©2013 Magnum Energy, Inc.
17
3.0 Setup
Table 3-4, ME-MR’s Inverter/Charger Default Settings
Menu
Default Setting
AC In
AC IN = 30 Amps
Search Watts
SEARCH = 5 Watt
Battery Amp-Hours
BAT AHRS = 400 AH
(Absorb Time = 90 min.)
Battery Type
BAT TYPE = Flooded
Charge Rate
CHG RATE = 100%
Low Battery Cut Out
LBCO = 10 VDC (12-volt models),
20 VDC (24-volt models),
40 VDC (48-volt models)
Low VAC Dropout
VAC DROP = 80 VAC (150 VAC for export)
Power Save
PWR SAVE = On (15 min.)
Equalize
EQUALIZE = Disabled
Charger Standby
CHARGER = No AC In
(Charger Standby is off, will automatically
charge when AC is connected)
Power On
POWER ON = Norm
TECH: SETUP
SETUP = Unlock
Defaults:
This menu restores all settings on the ME-MR (and in the in-
verter/charger) to the original factory default settings. To restore, press
and hold the SAVE/HOLD button for 5 seconds (see Figure 4-1). After
the default settings have been restored, the display will show “
Loaded
”.
The ME-MR factory defaults are listed in Table 3-4.
Figure 3-13, TECH Menus
Press the ON/OFF button to
to view TECH menus
TECH menus are “read only”
displays, no changes can be
made to these screens*/**
To scroll next
screen:
press
press
ON/OFF
CHANGE
MENU
HOME
* Press and hold the SAVE/HOLD button to restore defaults
**Press the SAVE/HOLD button to select
Lock
or
Unlock
TECH
Press ON
Bat Temp
xx C
Xfm Temp
xx C
FET Temp
xx C
Inverter
Rev x.x
Model
xxxxxx
Ext Ctrl
No
SETUP
**
Lock
Remote
Rev 1.1
Defaults*
5.0 secs