Physical Installation
● Wiring
CONTOUR Operating Instructions © 2013 Magnetrol International all rights reserved
19
Attach the rear panel back to position at the rear of the
scanner housing and tighten the four screws to secure it in
place, using a 4mm hex key.
The CONTOUR is ready for configuration.
IMPORTANT:
Use direct connection between the scanners and the plant
(PLC/SCADA).
IMPORTANT:
For a remote connection, use the CONTOUR Connect remote
connection module or a local PC/Laptop computer as detailed in the following
drawing.
CAUTION:
Do not connect power supply to the 4-20 mA or to the RS485 ports.
The CONTOUR is not a loop powered device but a 4W device.
WARNING:
The 4-20 mA / HART lines should NOT be connected using
multidrop.
9