: ...cteur d humidit interne PP 45 HYI est activ ici Ce d tec teur peut tre install ult rieure ment en option seulement dans l appareil ma tre et n est pas fourni La LED orange de mode de fonctionne ment c...

Страница 75: ...e 4x La dur e d utilisation du filtre est param tr e ici r glage usine 6 mois La LED bleue de mode de fonctionne ment clignote 4x de fa on cyclique Appareil de ventilation pour pi ce individuelle 1 2...

Страница 76: ...et E059 1180 9000 5 Cache de protection des platines PP 45 K PP 45 RC 0059 1182 0000 6 Module d insertion complet E093 1425 0000 7 Ventilateur complet E093 1426 0000 8 Support de filtre 0059 1176 0000...

Страница 77: ...her dimensions Autres dimensions Komponente Component Composant Abmessungen BxHxT Dimensions WxHxD Dimensions lxhxp RLS 45 O RLS 45 K Raumluftsteuerung Room air control Commande air ambiant 80 x 80 x...

Страница 78: ...78 DE UK FR ANHANG APPENDIX ANNEXE Anschlussplan RLS 45 O PP 45 O Wiring diagram RLS 45 O PP 45 O Sch ma des connexions RLS 45 O PP 45 O...

Страница 79: ...venti lation au distributeur W F1 Fan 1 W F2 Fan 2 Steuerleitung Fan 1 Fan 2 Empfohlene Steuerleitung J Y ST Y 2x2x0 8mm Max L nge zum Verteiler 4 m Fan 1 Fan 2 Control cable Recommended control ca b...

Страница 80: ...80 DE UK FR ANHANG APPENDIX ANNEXE Anschlussplan RLS 45 K PP 45 K Wiring diagram RLS 45 K PP 45 K Sch ma des connexions RLS 45 K PP 45 K...

Страница 81: ...p les s par s UP L UP Verteiler Anschluss L ftungsger te Anschluss al ler L ftungsger te sternf rmig zum Verteiler Recessed mounted distri butor connection for ventila tion units connection of all ven...

Страница 82: ...82 DE UK FR ANHANG APPENDIX ANNEXE Anschlussplan RLS 45 O Systembus Wiring diagram for RLS 45 O system bus Sch ma des connexions RLS 45 O Bus syst me...

Страница 83: ...ilation 7 9 11 sur RLS esclave 1 Fan 4 1 4 3 L ftungsger t 8 10 12 an RLS Slave 2 Ventilation unit 8 10 12 on RLS slave 2 Appareil de ventilation 8 10 12 sur RLS esclave 2 Fan 5 1 5 3 L ftungsger t 13...

Страница 84: ...84 DE UK FR ANHANG APPENDIX ANNEXE Anschlussplan RLS 45 K Systembus Wiring diagram for RLS 45 K system bus Sch ma des connexions RLS 45 K Bus syst me...

Страница 85: ...ve 2 Ventilation unit 14 16 18 on RLS slave 2 Appareil de ventilation 14 16 18 sur RLS esclave 2 S1 Taster Schalter Zusatzfunktion Einschlaf Intensiv Zuluft betrieb Sicherheits Funktion Einbindung der...

Страница 86: ...ur Fan Bus W1 Anschlussleitung GLT ModBus Empfohlene Steuerleitung J Y ST Y 2x2x0 8 mm Max Leitungsl nge bis zum Gateway ca 100 m Parametrisierung und Adressierung mittels Service Mode oder IBS vorneh...

Страница 87: ...ontrol Appareil de ventilation PushPull 45 RC commande radio W1 Anschlussleitung Netz max zul ssiger Leitungs querschnitt 1 5 mm2 Empfohlener Leitungstyp NYM J 3 x 1 5 mm2 Mains connection cable max p...

Страница 88: ...88 DE UK FR 11 ANHANG APPENDIX ANNEXE...

Страница 89: ...11 ANHANG APPENDIX ANNEXE DE UK FR 89...

Страница 90: ...90 DE UK FR 11 ANHANG APPENDIX ANNEXE...

Страница 91: ...11 ANHANG APPENDIX ANNEXE DE UK FR 91...

Страница 92: ...0185 1213 0002_RLF 7_10 19_DSW AS 10 19_Es MAICO Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Germany Service 49 7720 6940 info maico de...

Отзывы: