Additional instructions for
sound-absorbing insert
Quick guide to fitting
sound-absorbing inserts:
ER-SE UP:
Article no. 0192.0678
ER-SE AP:
Article no. 0192.0679.
Supplement to mounting and
operating instructions
ER UP/Centro:
0185.0947.0012
(Article no. on back cover)
Specialist installer qualification
Mounting may only be carried out by
specialists who have the necessary
knowledge and experience in ventilation
engineering. The unit must be connected
in accordance with the "General building
approval".
Only a trained electrician is permitted to
work on the electrics. You are deemed a
trained electrician if you are familiar with
the relevant standards and guidelines,
can competently and safely connect units
to an electrical power supply in line with
the attached wiring diagram and are able
to recognise and avoid risks and dangers
associated with electricity on the basis of
your technical training and experience.
Safety instructions and
warnings
Warnings: Meaning
DANGER:
Indicates a possibly hazardous
situation which will result in death or serious
injuries if not avoided.
Danger of operating when
fan is not installed in its entirety.
Electric components are a potential
source of electric shock.
If the unit is open, all off the supply
circuits must be switched off (mains fuse
off), secured against being accidentally
switched back on and a visible warning
sign positioned.
Only operate the fan when it is
completely installed.
Do not cover the fan.
Risk of injury and health risk
in the event of changes or
modifications or if components which
are not permitted are used.
The unit may only be operated with
original components.
Changes and modifications to the units
are not permitted and release the
manufacturer from any guarantee
obligations and liability, e.g. if the housing
is drilled at a point which is not permitted.
Danger of electric shock.
Before removing the housing cover
and before installing the electrics, switch
off all supply circuits as well as the mains
fuse and secure them against being
accidentally switched back on again.
Attach a warning sign in a clearly visible
place.
Danger if the relevant regulations
for electric installations are not
observed.
Before removing the upper part of the
housing/fan insert and before installing the
electrics, switch off all supply circuits as
well as the mains fuse and secure them
against being accidentally switched back
on again. Attach a warning sign in a clearly
visible place.
Be sure to observe the relevant
regulations for electrical installation; e.g.
DIN EN 50110-1, in Germany this is
particularly VDE 0100, with the
corresponding parts.
A mains isolation device with contact
openings of at least 3 mm at each pole is
mandatory.
Only connect unit to permanently wired
electrical installation and with NYM-O or
NYM-J cables, depending on the unit
variant, 3x 1.5 mm² or 5x 1.5 mm².
The units may only be operated using
the voltage and frequency shown on the
rating plate.
Unit may also be energized even when
at a standstill and may be switched on
automatically by sensors (time delay,
humidity etc.) or by the thermo switch in
the motor winding. Maintenance and fault