8 Installation and commissioning

17

 Use ZM 11 mounting plate for rectangular

wall breakthroughs.

3. Lay power cable (flush-mounted) up to the in-

stallation location. For spacing, see figure Min-
imum distances.

7.2 Ceiling

1. Perform installation preparations as described

in the chapter Wall.

2. Prepare cover. Remove the cover before

drilling the housing. Drill cover with suitable
drill to avoid moisture and the formation of
bacteria in the fan housing.

NOTICE Danger of short-circuits and damage
to unit if condensation builds up in the fan
housing.

Thermally insulate ventilation ducts properly. Al-
low for a condensation drain or condensate col-
lector in the riser.

7.3 Duct

1. Deburr edges on the inside of the duct.

2. Perform installation preparations as described

in Chapter Wall.

7.4 Housing

NOTICE Damage to unit/functional problems
in the event of rubbing impeller.

Do not fit flange sleeve either twisted or crushed.
Make sure that the surface is flat.

1. Check rear of housing for the presence of a

sealing ring and check that it is properly posi-
tioned.

2.

ECA piano STANDARD, ECA piano TC:

 If

necessary, use auxiliary materials (e.g. foam
strip) for fixing in wall or duct. When doing so,
maintain a minimum distance of 20 mm to the
end of the socket! Do not tape over the attach-
ment of the shutters (arrow).

ECA piano H:

 Attach foam strip as described

above

. This is important so that the unit

cannot draw in air from the outside.

7.5 Preparations for operation with
speed controller

Only for ECA piano STANDARD. 
Not permissible for ECA piano TC and H mod-
els.

1. Remove shutters.

2.

STX

 speed controller from the Maico range of

accessories.

NOTICE The fan will stop and have functional
problems if the output voltage on the speed
controller is too low.

Observe information in the speed controller oper-
ating instructions. Always set the minimum speed
on the speed controller so that the motor starts
up again after a power failure.

 The technology used in the phase angle

controller may cause humming noises.

8 Installation and commissioning

8.1 Housing installation

NOTICE Damage to unit/functional problems
in the event of rubbing impeller.

Do not fit flange sleeve either twisted or crushed.
Make sure that the surface is flat.

1. Guide the power cable into the terminal com-

partment.

Содержание ECA piano

Страница 1: ...und Betriebsanleitung Installation and operating instructions Notice de montage et mode d emploi ECA piano STANDARD ECA piano TC ECA piano H Kleinraumventilatoren Small room fans A rateurs pour petite...

Страница 2: ...Inhaltsverzeichnis Deutsch 3 English 12 Fran ais 21...

Страница 3: ...r te bersicht 1 Geh use mit Motor 2 Platinentr ger 2 1 Klemmleiste ECA piano STANDARD 2 2 Timerplatine ECA piano TC 2 3 Feuchteplatine ECA piano H 3 Motordeckel 4 Abdeckung 5 Dichtring 6 Klappe 7 Fl g...

Страница 4: ...H 7 6 Technische Daten 7 6 1 Umgebungsbedingungen 7 6 2 Technische Datentabelle 7 7 Montagevorbereitungen 7 7 1 Wand 7 7 2 Decke 8 7 3 Rohr 8 7 4 Geh use 8 7 5 Vorbereitungen f r den Betrieb mit Drehz...

Страница 5: ...Ger t darf in folgenden Situationen auf kei nen Fall eingesetzt werden GEFAHR Entz ndungs Brandgefahr durch brennbare Materialien Fl ssigkeiten oder Gase in der N he des Ger ts In der N he des Ger ts...

Страница 6: ...r eine ausreichende Zuluftnachstr mung sorgen GEFAHR Gefahr durch Stromschlag bei Betrieb mit nicht komplett montiertem oder besch digtem Ventilator Vor dem Abnehmen des Elektronikabdeckung al le Vers...

Страница 7: ...olgt nach Unter schreiten des Schaltpunktes und anschlie endem Ablauf einer einstellbaren Nachlauf zeit Mit zus tzlichem Schalter S1 l sst sich der Ventilator manuell ausschalten Anschlussvariante 2 V...

Страница 8: ...ermisch isolie ren Kondenswasserableitung oder Kondensat sammler in der Steigleitung einplanen 7 3 Rohr 1 Kanten der Rohrinnenseite entgraten 2 Montagevorbereitungen wie in Kapitel Wand beschrieben vo...

Страница 9: ...Nachlauf zeit einstellen ab Werk ca 6 Minuten 9 00 Uhr ECA piano H Mit Potentiometer P1 die Nachlauf zeit einstellen ab Werk ca 12 Minuten 12 00 Uhr ECA piano H Mit Potentiometer P2 den Feuchte schal...

Страница 10: ...trofachkraft hinzu ziehen Reparaturen sind nur durch Elektro fachkr fte zul ssig St rung Ursache Ma nahmen Ventilator schaltet nicht ein Keine Netzspannung Pr fen ob die Netzsiche rung ausgefallen ist...

Страница 11: ...n 3 Motordeckel abnehmen 15 Umweltgerechte Entsorgung Das Ger t und auch die Verpackung enthalten wiederverwertbare Stoffe die nicht in den Rest m ll gelangen d rfen Entsorgen Sie die Verpa ckungsmate...

Страница 12: ...1 Housing with motor 2 Circuit board holder 2 1 Terminal block ECA piano STANDARD 2 2 Timer circuit board ECA piano TC 2 3 Humidity circuit board ECA piano H 3 Motor cover 4 Cover 5 Gasket 6 Shutter...

Страница 13: ...ta 16 6 1 Ambient conditions 16 6 2 Technical data table 16 7 Preparation for installation 16 7 1 Wall 16 7 2 Ceiling 17 7 3 Duct 17 7 4 Housing 17 7 5 Preparations for operation with speed controller...

Страница 14: ...in the following situ ations under any circumstances DANGER Risk of combustion fire from flammable materials liquids or gases in the vicinity of the unit Do not place any flammable materials liquids o...

Страница 15: ...on and position a visible warning sign Only operate the fan when it is completely in stalled Do not commission a damaged unit DANGER Danger if the relevant regula tions for electrical installations a...

Страница 16: ...nt 1 or manu ally light switch Note With a relative room humidity over the switching point the fan can no longer be switched off not even with the light switch The fan switches off when the room humid...

Страница 17: ...roperly posi tioned 2 ECA piano STANDARD ECA piano TC If necessary use auxiliary materials e g foam strip for fixing in wall or duct When doing so maintain a minimum distance of 20 mm to the end of th...

Страница 18: ...umidity switching point with potentiometer P2 Stop all the way to the left approx 50 r h 12 00 o clock see figure factory setting approx 70 Stop all the way to the right ap prox 90 r h 8 3 Final mount...

Страница 19: ...ed electrician Call on the services of a qualified electrician any time there is a fault Repairs should only be carried out by a qualified electrician Fault Cause measures Fan does not switch on No ma...

Страница 20: ...l The unit and the packaging contain parts that can be recycled and should not end up in the do mestic waste Dispose of the packaging material and the unit in an environmentally friendly way in compli...

Страница 21: ...pareil 1 Bo tier avec moteur 2 Porte platine 2 1 R glette de bornier ECA piano STAN DARD 2 2 Platine minuterie ECA piano TC 2 3 Platine humidit ECA piano H 3 Couvercle du moteur 4 Cache de protection...

Страница 22: ...26 6 2 Tableau de donn es techniques 26 7 Pr paratifs de montage 26 7 1 Mur 26 7 2 Plafond 26 7 3 Gaine ronde 27 7 4 Bo tier 27 7 5 Pr paration pour l utilisation avec r gulateur de vitesse 27 8 Monta...

Страница 23: ...e rectangulaire ou ronde branchement lectrique encastr Cet appareil est exclusivement r serv l usage domestique et similaires 4 Consignes de s curit 4 1 Consignes de s curit g n rales Ne jamais utilis...

Страница 24: ...T Risque de blessure et pour la sant en cas de modifications ou de transformations ou encore en cas d utilisation de composants non autoris s Le fonctionnement n est autoris qu avec des composants d o...

Страница 25: ...pour petite pi ce destin l vacua tion d air des locaux Version standard ECA piano avec grille int rieure fixe Marche Arr t par interrupteur d clairage ou interrupteur s par vitesse variable C ble d al...

Страница 26: ...andation en cas d utilisation des inter rupteurs lumineux connecter un condensateur X2 220 nF 250 V au fil neutre Le condensa teur est fournir par le client Stockage Stocker l appareil uniquement dans...

Страница 27: ...0 mm par rapport l extr mit du raccord Ne pas recouvrir l at tache des volets fl che ECA piano H positionner le ruban en mousse comme d crit pr c demment Ceci est important afin que l appareil n attir...

Страница 28: ...des volets 2 Activer le fusible secteur 3 Effectuer un test de fonctionnement 9 Utilisation ECA piano STANDARD Marche Arr t avec interrupteur d clairage ou in terrupteur s par les deux fournir par le...

Страница 29: ...alifi s Dysfonctionnement Cause mesures Le ventilateur ne se met pas en marche Pas de tension du sec teur Contr ler si le fu sible secteur fonctionne correctement Le cas ch ant l activer Le ventilateu...

Страница 30: ...ent r serv des lectriciens qualifi s 14 1 Enlever le cache de protection les crochets d arr t le couvercle du moteur 3 Couvercle du moteur 1 Retirer d abord le cache de protection dans le tiers inf ri...

Страница 31: ...brik GmbH Traduc tion du mode d emploi d origine en langue alle mande Sous r serve de fautes d impression d erreurs et de modifications techniques Les marques marques commerciales et marques d pos es...

Страница 32: ...Maico Elektroapparate Fabrik GmbH Steinbeisstr 20 78056 Villingen Schwenningen Deutschland Service 49 7720 6940 info maico de 0185 1111 0005_RLF 8_04 21_DSW AS...

Отзывы: