25
TOTAL_SP
: The set point for a batch totalization.
OUT
: The block output value and status.
OUT_RANGE
: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point associated with OUT.
GRAND_DENY
: Options for controlling access of host
computers and local control panels to operating, tuning,
and alarm parameters of the block (not used by the device).
STATUS_OPTS
: Allows you to select option for status
handling and processing. The supported status option for
the Integrator block is: “Uncertain if Manual mode.”
IN_1
: The block input value and status.
IN_2
: The block input value and status.
OUT_TRIP
: The first discrete output.
OUT_PTRIP
: The second discrete output.
TIME_UNIT1
: Converts the rate time, units in seconds.
TIME_UNIT2
: Converts the rate time, units in seconds.
UNIT_CONV
: Factor to convert the engineering units of
IN_2 into the engineering units of IN_1.
PULSE_VAL1
: Determines the mass, volume or energy per
pulse.
PULSE_VAL2
: Determines the mass, volume or energy per
pulse.
REV_FLOW1
: Indicates reverse flow when “true”; 0-
Forward, 1- Reverse
REV_FLOW2
: Indicates reverse flow when “true”; 0-
Forward, 1- Reverse
RESET_IN
: Resets the totalizers
STOTAL
: Indicates the snapshot of OUT just before a
reset.
RTOTAL
: Indicates the totalization of “bad” or “bad” and
“uncertain” inputs, according to INTEG_OPTIONS.
SRTOTAL
: The snapshot of RTOTAL just before a reset
SSP
: The snapshot of TOTAL_SP
INTEG_TYPE
: Defines the type of counting (up or
down) and the type of resetting (demand or periodic)
BE57-646 ECLIPSE Guided Wave Radar Transmitter - F
OUNDATION
fieldbus
™