7.5 Anode replacement

1. Opening the HWR reaction vessel to replace anodes

Once the display indicator of the regulator is on the left in the “0” range during the
heating phase, you must check the installed anode and replace it where applicable. 
To do this, follow the steps below:
- Close the inlet and outlet on the HWR
- Place a bucket or other collecting vessel under the emptying valve
- If possible remove the bleeder, open the drain ball valve, and speed up the empty-
ing process by pressing the cut-off valve.
- Carefully pull the polycover off in an upwards movement.
- Sever the orange connector on the cable of the functional display.
- Remove the insulation fleece and remove the plug from the plug-in flap.
- The container is closed by means of a flange. Open the vessel and take the flange
with the anode bracket out and check it.
a) If the anode is completely used up and only the black wire is present, it is neces-
sary to install a new anode
b) If the anode is still there and the display was showing “0” before this, an oxide 
layer is covering the anode, which is preventing it from working. Clean the anode 
with a wire brush, then it should function again. Otherwise check the display func-
tion using a 1.5V. If it doesn’t react, then the display device is faulty.

2. Installing the new anode

When the anodes are completely used up, install the new anodes as follows:
The anodes are attached to a bushing screw (1), which is fed through the flange and
sealed using PTFE seals. Do not remove this bushing screw!
- Do not remove the anode stabiliser.
- Often the anode bracket is strongly soiled and needs to be cleaned using a steel
brush prior to removal.
- In order to remove the anode, hold the bushing screw (1) and loosen the anode
screw (2).
- Hold the new anode by screwing the anode screw (2) into the bushing screw (1). The
firm connection between the anode screw and bracket is important.
- After assembly the firm fit of the entire bushing screw on the flange must be checked
and retightened where applicable.
- Replace the seal of the flange whenever you replace the anode
- Reattach the flange or brass plug on the HWR and pay attention that the cable con-
nection is reattached to the functional display before you replace the plastic lid on the
insulation.

 2

1

Содержание HWR 50 plus

Страница 1: ...magnetic heating water regulator HWR 50 100 plus Operating manual magnetic einfach besser Anodenstrom...

Страница 2: ...heim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade Register HRA 571362 Registered c...

Страница 3: ...operating instructions 1 8 Conformity declaration 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator 2 2 Estimating the system volume 2 3 Water content of buffe...

Страница 4: ...ring 7 Maintenance 7 1 Functional check flow rate 7 2 Functional check Anode function 7 3 Backwashing desludging container cleaning 7 4 Monitoring water quality 7 5 Anode replacement 8 Troubleshooting...

Страница 5: ...l may be used for this purpose This operating manual must always be available at the place of operation 1 2 Area of application The magnetic Heating Water Regulator is used for the electrochemical tre...

Страница 6: ...e system from the water pressure or supply network Damaged systems should be decommis sioned immediately Faulty or damaged reaction vessels should only be repaired by specialist personnel authorised b...

Страница 7: ...to good engineering practice A leakage and original pressure inspection is carried out 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator The magnetic Heating W...

Страница 8: ...mp The advantage is that the treated water ends up directly in other system parts too Due to increasing the return flow temperature it is not suitable for condensing boiler techno logy System group re...

Страница 9: ...low before buffer Installation in main return flow before the buffer tanks if oxygenation is likely or circulating impu rities are present Anodenstrom Anodenstrom Anodenstrom Notes on bypass installat...

Страница 10: ...al residue Strongly contaminated old systems in particular those which have been pretreated using chemicals must be rinsed completely prior to installing an HWR For this purpose we recommend using our...

Страница 11: ...lling water in conjunction with an HWR A residual conductivity of 50 100 S cm must be retained When using a heating water regulator the filling water should not be softened using ion exchange 4 4 Use...

Страница 12: ...ntrol and document flow by means of the water metre provided 6 Success monitoring In order to guarantee the successful function of the regulator one should pay particular attention to the following po...

Страница 13: ...up however ideally every 2 years checking and documenting water chemistry with regards to pH values and conductivity during maintenance and consulting us if the values strongly deviate from our recom...

Страница 14: ...es mA on the display signalises how hard the HWR is working The display allows the following interpretations The display indicator is between 10 and 100 This is the normal operating range The lower th...

Страница 15: ...he device After the rinse process close the ball valve 3 and fill the HWR with water 6 After rinsing is concluded lower the magnet on the chain again Open the ball valve 1 on the supply line to the HW...

Страница 16: ...e layer is covering the anode which is preventing it from working Clean the anode with a wire brush then it should function again Otherwise check the display func tion using a 1 5V If it doesn t react...

Страница 17: ...sulation the automatic quick bleeder is faulty In this case it needs to be replaced the water metre is not turning Check if the pumps are working and all the valves are open If the water metre is stil...

Страница 18: ...ductivity upon initial operation Serial number Date Colour of rinsing water Water residue free yes no Metre reading if available Conductivity S cm pH value mA metre Anode replace ment yes no Executor...

Страница 19: ...Floor Centre outflow 745 5 895 5 F Depth incl ball valve 460 460 G Minimum distance 1000 1000 Inflow below outflow top 1 1 Performance data System water content 15000 l 35000 l Flow rate max 600l h m...

Страница 20: ...term nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade register HRA 571362 Regis...

Отзывы: