Introduction / Description 

 

The Model IP-80 is a current-to-pressure transducer with bias offset and volume / pressure booster, dual air filters, 
20 psi reference regulator all enclosed in a compact single cabinet. 
 
 

Installation 

 

The wall mounted unit is factory set in the upright position so that 4 to 20 madc produces 0 to 80 psi output.  Other 
mountings will require zero and span adjustment.  The IP-80 should be located as close as possible to the clutch / 
brake and oversized lines to the clutch / brake must be avoided.  Long, large diameter lines limit system response 
since a large volume must be filled to change the pressure.  Avoid undersized fittings that will limit flow and cause 
pressure drop downstream of the IP-80. 

 

Input air is supplied through a ¼ npt female bulkhead connector on the bottom of the cabinet, which distributes it to 
the reference regulator, filters and the volume / pressure booster.  Normal shop air is sufficient, but an oil and water 
absorption filter for supply air is recommended if air quality is unknown.  Input pressure must be 5 psi greater than 
the maximum output pressure and must also be between 35 and 250 psi.  Input pressure above 250 psi can 
damage the unit.  The outlet port is also a ¼ npt female bulkhead connector and also located on the bottom of the 
cabinet. 

 

Electrical connections (2 wires) are made through a 7/8 in. cutout on the bottom of the cabinet.  Connect positive 
lead to black wire, and connect negative lead to white wire. 
 

Adjustment 

(Not normally required, since unit is adjusted at the factory.) 

 

The zero and span adjustments are born accessible when the cabinet door is open.  Both adjustments are located 
on I/P transducer’s front side.  Zero adjust is accomplished by adjusting one of the balance springs, and span is 
adjusted electronically by a simple trim pot adjustment.  The transducer is factory tested and set at 0 to 80 psi 
output in the vertical position.  A slight adjustment of zero and span may be required after shipping.  Units mounted 
other than perpendicular (to the base) will require a larger zero adjustment.  The transducer may be adjusted as 
follows: 

 

1.  Introduce a supply pressure to the inlet port greater than 85 psi. 
2.  Attach the current source to the terminals and adjust for 8 madc. 
3.  Read the output pressure and set the zero screw at the back of the transducer for a reading of 20 psig. 
4.  Switch the input signal to 20 madc and adjust span adjustment for a reading of 80 psig. 
5.  Switch back to an 8 madc input signal and reset the zero screw for a 20 psig reading. 
6.  Work back and forth from low to high signal and adjust to 20 and 80 psig several times until the low reading is 

20 psig and the high reading is 80 psig, when the input signal is switched from low to high. 

 
 

 