15
BE57-646 ECLIPSE Guided Wave Radar Transmitter - F
OUNDATION
fieldbus
™
On the other hand, part of the advantage of F
OUNDATION
fieldbus™ is to provide the ability to monitor changes and
make adjustments to a transmitter. The Fieldbus™ concept
allows a user to make adjustments if deemed necessary.
2.3.4 Eclipse Model 706 FF device-Specific
Configuration Parameters
Please refer to ECLIPSE Model 706 I/O Manual BE 57-606
for detailed information on the Model 706 device-specific
configuration parameters.
2.4 Analog Input Block
The ANALOG INPUT (AI) block takes the ECLIPSE
Model 706 FF input data, selected by channel number, and
makes it available to other function blocks at its output.
The channel selections are:
2.4.1 aI Block Parameters
The following are general descriptions of the parameters
common to all function blocks. Additional information for
a given parameter may be described later in a section that
describes the specific block.
Transducer
Blocks
Process Variable
Channel Parameter
Value
(AI Blocks)
TB1 – Level
Level
1
Interface Level
2
Upper Thickness
3
Distance
4
Echo Strength
5
Ifc Echo Strength
6
Electronics Temperature
7
Probe Buildup
8
TB2 – Volume Volume
9
TB3 – Flow
and Totalizers
Flow
10
Head
11
NR Totalizer
12
R Totalizer
13