Magtrol AN 2000 C
Instruction Manual
Nº Function
Description
Activation
13 ANA GROSS
Makes the analog output follow the gross value (measured value + tare)
Low level
14 ZERO ANA
Puts the analog output to the zero state (0 V for 0-10 V, 4 mA for 4-20 mA)
Low level
15 ANA PEAK
Makes the analog output follow the peak value
Low level
16 ANA VALLEY
Makes the analog output follow the valley value
Low level
13 to 16 : FUNCTIONS ASSOCIATED WITH THE ANALOG OUTPUT
17 to 23 : FUNCTIONS FOR USE WITH A PRINTER VIA THE RS OUTPUTS
Nº Function
Description
Activation
17 PRINT NET
Prints the net value.
Falling edge
18 PRINT GROSS
Prints the gross value.
Falling edge
19 PRINT TARE
Prints the tare value.
Falling edge
20 PRINT SET1
Prints the setpoint1 value and its output status.
Falling edge
21 PRINT SET2
Prints the setpoint2 value and its output status.
Falling edge
22 PRINT SET3
Prints the setpoint3 value and its output status.
Falling edge
23 PRINT SET4
Prints the setpoint4 value and its output status.
Falling edge
24 to 25 : FUNCTIONS ASSOCIATED WITH THE SETPOINTS AND RS OUTPUTS
Nº Function
Description
Activation
24 FALSE SETPOINTS
Exclusively for instruments WITHOUT relays/transistors control outputs card.
Allows programming and operation of 4 setpoints.
Low level
25 RESET SETPOINTS
Exclusively for instruments with 1 or more setpoints programmed as "latched
setpoints" (That is, the setpoints that once energized remain on the ON status
although the alarm condition disappears). Deactivates the setpoints output.
Falling edge
26 to 28 : SPECIAL FUNCTIONS
Nº Function
Description
Activation
26 ROUND RS
The display value as sent via the RS output, includes no filtering or rounding.
Low level
27 ROUND BCD
Makes the BCD output follow the display value without rounding.
Low level
28 SEND ASCII
Transmission of the last four digits of the display to a remote serial indicator
model MICRA-S. By holding the pin to a low level, the display is continuously
sent at a rate of 1 message per second.
Low level
or
Falling edge