6

Tuffy Liquid Level Control with Pneumatic Switch

2.3

Preventive Maintenance

Periodic inspections are a necessary means to keep your
Magnetrol level control in good working order. This control
is a safety device to protect the valuable equipment it serves.
A systematic program of preventive maintenance should be
implemented when the control is placed into service. Based
on utilizing a preventative maintenance program and
observing the following section on “what to avoid”, your
Tuffy will provide reliable protection of your capital equip-
ment for many years.

WHAT TO AVOID

1. Use only the 2" wrench flats to install or remove the unit.

Refer to Figure 1. Use of any other surface could change the
calibration. The valve body is calibrated at the factory and
locked in place.

2. NEVER attempt to make adjustments without reading the

instructions carefully. When in doubt, consult the factory or
your local representative.

3. NEVER use in systems which have excess iron particles in

the solution. The magnet at the counterweight end of the
float can attract the particles which could cause the float rod
to jam.

2.4

Troubleshooting

If Tuffy fails to shut off or turn on inlet air:

1. Check float for full range of travel; clicking of mechanism

should be heard.

2. If the complete Tuffy mechanism operates properly when

removed from service, check to be certain that liquid is
entering the storage tank or vessel. A valve may be closed
or a pipe line clogged.

3. If the float is determined to be filled with liquid or is

collapsed, the entire level switch must be replaced. Do
not attempt to repair the float.

4. The factory calibration setting should not require any

adjustment in the field. Check to see that the unit is
installed properly with the serial number tag positioned
on the top of the unit. If the unit is still not operating
correctly, please contact the factory.

NOTE: When in doubt about the condition or performance of a

control, please contact the factory for assistance.

Содержание Tuffy 039-6000-100

Страница 1: ...Side Mounted Float Level Switch Tuffy Liquid Level Controls with Pneumatic Switch Installation and Operating Manual...

Страница 2: ...any components WARNING Explosion hazard Do not connect or dis connect equipment unless power has been switched off or the area is known to be non hazardous Notice of Trademark Copyright and Limitation...

Страница 3: ...Ensure that the length and inside diameter of the mounting nozzle are sized correctly to allow for switch actuation at design levels Refer to Figure 1 2 Ensure that the mounting nozzle or coupling is...

Страница 4: ...ould be done in such a way as to minimize the action of dynamic forces on the float or displacer sensing element Good practice for reducing the likelihood of damage to the control is to equal ize pres...

Страница 5: ...he field of the switch mechanism magnet As a result the magnets repel causing the pivot arm and valve plunger to move so that air is allowed to pass from air inlet A to air outlet C As liquid level ri...

Страница 6: ...tory or your local representative 3 NEVER use in systems which have excess iron particles in the solution The magnet at the counterweight end of the float can attract the particles which could cause t...

Страница 7: ...40 F to 300 F 40 C to 149 C Ambient Temperature Max 100 F 38 C with maximum process temperature Pneumatic Switch Supply Pressure Vacuum to 200 psig 13 8 bar maximum Maximum Leakage Rate 0 5 SCFH 0 015...

Страница 8: ...e impaired Return Material Procedure So that we may efficiently process any materials that are returned it is essential that a Return Material Authorization RMA number be obtained from the fac tory pr...

Отзывы: