35
57-642 ECLIPSE Model 705 Guided Wave Radar Transmitter for Hygienic Industries
5.2
Status Messages
Display Message
Action
Comment
OK
None
Normal operating mode
Initial
None
Program is Initializing, level reading held at 4 mA set point. This is a
transient condition.
DryProbe
None
Normal message for a dry probe. End of probe signal is being detected.
EOP < Probe
Length
End of Probe signal from a dry
probe is out of range
1) Ensure probe length is entered correctly
2) Set transmitter to a lower dielectric range
3) Consult factory
4) Ensure proper blocking distance
EOP High
End of Probe signal is out of
range
1) Ensure probe length is entered correctly
2) Consult factory (old twin rod probe being used with enhanced 705)
WeakSgnl
None. Signal amplitude is lower
than desired.
1) Set transmitter to lower dielectric range
2) Increase sensitivity
Flooded?
Loss of level signal possibly
due to flooding, twin rod
probes only
1) Decrease level in vessel
2) Set transmitter to lower dielectric range
3) Replace with Model 7xR Overfill probe
NoSignal
No level signal being detected
1) Ensure dielectric setting is correct for measured medium
2) Increase sensitivity
3) Confirm that the probe type is proper for the dielectric of the medium
4) Consult factory
No Fid
Fiducial signal is not being
detected
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Check for damaged gold pin on the high frequency connector
4) Consult factory
FidShift
FidTicks shifted from expected
value
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Check for damaged gold pin on the high frequency connector
4) Consult factory
Fid Sprd
Fiducial Ticks variation is
excessive
1) Check connection between probe and transmitter
2) Check for moisture on top of probe
3) Consult factory
SZ Alarm
Safety Zone alarm has been
tripped, loop current fixed at
SZ Fault
Decrease level in vessel
Hi Temp
Present temperature in
electronics compartment is
above +80° C
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter