The HART Communicator now 
requests that the level float be 
set to the desired level upper trim 
point.  The second trim point can 
be any other level point but it is 
recommended that this point be 
as far away from the zero point as 
possible.  When the float is at this 
position, the transmitter will always 
report the digital value entered in 
the user chosen units.  The user 
must press OK when the float is at 
that position.

The transmitter will take several 
seconds to insure that the level 
signal has stabilized.  Once 
the measurement is stable, the 
procedure will continue without 
user intervention.  The HART 
communicator will then send 
the command to the transmitter 
to calculate the new Level gain 
calibration constant.

The HART Communicator will now 
request the user to enter the value 
at the high trim point.  The HART 
Communicator will display the 
last upper trim point, for example 
60 in, and the user will enter the 
new upper trim point, for example 
59.0 in.  The HART Communicator 
will now send this value to the 
transmitter.

When the transmitter has completed 
its calculation of the new Level gain 
calibration constant, it will reply to 
the HART Communicator.  Then the 
HART Communicator will inform the 
user that the level upper trim point 
has been trimmed.  Then the HART 
Communicator will inform the user 
that the upper level trim point has 
been trimmed.

The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Calibration screen.

The HART Communicator is now at 
the starting screen for the Full Level 
Trim.

Zero Temperature Trim

Starting at the Calibration screen, 
select the Zero Temper Trim 
procedure.  This procedure trims 
the Temperature digital value 
measurement at the reference value 
of the RTD (1000 ohms).

If the user selects Zero Temper 
Trim from the Calibration screen, 
this screen will appear reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press OK 
to continue.

This screen warns the user that 
proceeding will affect the sensor 
calibration.  The user must press 
OK when ready to proceed.

The HART Communicator now 
requests that the temperature 
be set to the desired 0 deg C 
temperature point.  If using a 
temperature simulator, adjust the 
simulator temperature to 0 deg C 
or if using a resistance box, adjust 
the resistance value to 1000 ohms.  
The user must press OK when the 
RTD or simulator is at the required 
value.

The transmitter will take about 
fifteen seconds to insure that the 
temperature signal has stabilized.  
Once the measurement is stable, 
the procedure will continue without 
user intervention.  The HART 
communicator will then send the 
command to the transmitter to 
calculate the new Temperature zero 
calibration constant.

When the transmitter has completed 
its calculation it will reply to the 
HART Communicator.  Then the 
HART Communicator will inform the 
user that the zero level point has 
been trimmed.

13

Содержание LTM-300 Series

Страница 1: ...81 488 0788 FAX 281 488 7080 EMAIL magtech isemagtech com www isemagtech com LTM 300 Series Magnetostrictive Level Transmitter Instruction Operation Manual 3902 Magnolia Road Pearland Texas 77584 Jan...

Страница 2: ...r Installation 3 3 1 Standalone Transmitter Installation 3 3 2 Recommended Wiring Single Loop 4 Section 4 Speci cations Page 4 0 Transmitter Electrical Speci cations 4 4 1 Transmitter Sensor Tube 4 Se...

Страница 3: ...hange and continuously activates the sensor in the tube The electronics in the housing process the changing signal and update an analog 4 20 mA output This analog output is precisely proportional to t...

Страница 4: ...e base to resolve sub microsecond timing increments The binary number equivalent to the microseconds of the echo travel time is written to an output D A Converter and subsequently converted to a 4 20...

Страница 5: ...ectronicshousingmountedatthebottomofthegageforeasyaccess THIS MUST BE SPECIFIED AT TIME OF PURCHASE Installation Note European The cable entry devices and blanking elements of unused apertures shall b...

Страница 6: ...gurations A single output version with only one variable that will output a 4 20 mA signal for level The second con guration is a transmitter tted with a second oat to provide a digital output for in...

Страница 7: ...elect Data not required Span Trim Move the oat to the 20mA mark 100 on the probe Using the arrow buttons input the correct distance from the zero point and then Select Level O set Enter the desired va...

Страница 8: ...ion Problems 6 2 Magnetic Interface 6 3Troubleshooting Power Supply Problems Never move a magnet in a perpendicular motion from along the sensor tube This will always leave a residual eld in the waveg...

Страница 9: ...as this could leave magnetic indentation in the sensor wire The LTM 300 level transmitter has an inductor located inside the bulkhead of the sensor tube During operation of the transmitter this induc...

Страница 10: ...d the Alarm type In addition this screen presents the procedure to select the Primary variable PV if the transmitter is con gured with both Level and Interface It also displays the menu that will allo...

Страница 11: ...t are not normal Any status items not reported are within the normal range of operation or calibration The HART Communicator issues a command to receive the results of the transmitter diagnostics Duri...

Страница 12: ...xited if the user selects End The example shows the user selection 4mA The user must press ENTER before the procedure continues When the user selects the Loop test option the HART Communicator display...

Страница 13: ...output to 4 000mA the user is to enter the reference meter reading For example if the meter actually reads 4 234mA that value is input with the keypad The user must press ENTER when the current value...

Страница 14: ...matic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Zero Level Trim Full Level Trim Starting at...

Страница 15: ...now be returned to automatic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Full Level Trim Zero...

Страница 16: ...ed Once the measurement is stable the procedure will continue without user intervention The HART communicator will then send the command to the transmitter to calculate the new Temperature zero calibr...

Страница 17: ...t Value for 4mA and 20mA by Keypad If you desire to change the Level value at which the Current output is 4mA and 20mA when the Level is the selected Primary Variable or change the Interface value at...

Страница 18: ...g the edit box to continue with the reranging of the transmitter On returning to the Keypad rerange screen the values shown for LRV and URV are the changes that the user has made The user should check...

Страница 19: ...pper range value getting an update of the digital reading from the transmitter or leaving the 20mA range point as it was If the user accepts the measurement value as the 20mA loop current point the HA...

Страница 20: ...h is set in the factory when the unit is prepared for shipment The probe length is used as a reference for a number of diagnostics fuctions as well as setting the URL and LRL shown on the Keypad reran...

Отзывы: