background image

46

58-603 Pulsar

®

Model R86 Radar Transmitter

• Failure

• Function Check

• Out of Specification

• Maintenance required

These categories are shown by both symbols and colors,
depending on the display capability.

In essence, this approach ensures that the correct diagnostic
information is available to the correct person-at the correct
time. In addition, it allows diagnostics to be applied, as
most appropriate, for a particular plant application (such as
process control engineering or asset management mainte-
nance). Customer specific mapping of diagnostics to these
categories allows for flexible configuration depending on the
user's requirements.

From an external Model R86 transmitter perspective, diag-
nostic information includes measurement of process condi-
tions, in addition to detection of internal device or system
anomalies. 

As mentioned above, the indicators can be assignable (via
the a DTM or host system) by the user to any (or none) of
the NAMUR recommended Status Signal categories:
Failure, Function Check, Out of Specification, and
Maintenance Required.

In the F

OUNDATION

fieldbus version of the transmitter,

diagnostic indicators can be mapped to multiple categories
(e.g., as shown in the diagram at left). 

Indicators that are mapped to the Failure category will nor-
mally result in a current loop alarm output. The alarm state
for HART transmitters is configurable as high (22 mA),
Low (3.6 mA), or Hold (last value).

Users will not have the ability to unassign certain indicators
from the Failure signal category as the Model R86 user
interfaces will prohibit or reject such re-assignment entries.
This is to ensure that current loop alarms are asserted in situ-
ations where the device is not able to provide measurements
due to critical failures. (For example, if the alarm selection
has not been set to Hold or a fixed current mode is in effect.)

A default mapping of all diagnostic indicators will be applied
initially, and can be re-applied through use of a reset function. 

Analog Output Error

Echo Lost

Calibration

Required

Failure

Function
Check

Out of
Specification

Maintenance
Required

NE-107

Status Signals

Diagnostic Indicators

High

Elec Temp

Содержание Pulsar R86

Страница 1: ...2014 68 EU High Performance 26 GHz Pulse Burst Radar Level Transmitter Installation and Operating Manual for Pulsar Model R86 with HART output Software Version 1 x...

Страница 2: ...C rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may ca...

Страница 3: ...sion Proof 19 2 6 Configuring the Transmitter 20 2 6 1 Bench Configuration 20 2 6 2 Menu Traversal and Data Entry 21 2 6 2 1 Navigating the Menu 21 2 6 2 2 Data Selection 21 2 6 2 3 Entering Numeric D...

Страница 4: ...y Approvals 52 3 5 1 Agency Drawing Entity Parameters 54 3 6 Parts 56 3 6 1 Replacement Parts 56 3 7 Specifications 57 3 7 1 Functional Transmitter 57 3 7 2 Functional Environmental 58 3 7 2 1 Safe Op...

Страница 5: ...Complete Installation Section 2 0 for detailed installa tion instructions 1 1 Getting Started Before beginning the QuickStart Installation procedures have the correct equipment tools and information...

Страница 6: ...antenna _____________ Antenna What is maximum nozzle length for Extension which the antenna can be used Select 8th digit of antenna model number See nameplate on side of antenna _____________ Antenna...

Страница 7: ...l ready to install the transmitter NOTE Do not use sealing compound or TFE tape on antenna connec tion to transmitter This connection is sealed by a Viton O ring 1 2 2 Transmitter 1 Remove the protect...

Страница 8: ...sted the PULSAR Model R86 transmitter is shipped fully pre configured for the application and can be installed immediately Otherwise the unit is shipped config ured with default factory values and can...

Страница 9: ...ess ENTER with the WIZARDS menu item high lighted 6 Press ENTER with the SETUP WIZARD menu item highlighted The Setup Wizard shows the basic parameters along with Help Text to guide the procedure One...

Страница 10: ...l refer to antenna nameplate NPT National Pipe Thread BSP British Standard Pipe Flange ANSI or DIN Dielectric Range Enter the Dielectric Range for the material to be measured Below 1 7 light hydrocarb...

Страница 11: ...ost position then the screen is exited without changing the previously saved value ENTER Moves the cursor to the right If the cursor is located at a blank character position the new value is saved Scr...

Страница 12: ...eplaced with a cable gland Record the model and serial numbers for future reference when ordering parts 2 2 Electrostatic Discharge ESD Handling Procedure MAGNETROL electronic instruments are manufact...

Страница 13: ...2 3 2 Equipment and Tools No special tools are required The following items are recommended Threaded antenna and process connection 2 50 mm Transmitter antenna connection 13 4 44 mm wrench Transmitter...

Страница 14: ...eavily cluttered with false targets mixers pumps ladders pipes etc During times of very low liquid levels of low dielectric media the metal tank bottom may be detected which can deterio rate performan...

Страница 15: ...m from the sensor reference point whichever is greater 2 4 1 1 Location Ideally the Radar transmitter should be mounted providing an unobstructed signal path to the liquid surface where it should illu...

Страница 16: ...hin the vessel 2 4 1 5 Standpipes and Stillwells The PULSAR Model R86 can be mounted in a standpipe or stillwell but certain items must be considered Metal stillwells only Sizes 11 2 4 inches 38 100 m...

Страница 17: ...ecific point in the vessel it is usually a symptom of multipath side wall reflections causing cancellation by returning to the transmitter exactly 180 out of phase with the actual Level signal This ca...

Страница 18: ...For the same reason cable gland and plugs should be properly installed in the cable entries 2 5 1 General Purpose or Non incendive Cl I Div 2 A general purpose installation does not have flammable me...

Страница 19: ...shield to an earth ground at power supply 5 Connect an earth ground wire to the nearest green ground screw not shown in illustration 6 Connect the positive supply wire to the terminal and the negative...

Страница 20: ...ides a convenient and efficient way to set up the transmitter before going to the tank site to complete the installation Before configuring any transmitter collect all operating parameters information...

Страница 21: ...labels or parameter names Menu labels are presented in all capital letters Parameters are capital words 2 6 2 1 Navigating the Menu UP moves to the previous item in the menu branch DOWN moves to the...

Страница 22: ...st digit 0 1 2 3 9 or decimal point If held down the digits scroll until the push button is released Back Moves the cursor to the left and deletes a digit If the cursor is already at the leftmost posi...

Страница 23: ...d to any numerical value up to 59999 When the transmitter is programmed for password protection a password is required whenever configuration values are changed NOTE If a User Password is not known or...

Страница 24: ...mitter The menu layout is similar between the local Keypad LCD interface the DD and the DTM Use these tables as a step by step guide to configure the transmitter based on the desired measurement type...

Страница 25: ...t this point are NOTES 1 Items and parameters that are shown in lower level menus will depend on the Measurement Type chosen Those parameter not applicable to the present Measurement Type will be hidd...

Страница 26: ...om the MAIN MENU will result in an LCD presentation as shown at left The small down arrow shown at the right hand side of the screen is the indication that more items are available below and can be ac...

Страница 27: ...Horn RB4 x 4 Horn Antenna Extension 0 No nozzle 1 Nozzle 4 2 Nozzle 8 3 Nozzle 12 4 Nozzle 24 5 Nozzle 48 6 Nozzle 72 Rate of Change 5 in min 5 20 in min 20 60 in min 60 in min Display Config Advanced...

Страница 28: ...ters Stillwell I D 1 6 to 19 7 inches 40 to 5000 mm Turbulance None Light Medium Heavy Foam None Light Medium Heavy Volume Config I O Config Antenna Model RB1 x 1 5 Horn RB2 x 2 Horn RB3 x 3 Horn RB4...

Страница 29: ...eet 0 to 30 meters 0 to 9999999 cf Volume PV Alarm Selection High Low Hold Last Output Value Damping 0 to 10 seconds Language English French German Spanish Russian Portuguese Status Symbol Hide View L...

Страница 30: ...ue Output Echo Loss Delay 1 to 1000 seconds Failure Alarm Delay 0 to 5 seconds Level Trim 10 to 10 inches 25 to 25 cm THRESHOLD SETTINGS Target Selection First Echo Largest Echo Target Thresh Mode Aut...

Страница 31: ...ig I O Config Display Config Advanced Config Factory Config NAP Factory Reset FACTORY CALIBRATION Factory password required Elec Temp Offset Conversion Factor Scale Offset Window Fiducial Gain 0 255 r...

Страница 32: ...necting it directly to the terminal block in the electronics housing of the PULSAR Model R86 transmitter HART uses the Bell 202 frequency shift key technique of high frequency digital signals It opera...

Страница 33: ...oints 1 Manufacturer 2 Model 3 Magnetrol S N 4 Hardware Rev 5 Firmware Rev 6 Cfg chng count 7 Dev id 8 Universal Rev 9 Fld Dev Rev 10 Software Rev 11 Num Req Preams 1 Enter Password 2 Vessel Type 3 Le...

Страница 34: ...bol 4 Long Tag 5 PV Bar Graph 6 Measured Values 1 Enter Password 2 Sensitivity 3 Top Blocking Distance 4 Bottom Blocking Distance 5 Safety Zone Settings 6 Echo Loss Settings 7 Failure Alarm Delay 8 Ad...

Страница 35: ...ts connect via a watertight feed through 3 2 Theory of Operation 3 2 1 Pulse Burst Radar PULSAR Model R86 is a top mounted downward looking pulse burst radar operating at 26 GHz Unlike true pulse devi...

Страница 36: ...h today s technology ETS is accomplished by scanning the tank to collect thou sands of samples Approximately three scans are taken per second each scan gathers more than 50 000 samples 3 3 Configurati...

Страница 37: ...t Function A parameter labeled Reset Parameter is located at the end of the DEVICE SETUP ADVANCED CONFIG menu In the event a user gets confused during configuration or advanced troubleshooting this pa...

Страница 38: ...f the System Configuration parameters required for volume applications that use one of the nine Vessel Types Configuration Parameter Explanation System Units A selection of Gallons Barrels Milliliters...

Страница 39: ...8 603 Pulsar Model R86 Radar Transmitter SPHERICAL HORIZONTAL SPHERICAL Vessel Types VERTICAL FLAT VERTICAL CONICAL HORIZONTAL FLAT RECTANGULAR HORIZONTAL ELLIPTICAL VERTICAL ELLIPTICAL VERTICAL SPHER...

Страница 40: ...Type The Custom Table points can be a Linear straight line between adjacent points or Spline can be a curved line between points relationship See drawing below for more information Cust Table Vals A...

Страница 41: ...the weir is related to the Head at a specified measurement location The Model R86 is the secondary measuring device which measures the Head of the liquid in the flume or weir Open channel flow equati...

Страница 42: ...ee page 43 for flow calculation Weir Crest Length The Weir Crest Length screen only appears when the chosen Flow Element is Cipoletti or one of the Rectangular weirs Input this length in the user sele...

Страница 43: ...the values of K L C H and n See example below NOTE The Generic Equation parameters must be entered in Cu Ft Second units The resultant flow is converted by the Model R86 into whatever Flow Units are...

Страница 44: ...e capability of using a Generic Equation see page 44 for flow calculation Custom Table The Custom Table points can be a Linear straight line between adjacent points or Spline can be a curved line betw...

Страница 45: ...shooting tool that can aid in the resolution of any diagnostic indicators that may appear Refer to Section 4 0 Advanced Configuration Troubleshooting Techniques for additional information 3 4 1 Diagno...

Страница 46: ...l categories Failure Function Check Out of Specification and Maintenance Required In the FOUNDATION fieldbus version of the transmitter diagnostic indicators can be mapped to multiple categories e g a...

Страница 47: ...highest MAGNETROL priority active diagnostic indicator numer ically lowest in Table 3 4 is displayed on the bottom LCD line Pressing the ENTER key moves the active diagnostic indicator to the top lin...

Страница 48: ...CED DIAGNOSTICS This menu displays parameters related to some of the advanced diagnostics available within the Model R86 INTERNAL VALUES Displays read only internal parameters ELEC TEMPERATURES Displa...

Страница 49: ...eak to detect Torque HF nut Clean gold pin on transmitter and socket on antenna Check settings Fiducial Gain Window Increase Fid Gain Contact MAGNETROLTechnical Support 12 Too Many Echoes Failure Exce...

Страница 50: ...Spec Echo Rejection inoperative May report erroneous Level readings Upr Echo may be lost Save a fresh Echo Rejection Curve 27 Spare Indicator 7 OK Reserved for future use 28 Inferred Level Out of Spe...

Страница 51: ...ion Descriptive information relevant to the highlighted parameter in the menu will be accessible via the local display and remote host interfaces This will most often be a parameter related screen but...

Страница 52: ...14ATEX0058X II 3 G Ex nA IIC Gc T6 Ta 15 C to 70 C IP67 IEC IECEx FMG 15 0034X Ex nA IIC Gc T6 Ta 15 C to 70 C IP67 Intrinsically Safe US Canada Class I II III Div 1 Group A B C D E F G T4 Class I Zon...

Страница 53: ...r peripheral the instructions furnished the user shall include the following or similar statement placed in a prominent location in the text of the manual Note This equipment has been tested and found...

Страница 54: ...54 58 603 Pulsar Model R86 Radar Transmitter 3 5 1 Agency Drawing and Entity Parameters...

Страница 55: ...55 58 603 Pulsar Model R86 Radar Transmitter 3 5 1 Agency Drawing and Entity Parameters...

Страница 56: ...placement Part 8 Heat Extension 032 6922 001 6 Housing Cover Digit 7 Digit 8 Digit 9 Replacement Part 0 all 1 004 9225 002 2 004 9225 003 A all 1 036 4413 013 all 2 036 4413 016 7 Housing Cover Digit...

Страница 57: ...hic Liquid Crystal Display Digital Communication HART Version 7 with Field Communicator FOUNDATION fieldbus AMS or FDT DTM PACTware EDDL Menu Languages Transmitter LCD English French German Spanish Ru...

Страница 58: ...1 inch or 1mm Repeatability 0 1 inch 3 mm or 0 05 of tank height whichever is greater Response Time 2 seconds configuration dependent Initialization Time 30 seconds Ambient Temperature Effect Digital...

Страница 59: ...r chlorosulfuric acids sour HCs Kalrez 4079 2 400 F 232 psi 200 C 16 bar 750 psi 70 F 51 7 bar 20 C 40 F 40 C Inorganic and organic acids including HF and nitric aldehydes ethylene glycols organic oil...

Страница 60: ...lwells 0 500 250 40 70 750 1000 1500 1250 2000 2250 1750 2500 100 0 100 200 300 400 500 600 700 800 Pressure psig 0 20 40 60 80 100 120 140 160 50 0 50 100 150 200 250 300 350 400 Pressure bar Tempera...

Страница 61: ...8 3 211 3 12 12 305 12 305 12 4 315 14 4 366 4 24 24 610 24 610 24 610 24 610 5 48 48 1219 48 1219 48 1219 48 1219 6 72 72 1829 72 1829 72 1829 72 1829 Dim D 1 56 40 1 89 48 2 95 75 3 74 95 HORN ANTE...

Страница 62: ...20 mA with HART 2 Foundation fieldbus H1 6 SAFETY OPTIONS 0 None FOUNDATION fieldbus only 5th digit 2 1 SIL 2 Hardware HART only 5th digit 1 7 ACCESSORIES MOUNTING 0 No Digital Display and Keypad Inte...

Страница 63: ...EN 1092 1 Type A 45 2 600 ANSI raised face flange DD DN 50 PN 63 EN 1092 1 Type B2 53 3 150 ANSI raised face flange EA DN 80 PN 16 EN 1092 1 Type A 54 3 300 ANSI raised face flange EB DN 80 PN 25 40...

Страница 64: ...AL OF CONSTRUCTION MFG NUT ROD INSULATION 9 FUTURE 0 10 O RING MATERIALS SEAL OPTIONS 0 Viton GFLT 2 Kalrez 4079 8 Simriz SZ485 formerly Aegis PF128 NACE A Kalrez 6375 N None Quartz seal 0 None 1 For...

Страница 65: ...ns are best suited for use with PACTware and the Model R86 DTM and should be implemented only after contacting Magnetrol Technical Support 4 1 Echo Rejection After choosing a proper mounting location...

Страница 66: ...ge On the next screen enter the actual location of the level to be measured and then click on NEXT A password window will then appear unless the password was previously entered Enter the password and...

Страница 67: ...he loop can be returned to automatic control At this point the echo rejection curve can be viewed by selecting Rejection Curve as Curve 2 in the lower left corner of the Echo Curve screen The Rejectio...

Страница 68: ...rejection Since the local display does not have the ability to concurrently display the live and rejection echo curves the manipulation of the echo rejection curve will be done in the DD and DTM only...

Страница 69: ...re echo rejection curve would result in a lower portion of the rejection curve being lost Therefore it is beneficial in that circumstance to be able to add the echo to the existing custom curve so tha...

Страница 70: ...he Rejection echo list along with a display of the present level the user selects the desired echo to be modified The distance to the echo must be smaller than the distance to the level echo 3 The use...

Страница 71: ...tank For example some processes may only operate in a smaller range 6 The increments can be set as a percentage of the Start Stop range Increment by or in Level Distance units Increment by Unit 7 The...

Страница 72: ...ases but the Echo Margin decreas es a False Target is reaching closer to the Threshold see drawing above If the False Target reaches above the Threshold it will be detected as a valid Level echo and w...

Страница 73: ...e transmitter has the ability to store a number of echo curves in its on board memory These echo curves can then be downloaded to a laptop running software such as PACTware and reviewed in Diagnostics...

Страница 74: ...f the DTM 4 x Event History Although Event History has been included and found to be very useful in other Magnetol devices it has been improved in the Model R86 Event History becomes the main reposito...

Страница 75: ...rocedure used when accessing the Event Hisotry from the DTM Although Event History can be viewed via the Local User Interface the DTM offers a more complete view of the information Press Refresh Event...

Страница 76: ...3 1 9 Echo Reject State 2017 01 08 15 51 05 000 00 00 0 2 0 8 Echo Curve 2017 01 08 15 32 46 000 00 00 7 29 5 7 Low Echo Margin 2017 01 08 15 32 16 000 00 00 5 29 5 6 BC Level 2017 01 08 15 31 10 028...

Страница 77: ...Echoes Number of Echoes found Level value when captured Event Value1 Value2 Run Average Old value New Value 4mA LRV Old value New value 20mA URV Old value New value Base Threshold Old value New value...

Страница 78: ...lue Turbulence 0 None 1 Light 2 Medium 3 Heavy Corresponding Echo Strength TVG End Location Old value New value TVG End Value Old value New value TVG Start Location Old value New value TVG Start Value...

Страница 79: ...Inferred Level Typically this is caused when the Level target has been lost or has entered either the Top or Bottom Blocking Distance zones If in the Top or Bottom Blocking Distance zones the transmi...

Страница 80: ...turn This is available through a MAGNETROL local representative or by contacting the factory Please supply the following information 1 Company Name 2 Description of Material 3 Serial Number 4 Reason f...

Отзывы: