79
58-603 Pulsar
®
Model R86 Radar Transmitter
Complete Listing of Diagnostic Indicators including Analog Board Errors (continued)
Error Code
Diagnostic
Explanation
12
Too Many Echoes
Excessive number of waveform features are possible echoes
13
Safe Zone Alarm
Level is above Safe Zone end
14
No Echoes
Echo from upper surface missing for longer than Echo Loss Delay
15
Spare
16
Config Conflict
Configuration conflict caused by incompatible parameter selections
17
High Volume Error
Calculated Volume exceeds maximum for vessel or custom table
18
High Flow Error
Calculated Flow exceeds maximum for flume or custom table
19
Spare
20
Initializing
System warming up, distance measurement not yet valid
21
Config Changed
A parameter(s) has recently been modified from the User Interface
22
Spare
23
High Electrical Temp
Present electronics temperature above maximum
24
Low Electric Temp
Present electronics temperature below minimum
25
Calibration Required
Distance calibration parameters are at default values
26
Echo Rejection Invalid
Previously stored Echo Rejection Curve invalidated by parameter change
27
Spare
28
Inferred Level
Typically this is caused when the Level target has been lost or has
entered either the Top or Bottom Blocking Distance zones. If in the Top
or Bottom Blocking Distance zones the transmitter will read Full (Top) or
Empty (Bottom). The Level reading (and mA value) will never be higher
than the value related to the Top Blocking Distance or lower than the
value related to the Bottom Blocking Distance.
29
Adjust Analog Output
Loop trim parameters are at default values
30
Totalizer Data Lost
Totalizer data has been lost, restarted from zero
31
Low Supply Voltage
Power supply voltage inadequate to prevent brownout or reset
32
Spare
33
Max Jump Exceeded
Transmitter has jumped to an echo that exceeds the Max Distance Jump
value from the previous echo.
34
Marginal Echo
Signal Margin is less than allowable minimum
35
High Surface Velocity
The measured Surface Velocity is greater than the Max Surface Velocity
value derived from the Rate of Change parameter.
36
Spare
37
Seq Record
Instruction execution traversed a correct but unexpected path (formerly
System Warning)
38
Unknown
Unknown event id received
39
No Event
Used when reading history from host
70
Device Variable Alert
Device variable alert active in Extended Device Status byte
71
Echo History Time
Used for denoting time-based echo history save