14
CONTROL PANEL
The CANplus® 600 (CP600™) control panel is an economical platform to monitor and control electronically governed
diesel engines. Graphical gauge pages or a single large analog gauge are displayed on the 4.25 in (107.95 mm)
diagonal LCD. Virtually any SAE J1939 parameter reported by the ECU (Engine Control Unit) can be displayed
including RPM, coolant temperature, oil pressure, engine hours, voltage and diagnostic codes. The trans-reflective,
backlit display is clearly readable in both bright sunlight as well as total darkness and is housed in a rugged IP67
rated housing.
Current alarm conditions are displayed in plain language on pop-up messages and can be viewed in the alarm list.
Various diagnostic screens allow detailed investigation of the CANbus data stream. By accessing the “Configuration”
menu, users can customize displayed data to show metric or US units, display language and various other parameters
such as the full-scale reading of gauges.
Five buttons access a context dependent button bar
when any button from 1 to 4 is pressed. The graphical menu
structure uses easily understood icons to indicate the button’s current function. After five seconds of inactivity, the
button bar disappears.
Note:
Most problems with electronically controlled engines can be pinpointed via ECU diagnostic messages. Use
the display or ECU diagnostic tool to view fault codes. Engine state information and diagnostic codes displayed by
the CANplus display are provided via the CANbus.
THROTTLE CONTROL
The standard ramp throttle
uses a momentary rocker switch to adjust the integral throttle control. All throttle commands
are sent directly to the engine using CANbus throttle control.
Button 1
Button 2
Button 3
Button 4
Button 5
Analog Gauge
Pages
Repeated presses
cycle through four
pages of analog
gauges (16 total)
Digital Gauge
Pages
Repeated presses
cycle through four
pages of digital
gauges (16 total)
Single Analog
Gauge
Repeated presses
cycle through avail-
able analog
gauges.
Active Alarm Page
Displays active
alarms including a
plain language
description.
Gauge Adjust
Configures the
parameters dis-
played by gauge
pages.
(Quad Adjust must
be enabled.)