N O Z Z L E S

Improper installation in a nozzle creates “ringing” (unde-

sired signals) which can adversely affect measurement. The

antenna should always be mounted such that the active

section of the antenna is a minimum of 0.5" (13 mm)

below the nozzle. Be sure to include any nozzle dimension

that may extend down inside the vessel. Refer to Figure 10.

Antenna extensions are offered to allow the PULSAR Model

R86 transmitter to work reliably in nozzles with an “L”

dimension up to 72" (1.8 m).

O R I E N T A T I O N

The PULSAR Model R86 transmitter utilizes circular

polarization. This means that the microwave beam does

not need to be manually adjusted (rotated) during

commissioning as is necessary with other radar transmitters.

The result is a much simpler start-up process.

M O U N T I N G

5

0.50" (13 mm)

Minimum

2" (50 mm)

" L " Dimension (Nozzle Height)

Figure 10

To limit the temperature exposure to the transmitter in high

temperature applications, a heat extension (032-6922-001) is

required between the antenna and transmitter. Refer to

“Operating Temperature Range” chart on page 6.

T E M P E R A T U R E   E X T E N S I O N

H E A T   E X T E N S I O N   F O R   U S E   W I T H   H I G H
T E M P E R A T U R E / H I G H   P R E S S U R E   A N T E N N A S

The PULSAR Model R86 can be mounted in a standpipe

or stillwell but certain items must be considered:

Metal stillwells only:

Inside diameter 1

3

4

–8 inches (45–200 mm).

Diameter must be consistent throughout length; no

reducers or gaps.

Use only horn antennas sized to pipe ID; 1

1

2

"–4"

(44–100mm); 8-inch pipe can use 4-inch horn.

Stillwell length must cover complete range of

measurement (i.e., liquid must be in stillwell).

Welds should be smooth.

Vents: holes <0.125" (3 mm) diameter,

slots <0.125" (3 mm) width.

If an isolation valve is used, it must be a full port

ball valve with an I.D. equal to the pipe diameter.

Configuration must include a non-zero entry for

PIPE I.D parameter.

S T A N D P I P E S   A N D   S T I L L W E L L S

Содержание Pulsar R86

Страница 1: ...s configuration wizards bring simplicity to an often complex technology This latest entry into the radar level measurement field is designed to provide unparalleled performance and ease of use The 26...

Страница 2: ...ght multiplied by the transit time divided by two Distance C Transit Time 2 Level is then calculated by factoring in tank height and other configuration information Figure 3 The reference point for di...

Страница 3: ...Turbulence Medium or Heavy Dielectric 1 7 3 3 10 10 100 1 7 3 3 10 10 100 Antenna Type 11 2 Horn 30 9 40 12 60 18 10 3 16 5 26 8 2 Horn 33 10 49 15 66 20 10 3 20 6 33 10 3 Horn 50 15 66 20 98 30 13 4...

Страница 4: ...maximum liquid surface with minimum striking of other objects in the vessel including the tank wall Use these drawings to determine the optimum installation location O B S T R U C T I O N S Almost any...

Страница 5: ...perature exposure to the transmitter in high temperature applications a heat extension 032 6922 001 is required between the antenna and transmitter Refer to Operating Temperature Range chart on page 6...

Страница 6: ...PTFE POLYPROPYLENE QUARTZ Ambient Temperature F C 40 40 20 29 0 18 20 7 40 4 60 16 80 27 100 38 120 49 140 60 160 71 180 82 700 371 750 400 600 315 500 260 400 204 300 149 200 93 100 38 0 18 100 73 P...

Страница 7: ...cannot be handled by the R86 transmitter Unusual flow applications can readily be accomplished through the use of either the 20 point Custom Table or the Generic Discharge Flow Equation which allows a...

Страница 8: ...C General purpose ethylene Ketones MEK acetone skydrol fluids amines anhy drous ammonia low molecular weight esters and ethers hot hydrofluoric or chlorosulfuric acids sour HCs Kalrez 4079 2 400 F 23...

Страница 9: ...1 2013 ANSI ISA 60079 15 2012 ANSI ISA 60079 26 2011 NEMA 250 2003 ANSI IEC 60529 2004 C22 2 No 0 4 2009 C22 2 No 0 5 2008 C22 2 No 30 2007 C22 2 No 94 2001 C22 2 No 213 2012 C22 2 No 1010 1 2009 CAN...

Страница 10: ...HART DD English French German Spanish Russian Chinese Portuguese FOUNDATION fieldbus Host System English Voltage Measured at instrument terminals HART General Purpose Weather proof Intrinsically Safe...

Страница 11: ...45 over entire temperature range 40 to 175 F 40 to 80 C Maximum Rate of Change 180 inches 450 cm minute FOUNDATION fieldbus ITK Version 6 2 0 H1 Device Class Link Master LAS selectable ON OFF H1 Profi...

Страница 12: ...I F I C A T I O N S I N C H E S M M 12 TRANSMITTER Model Number 3rd Digit Horn Size 11th Digit Extension 1 11 2 2 2 3 3 4 4 Dim H 0 None 3 2 81 4 5 114 8 5 216 11 5 292 Dim L 1 4 6 152 2 8 8 203 8 3...

Страница 13: ...ne FOUNDATION fieldbus only 5th digit 2 1 SIL 2 Hardware HART only 5th digit 1 A None FOUNDATION fieldbus only 5th digit 2 ETSI B SIL 2 Hardware HART only 5th digit 1 ETSI 7 ACCESSORIES MOUNTING 0 No...

Страница 14: ...150 ASME raised face flange EA DN 80 PN 16 EN 1092 1 Type A 54 3 300 ASME raised face flange EB DN 80 PN 25 40 EN 1092 1 Type A 55 3 600 ASME raised face flange ED DN 80 PN 63 EN 1092 1 Type B2 63 4...

Страница 15: ...NS 0 Viton GFLT 2 Kalrez 4079 8 Simriz SZ485 formerly Aegis PF128 NACE A Kalrez 6375 N None Quartz seal mandatory for flame proof ATEX IEC approval 0 None 1 For nozzle height 4 100 mm available only w...

Страница 16: ...o be cov ered under the warranty then MAGNETROL will repair or replace the control at no cost to the purchaser or owner other than transportation MAGNETROL shall not be liable for misap plication labo...

Отзывы: