Starting at the Calibration 
screen, select the Zero Level 
Trim procedure.  This procedure 
trims the Level digital value 
measurement at the position that 
the user desires to be the zero 
reference position.

If the user selects Zero Level 
Trim from the Calibration screen, 
this screen will appear reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press OK 
to continue.

This screen warns the user that 
proceeding will affect the sensor 
calibration.  The user must press 
OK when ready to proceed

The HART Communicator now 
requests that the level float be set 
to the desired zero level trim point.  
When the float is at this position, 
the transmitter will always report 0 
in the user chosen units.  The user 
must press OK when the float is at 
that position.

Zero Level Trim

The transmitter will take several 
seconds to insure that the level 
signal has stabilized.  Once 
the measurement is stable, the 
procedure will continue without 
user intervention.  The HART 
communicator will then send 
the command to the transmitter 
to calculate the new Level zero 

calibration constant.

When the transmitter has 
completed its calculation it will reply 
to the HART Communicator.  Then 
the HART Communicator will inform 
the user that the zero level point 
has been trimmed.

The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Calibration screen.

The HART Communicator is now 
at the starting screen for the Zero 
Level Trim.

Full Level Trim

Starting at the Calibration 
screen, select the Full Level Trim 
procedure.  This procedure trims 
the Level digital value measurement 
at two points.  The first point is the 
position that the user desires to be 
the zero reference position.  The 
second point is a Level position 
near the end of the sensor.

If the user selects Full Level Trim 
from the Calibration screen, this 
screen will appear reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press 
OK to continue.

This screen warns the user that 
proceeding will affect the sensor 
calibration.  The user must press 
OK when ready to proceed.

The HART Communicator now 
requests that the level float be set 
to the desired zero level trim point.  
When the float is at this position, 
the transmitter will always report 0 
in the user chosen units.  The user 
must press OK when the float is at 
that position.

The transmitter will take several 
seconds to insure that the level 
signal has stabilized.  Once 
the measurement is stable, the 
procedure will continue without 
user intervention.  The HART 
communicator will then send 
the command to the transmitter 
to calculate the new Level zero 
calibration constant.

When the transmitter has 
completed its calculation it will reply 
to the HART Communicator.  Then 
the HART Communicator will inform 
the user that the zero level point 
has been trimmed.

12

Содержание LTM-300 Series

Страница 1: ...81 488 0788 FAX 281 488 7080 EMAIL magtech isemagtech com www isemagtech com LTM 300 Series Magnetostrictive Level Transmitter Instruction Operation Manual 3902 Magnolia Road Pearland Texas 77584 Jan...

Страница 2: ...r Installation 3 3 1 Standalone Transmitter Installation 3 3 2 Recommended Wiring Single Loop 4 Section 4 Speci cations Page 4 0 Transmitter Electrical Speci cations 4 4 1 Transmitter Sensor Tube 4 Se...

Страница 3: ...hange and continuously activates the sensor in the tube The electronics in the housing process the changing signal and update an analog 4 20 mA output This analog output is precisely proportional to t...

Страница 4: ...e base to resolve sub microsecond timing increments The binary number equivalent to the microseconds of the echo travel time is written to an output D A Converter and subsequently converted to a 4 20...

Страница 5: ...ectronicshousingmountedatthebottomofthegageforeasyaccess THIS MUST BE SPECIFIED AT TIME OF PURCHASE Installation Note European The cable entry devices and blanking elements of unused apertures shall b...

Страница 6: ...gurations A single output version with only one variable that will output a 4 20 mA signal for level The second con guration is a transmitter tted with a second oat to provide a digital output for in...

Страница 7: ...elect Data not required Span Trim Move the oat to the 20mA mark 100 on the probe Using the arrow buttons input the correct distance from the zero point and then Select Level O set Enter the desired va...

Страница 8: ...ion Problems 6 2 Magnetic Interface 6 3Troubleshooting Power Supply Problems Never move a magnet in a perpendicular motion from along the sensor tube This will always leave a residual eld in the waveg...

Страница 9: ...as this could leave magnetic indentation in the sensor wire The LTM 300 level transmitter has an inductor located inside the bulkhead of the sensor tube During operation of the transmitter this induc...

Страница 10: ...d the Alarm type In addition this screen presents the procedure to select the Primary variable PV if the transmitter is con gured with both Level and Interface It also displays the menu that will allo...

Страница 11: ...t are not normal Any status items not reported are within the normal range of operation or calibration The HART Communicator issues a command to receive the results of the transmitter diagnostics Duri...

Страница 12: ...xited if the user selects End The example shows the user selection 4mA The user must press ENTER before the procedure continues When the user selects the Loop test option the HART Communicator display...

Страница 13: ...output to 4 000mA the user is to enter the reference meter reading For example if the meter actually reads 4 234mA that value is input with the keypad The user must press ENTER when the current value...

Страница 14: ...matic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Zero Level Trim Full Level Trim Starting at...

Страница 15: ...now be returned to automatic control After the user presses OK the HART Communicator returns to the Calibration screen The HART Communicator is now at the starting screen for the Full Level Trim Zero...

Страница 16: ...ed Once the measurement is stable the procedure will continue without user intervention The HART communicator will then send the command to the transmitter to calculate the new Temperature zero calibr...

Страница 17: ...t Value for 4mA and 20mA by Keypad If you desire to change the Level value at which the Current output is 4mA and 20mA when the Level is the selected Primary Variable or change the Interface value at...

Страница 18: ...g the edit box to continue with the reranging of the transmitter On returning to the Keypad rerange screen the values shown for LRV and URV are the changes that the user has made The user should check...

Страница 19: ...pper range value getting an update of the digital reading from the transmitter or leaving the 20mA range point as it was If the user accepts the measurement value as the 20mA loop current point the HA...

Страница 20: ...h is set in the factory when the unit is prepared for shipment The probe length is used as a reference for a number of diagnostics fuctions as well as setting the URL and LRL shown on the Keypad reran...

Отзывы: