4.0 Model 706 Transmitter Configuration
Although the ECLIPSE Model 706 transmitter can be
delivered pre-configured from the factory, it can also be eas-
ily reconfigured in the shop or at the installation using the
local LCD/Keypad. Bench configuration provides a conve-
nient and efficient way to set up the transmitter before
going to the tank site to complete the installation.
NOTE: The transmitter can be configured without the probe. Please
disregard the “No Probe” diagnostic indicator that will appear.
4.1 Configuration Information
To utilize the QuickStart menu available on the
ECLIPSE Model 706, some key information is required
for configuration.
Gather the information and complete the following operating
parameters table before beginning configuration.
NOTES: The QuickStart menu is available for Level Only applications.
1. Refer to Section 4.5 for configuration menus for Interface,
Volume or Flow applications.
2. These configuration steps are not necessary if the transmitter
was pre-configured prior to shipment.
display
Question
answer
Level Units
What units of measurement will
be used?
(inches, millimeters, centimeters,
feet or meters)
_____________
Probe Model
What probe model is listed on
the model information?
(first three digits of probe
model number)
_____________
Probe Mount
Is the probe mounted NPT, BSP,
or flange? (Refer to probe model.)
_____________
Probe Length
What probe length is listed on
the probe model information?
(last three digits of the probe
model number)
_____________
Level Offset
The desired level reading when
the liquid is at the tip of the probe. _____________
Dielectric Range
What is the dielectric constant
range of the process medium?
_____________