20 

©2013 Magnum Energy, Inc.

5.0 Operation

CHANGE Button

This button scrolls through the selections available under each menu heading. 

Each menu restarts if you missed the desired selections, so if a selection is 

bypassed simply continue to press the MENU button until the desired selec-

tion reappears.

HOME Button

Hold down the HOME button for two seconds to return to the Home screens.

Info:

 The MENU/HOME button can be used to reset the remote by 

pressing and holding it down for 10 seconds. This is useful if the 

display shows unrecognizable letters or symbols.

HOLD Button

Hold down this button for two seconds to stop the Home screens from scroll-

ing. Hold down again to restart the scrolling of the Home screens.

Info:

 All adjustable inverter/charger settings in the ME-MR are saved 

in non-volatile memory and are preserved until changed—even if 

an inverter reset is performed (see Section 6.2), or if all power to 

the remote or inverter is removed.

Info:

 The ME-MR remote is only used to control an inverter. In 

order to control or display a Magnum Energy accessory, you need 

to use a ME-RC50 or ME-ARC50 remote control. Please refer to the 

particular remote control owner’s manual on the Magnum Energy 

website at www.magnumenergy.com for further information on 

displaying accessories.

5.2 

Operating the Inverter/Charger

Turning the inverter on 

– Press the ON/OFF button to activate the inverter. 

The inverter will either search for a load—using very little power from the bat-

teries—if in Search mode (see Figure 5-5), or will be actively inverting—using 

power from the batteries to power the AC loads (see Figure 5-3). The green INV 

LED is on when the inverter is actively inverting, and 

fl

 ashes when searching.

Turning the inverter off 

– While the inverter is actively inverting or search-

ing, the ON/OFF button can be pressed to switch the inverter function off, and 

this will turn the green INV LED off (see Figure 5-4).

Inverter Standby 

– The inverter is in standby when it is active (green INV 

LED is on) and the remote shows a charge status due to an external AC power 

source (utility/shore or generator) passing through the inverter to power the 

AC loads. During normal operation, the AC loads are powered by the external 

AC power source. However, if a blackout or brownout condition occurs the 

inverter senses these conditions, transfers to Inverter mode, and then powers 

the AC loads connected to the inverter.

CAUTION:

 If you have critical loads and are in Inverter Standby, do 

not press the ON/OFF button to turn the inverter off. If the green INV 

LED is off, inverter power will NOT be available to run your critical loads 

should the external AC power be interrupted.

Equalize charging 

– Equalizing is a controlled overcharge performed after 

your 

fl

 ooded (or AGM1 type) batteries have been fully charged. It mixes the 

battery electrolyte (to reverse strati

fi

 cation) and removes sulfation that may 

have built up on the plates. These conditions, if left unchecked, reduce the 

overall capacity of the battery.

Содержание ME-MR

Страница 1: ...Owner s Manual for Revision 1 1 or higher ME MR Remote Control...

Страница 2: ...th of the user or other persons may be endangered Copyright Notice Copyright 2013 by Magnum Energy Inc All rights reserved Permission to copy distribute and or modify this document is prohibited witho...

Страница 3: ...important points of the main text Remedy This symbol provides possible solutions for related is sues Product Safety Alerts All electrical work must be performed in accordance with local state and fede...

Страница 4: ...8 Power Save Menu 13 3 2 9 Equalize Menu 14 3 2 10 Charger Standby Menu 15 3 2 11 Power On Menu 15 3 2 12 TECH Menu 16 4 0 Menu Map ME MR Remote Control 18 5 0 Operation 19 5 1 Front Panel 19 5 1 1 L...

Страница 5: ...16 Figure 3 13 TECH Menus 17 Figure 4 1 ME MR Remote Menu Map 18 Figure 5 1 ME MR Front Panel Controls and Indicators 19 Figure 5 2 Inverter Standby Mode 21 Figure 5 3 Inverting Mode 21 Figure 5 4 Off...

Страница 6: ...ng 36 List of Figures Cont Figure 5 25 No Communication 30 Figure 5 26 Overcurrent Fault 31 Figure 5 27 Overtemp Fault 31 Figure 5 28 Stuck Relay Fault 32 Figure 5 29 Tfmr Overtemp Fault 32 Figure 5 3...

Страница 7: ...play LED Indicators SAVE HOLD Button ON OFF CHANGE Button MENU HOME Button The ME MR is equipped with the following features LED Indicators The at a glance LEDs provide a quick indication of the inver...

Страница 8: ...a smooth bend radius and do not become kinked If installing this remote in a boat RV or truck ensure the conductors passing through walls bulkheads or other structural members are protected to minimi...

Страница 9: ...selecting the desired location for flush mounting the remote cut out a square mounting hole measuring 2 x 2 see Figure 2 1 Place the remote into the cutout and then use the remote to mark and pre dri...

Страница 10: ...charger This 25 cable is a 4 wire telephony standard with RJ11 connectors on each end A standard telephone cable with 4 conductors may be substituted if the provided remote cable cannot be used 2 Conn...

Страница 11: ...how inverter status DC voltage and current and any fault present if ap plicable after 30 seconds if no buttons have been pressed Info When the left facing arrow symbol is shown on the display it indic...

Страница 12: ...ing to match the current rating of the utility power or the generator s circuit breaker If using multiple AC sources utility and generator through an AC transfer switch adjust this setting to the smal...

Страница 13: ...level setting while the inverter is searching the inverter will start inverting to provide full voltage on its output Should I use the Search Watts feature If the inverter can spend a great deal of ti...

Страница 14: ...rve capacity in minutes Amp hour AH capacity is a measurement of how many amps a battery can deliver for a specified length of time usually 20 hrs until the voltage achieves 1 75 VDC cell at 80 F Rese...

Страница 15: ...s are connected together which means they are connected in parallel The amp hours of each battery connected in parallel are added together 125 AH 125 AH 125 AH 375 AH but the voltage of the battery ba...

Страница 16: ...hot Table 3 3 Battery Type to Charge Voltages Battery Type Inverter Voltage Absorption Voltage Float Voltage Equalization Voltage GEL 12 VDC 14 1 VDC 13 6 VDC 14 1 VDC1 24 VDC 28 2 VDC 27 2 VDC 28 2 V...

Страница 17: ...is usually used when the objective is to charge the batteries as quickly as possible i e 400 AH 5 80 amp maximum charge rate A lower rate such as C 20 is used when the batteries need to be charged as...

Страница 18: ...ightly but not discharge them more than 20 the LBCO setting should be set to 11 VDC 12 volt models 22 VDC 24 volt models or to 44 VDC 48 volt models In some applications such as installations in an of...

Страница 19: ...setting when the AC source is well regulated and you are operating devices that are sensitive to voltage fluctuations Use the 80 VAC or lower setting 60 VAC when the AC source may have significant flu...

Страница 20: ...Disabled Range Disabled Request EQing What is equalizing Equalizing is a controlled overcharge of the batteries During this process there will be excessive gassing of the batteries This condition is n...

Страница 21: ...Chg Load Support AAC LS AAC Load Support VDC LS VDC Figure 3 11 Charger Standby Selections 3 2 11 Power On Menu POWER ON Select whether to have the inverter power up and provide AC power automaticall...

Страница 22: ...y Ext Ctrl Magnum has an open protocol policy that allows certain functions AC In Charge Rate VAC Dropout settings of the inverter charger to be controlled externally such as with a third party commun...

Страница 23: ...SETUP SETUP Unlock Defaults This menu restores all settings on the ME MR and in the in verter charger to the original factory default settings To restore press and hold the SAVE HOLD button for 5 seco...

Страница 24: ...equalize Export models Range 110VAC 150VAC 190VAC Default 150VAC AC IN 5 Amps AC IN 15 Amps AC IN 30 Amps AC IN 50 Amps SEARCH Off SEARCH 5 Watt SEARCH 20 Watt BAT AHRS 200 AH BAT AHRS 400 AH BAT AHR...

Страница 25: ...play is used for setting up the system operation as well as viewing the current operating status or any fault condition that may occur This display has two lines of alphanumeric characters and feature...

Страница 26: ...The inverter will either search for a load using very little power from the bat teries if in Search mode see Figure 5 5 or will be actively inverting using power from the batteries to power the AC loa...

Страница 27: ...s of the inverter charger Inverter Mode Charger Mode Fault Mode 5 3 1 Inverter Mode Messages The inverter charger is in Inverter mode when connected to a battery bank and AC power shorepower utility o...

Страница 28: ...harging During this stage the DC charging current decreases as the battery becomes charged This Charge stage continues until the absorb charging time determined by the Battery Amp Hours setting is fin...

Страница 29: ...ndby Mode The charger is disabled to prevent any charging but the AC power to the AC input is still available on the AC output Info Press the CHANGE button to turn the charger on See Section 3 2 10 fo...

Страница 30: ...avily used batteries should be equalized anywhere from x1 mo to 1 2x year Others only recommend it when the cells have a low specific gravity or when the difference between any individual cell has a s...

Страница 31: ...hours Float Charging the charger turns off and Full Chg displays charger is now in Battery Saver mode If the battery voltage drops to 12 6 12 volt models 25 2 24 volt models or 50 4 48 volt models th...

Страница 32: ...ort VDC feature operates in parallel with the AC input to support the inverter loads and is only available on MSH Series inverter chargers This feature is only active in Bulk Absorb Float or EQ Charge...

Страница 33: ...curs for longer than 10 seconds the unit shuts down and requires a manual restart Remedy This fault occurs because the connected AC loads are larger than the inverter s output capacity there is a wiri...

Страница 34: ...should be very close 0 5 VDC difference If not check to ensure all connections are tight and the fuse circuit breaker between the inverter and battery bank is good This fault automatically clears whe...

Страница 35: ...ision and model Remedy This fault usually occurs when an external DC source is charging the inverter s battery bank Turn off any other additional charging source to allow the DC voltage level to drop...

Страница 36: ...ny information from the inverter Remedy Reset the remote by disconnecting the remote commu nications cable from the inverter for 5 seconds and then reconnect it see Figure 2 3 If the fault continues f...

Страница 37: ...6 2 OvrCurnt appears on the LCD and the FAULT red LED is on The INV green LED is off FAULT OvrCurnt Figure 5 26 Overcurrent Fault What if the cable is not the issue Try another remote display Disconne...

Страница 38: ...t occurs often ensure the inverter is in a cool location has adequate ventilation and the internal cooling fans are operational FAULT StkRelay StkRelay appears on the LCD and the FAULT red LED is on T...

Страница 39: ...ault with the other inverter is corrected Stack Phase Fault 1 The AC input wiring is incorrect or 2 One phase was lost from the AC input source or 3 One of the inverter s internal transfer relays is b...

Страница 40: ...er on and to verify the fault has cleared If the internal fault remains the inverter may require repair at an authorized service facility FAULT CHARGER CHARGER appears on the LCD and the FAULT red LED...

Страница 41: ...ch Watts setting FAULT red OFF Normal operation ON A fault condition has been detected check the LCD display to find and correct the cause 5 3 4 LED Indicator Guide The remote provides the following L...

Страница 42: ...ade The remote is not getting sufficient power from the inverter Ensure the inverter batteries are connected and the inverter is operating correctly The inverter should be able to invert and power AC...

Страница 43: ...lk or Absorb Check the DC amps meter and the DC voltmeter on the ME MR display It should be 80 or more of rated charge current if the battery voltage is under 14 0 VDC 28 0 VDC on 24 volt models or 48...

Страница 44: ...Charging Inverting Status LED comes on and flashes rapidly 3 Once the rapid flashing has begun release the Power ON OFF pushbutton The Status LED will go off after the pushbutton is released 4 Press...

Страница 45: ...t the time the original purchaser returns the product for repair determined by the price paid by the original purchaser Magnum Energy shall not be liable for any other losses or damages 4 Upon request...

Страница 46: ...com If returning your product directly to Magnum for repair you must 1 Return the unit in the original or equivalent shipping container 2 Receive a Return Materials Authorization RMA number from the f...

Страница 47: ...Magnum Energy Inc 2211 West Casino Rd Everett WA 98204 Phone 425 353 8833 Fax 425 353 8390 Web www magnumenergy com PN 64 0031 Rev D...

Отзывы: