ECLIPSE Guided Wave Radar transmitters may be protected by one or more of the following U.S. Patent Nos.
US 6,626,038; US 6,640,629; US 6,642,807; US 6867729; US 6879282; US 6906662. Other patents pending.

Disclaimer

The SIL values in this document are based on an FMEDA analysis using exida’s SILVER Tool. MAGNETROL

 

accepts no liability whatsoever for the use of these numbers o

r

 for the correctness of the standards on which the

 

general calculation methods are based.

Magnetrol, Magnetrol logotype and Eclipse are registered trademarks of Magnetrol International, Incorporated.
F

OUNDATION

fieldbus logo is a registered trademark of the Fieldbus Foundation.

HART is a registered trademark of the HART Communication Foundation.
PACTware is trademark of PACTware Consortium.

References

• IEC 61508 Edition 2.0,2010

“Functional Safety of Electrical/Electronic/
Programmable Electronic Safety Related Systems”

• ANSI/ISA-84.00.01-2004 Part 1 (IEC 61511-1Mod)

“Functional Safety: Safety Instrumented Systems for
the Process Industry Sector – Part 1 Hardware and
Software Requirements”

• ANSI/ISA-84.00.01-2004 Part 2 (IEC 61511-2Mod)

“Functional Safety: Safety Instrumented Systems for
the Process Industry Sector – Part 2 Guidelines for

the Application of ANSI/ISA84.00.01-2004 Part 1
(IEC 61511-1 Mod) – Informative”

• ANSI/ISA-84.00.01-2004 Part 3 (IEC 61511-3Mod)

“Functional Safety: Safety Instrumented Systems for
the Process Industry Sector – Part 3 Guidance for the
Determination of the Required Safety Integrity Levels
– Informative”

• ANSI/ISA-TR84.00.04 Part 1 (IEC 61511 Mod)

“Guideline on the Implementation of ANSI/ISA-
84.00.01-2004”

Service Policy

Owners  of  MAGNETROL  controls  may  request  the
return of a control or any part of a control for complete
rebuilding or replacement. They will be rebuilt or replaced
promptly. Controls returned under our service policy must
be  returned  by  prepaid  transportation.  MAGNETROL
will  repair  or  replace  the  control  at  no  cost  to  the  pur-
chaser (or owner) other than transportation if:

1. Returned within the warranty period; and
2. The factory inspection finds the cause of the claim to

be covered under the warranty.

If the trouble is the result of conditions beyond our con-
trol;  or,  is  NOT  covered  by  the  warranty,  there  will  be
charges  for  labor  and  the  parts  required  to  rebuild  or
replace the equipment.

In  some  cases  it  may  be  expedient  to  ship  replacement
parts;  or,  in  extreme  cases  a  complete  new  control,  to
replace  the  original  equipment  before  it  is  returned.  If
this is desired, notify the factory of both the model and
serial  numbers  of  the  control  to  be  replaced.  In  such
cases, credit for the materials returned will be determined
on the basis of the applicability of our warranty.

No claims for misapplication, labor, direct or consequen-
tial damage will be allowed.

Return Material Procedure

So  that  we  may  efficiently  process  any  materials  that  are
returned,  it  is  essential  that  a  “Return  Material
Authorization”  (RMA)  number  be  obtained  from  the
factory  prior  to  the  material’s  return.  This  is  available
through a MAGNETROL local representative or by con-
tacting the factory. Please supply the following information:

1. Company Name
2. Description of Material
3. Serial Number
4. Reason for Return
5. Application

Any  unit  that  was  used  in  a  process  must  be  properly
cleaned in accordance with OSHA standards, before it is
returned to the factory.

A Material Safety Data Sheet (MSDS) must accompany
material that was used in any media.

All shipments returned to the factory must be by prepaid
transportation.

All replacements will be shipped F.O.B. factory.

Содержание Eclipse 706GWR

Страница 1: ...rature and pres sure It can be used in liquids slurries or solids with a dielectric constant in the range 1 4 100 to meet the safety system requirements of IEC 61508 Edition 2 0 2010 and IEC 61511 1 B...

Страница 2: ...nstructions 5 6 1 Systematic Limitations 5 6 1 1 Application 5 6 1 2 Environmental 6 6 1 2 1 Storage 6 6 2 Installation 6 6 3 Skill Level of Personnel 6 6 4 Necessary Tools 6 6 5 Configuration 7 6 5 1...

Страница 3: ...is reflected The transit time of the pulse is then measured via ultra high speed timing circuitry that provides an accurate measure of the liquid level The amplitude of the reflection depends on the...

Страница 4: ...is reading an incorrect level within the 4 20 mA range 2 deviation MAGNETROL defines a safe failure as one in which the 4 20 mA current is driven out of range i e less than 3 8 mA or greater than 21 5...

Страница 5: ...f the transmitter One of the following Electronic Device Description Files is also required if HART is used Manufacturer Code 0x56 Model 706 Device ID 0x56E0 device revision 1 DD revision 2 For device...

Страница 6: ...evice Offers configuration recommendations NOTE This SIL evaluation has assumed that the customer will be able to acknowledge an over or under current condition via the Logic Solver 6 3 Skill Level of...

Страница 7: ...for SIL applications Consult factory prior to making any changes LOOP CONTROL MODE Ensure this is set to ENABLED THRESHOLD Set to FIXED if used in a hydrocarbon application with any possibility of wa...

Страница 8: ...SIL Proof Test Firmware can only be upgraded by factory personnel 7 0 Recurrent Function Tests 7 1 Proof Testing 7 1 1 Introduction Following is the procedure utilized to detect Dangerous Undetected...

Страница 9: ...at the time of the proof test event times are calculated a Choose the menu DIAGNOSTICS Present Status i Present Status should indicate OK b Choose the menu DIAGNOSTICS EVENT HISTORY Event Log i Any FA...

Страница 10: ...ess the Fiducial Ticks and Fiducial Strength values in the menu DIAGNOSTICS ADVANCES DIAGNOSTICS INTERNAL VALUES i Observe and record 1 Fiducial Ticks _____________ 2 Fiducial Strength _____________ i...

Страница 11: ...declares as the manufacturer that the level transmitter Guided Wave Radar 4 20 mA Model 706 51x xxx is suit able for the use in safety instrumented systems according to IEC 61511 1 if the safety inst...

Страница 12: ...12 57 656 SIL Safety Manual for ECLIPSE Model 706 8 2 FMEDA Report exida Management Summary...

Страница 13: ...13 57 656 SIL Safety Manual for ECLIPSE Model 706...

Страница 14: ...the PFDAVG value needs to be 10 3 and 10 2 This means that for a SIL 2 application the PFDAVG for a 1 year Proof Test Interval of the Model 706 511x xxx is approximately equal to 6 7 of the range Thes...

Страница 15: ...endent on the subsystem itself and its operating conditions The assumption of a constant failure rate is based on the bathtub curve Therefore it is obvious that the PFDAVG cal culation is only valid f...

Страница 16: ...1 IEC 61511 Mod Guideline on the Implementation of ANSI ISA 84 00 01 2004 Service Policy Owners of MAGNETROL controls may request the return of a control or any part of a control for complete rebuildi...