7.3 Backwashing, desludging, container cleaning

A specialist should carry out rinsing.
1. Stop the water flow.
2. Close the cut-off valves (1) in the inlet and outlet.
3. For rinsing, connect the water pipe to the drain valve (2).
Open the drain valve (2). Demineralised water is ideal for
rinsing.
4. Collect the rinsing water from the ball valve (3) using a
bucket or use a hosepipe to dispose of the rinsing water in the
drain.
5. Open the ball valve slowly (Figure 2 - 

) and raise the 

magnet
on the magnetic flux filter using the chain (Figure 2-

).

 
If no water comes out, carefully stick a wire (e.g. a welding
rod) through the ball valve (3) into the device in order to loosen
impurities. If this is not successful, you will need to open the
HWR, as described in the chapter on anode replacement.
Then it is necessary to clean the vessel through the upper
opening. In case of stubborn deposits on the walls, you can
use a diluted acid such as e.g. citric acid in order to clean the
container walls.

CAUTION!! Always neutralise the container after cleaning 
using acid. 

Rinse it until clean water runs out of the device. After the rinse process, close the ball valve (3) and fill the HWR with water.
6. After rinsing is concluded, lower the magnet on the chain again. Open the ball valve (1) on the supply line to the HWR again
commission the pumps again. Where applicable, check the flow volume of a heating water regulator in bypass installation.
7. Enter the rinsing process and measuring values in the maintenance form for the regulator.
The following rinsing intervals should be maintained:
- 1. Rinsing 4 weeks after installing the HWR
- 2. Rinsing after another 4 weeks 
 
As soon as the rinsing water is clean from the start, switch to rinsing annually. Otherwise rinse every 4-8 weeks. During normal
operation, the device should be rinsed and checked once a year as part of heating maintenance. If the HWR is installed in a
new system, you can skip the rinsing series following installation. In this case, it is sufficient to rinse once a year.

7.4 Monitoring water quality
The pH value and electrical conductivity of the heating water must be documented as part of maintenance. In addition, we
recommend a comprehensive water analysis from a laboratory.

Anodenstrom

1

m

3

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

0

0

0

0

0

1

2

3

minimum distance

1000 mm

flow

return

Anodenstrom

Figur

e 2

Содержание HWR 50 plus

Страница 1: ...magnetic heating water regulator HWR 50 100 plus Operating manual magnetic einfach besser Anodenstrom...

Страница 2: ...heim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade Register HRA 571362 Registered c...

Страница 3: ...operating instructions 1 8 Conformity declaration 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator 2 2 Estimating the system volume 2 3 Water content of buffe...

Страница 4: ...ring 7 Maintenance 7 1 Functional check flow rate 7 2 Functional check Anode function 7 3 Backwashing desludging container cleaning 7 4 Monitoring water quality 7 5 Anode replacement 8 Troubleshooting...

Страница 5: ...l may be used for this purpose This operating manual must always be available at the place of operation 1 2 Area of application The magnetic Heating Water Regulator is used for the electrochemical tre...

Страница 6: ...e system from the water pressure or supply network Damaged systems should be decommis sioned immediately Faulty or damaged reaction vessels should only be repaired by specialist personnel authorised b...

Страница 7: ...to good engineering practice A leakage and original pressure inspection is carried out 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator The magnetic Heating W...

Страница 8: ...mp The advantage is that the treated water ends up directly in other system parts too Due to increasing the return flow temperature it is not suitable for condensing boiler techno logy System group re...

Страница 9: ...low before buffer Installation in main return flow before the buffer tanks if oxygenation is likely or circulating impu rities are present Anodenstrom Anodenstrom Anodenstrom Notes on bypass installat...

Страница 10: ...al residue Strongly contaminated old systems in particular those which have been pretreated using chemicals must be rinsed completely prior to installing an HWR For this purpose we recommend using our...

Страница 11: ...lling water in conjunction with an HWR A residual conductivity of 50 100 S cm must be retained When using a heating water regulator the filling water should not be softened using ion exchange 4 4 Use...

Страница 12: ...ntrol and document flow by means of the water metre provided 6 Success monitoring In order to guarantee the successful function of the regulator one should pay particular attention to the following po...

Страница 13: ...up however ideally every 2 years checking and documenting water chemistry with regards to pH values and conductivity during maintenance and consulting us if the values strongly deviate from our recom...

Страница 14: ...es mA on the display signalises how hard the HWR is working The display allows the following interpretations The display indicator is between 10 and 100 This is the normal operating range The lower th...

Страница 15: ...he device After the rinse process close the ball valve 3 and fill the HWR with water 6 After rinsing is concluded lower the magnet on the chain again Open the ball valve 1 on the supply line to the HW...

Страница 16: ...e layer is covering the anode which is preventing it from working Clean the anode with a wire brush then it should function again Otherwise check the display func tion using a 1 5V If it doesn t react...

Страница 17: ...sulation the automatic quick bleeder is faulty In this case it needs to be replaced the water metre is not turning Check if the pumps are working and all the valves are open If the water metre is stil...

Страница 18: ...ductivity upon initial operation Serial number Date Colour of rinsing water Water residue free yes no Metre reading if available Conductivity S cm pH value mA metre Anode replace ment yes no Executor...

Страница 19: ...Floor Centre outflow 745 5 895 5 F Depth incl ball valve 460 460 G Minimum distance 1000 1000 Inflow below outflow top 1 1 Performance data System water content 15000 l 35000 l Flow rate max 600l h m...

Страница 20: ...term nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade register HRA 571362 Regis...

Отзывы: