Maintenance

In accordance with our maintenance manual, the device must be desludged and rinsed 4 weeks
after installation. During the construction phase, this maintenance process is repeated twice at
intervals of 4 weeks. It is important that the pumps are turned on during the construction phase,
and that the system water can circulate. The water should be clean during the final maintenance
date. If this is not the case, the maintenance process must be repeated every 8 weeks until the
water is clear. After that, the construction phase is concluded. After this, it is sufficient to service
the device once a year.

Functional check

The magnetic regulators have a display device which displays the anode activity. This display
must be checked regularly.

Professional use

In our understanding, professional use refers to:
- the device is installed according to our instructions, so the system water flow through the
device is guaranteed,
- our instructions regarding the filling water have been taken into account,
- during the construction phase, the device is maintained every 4-8 weeks according to our
instructions,
- during normal service, the device is serviced once a year,
- regular anode function checks,
- replacing anodes as soon as these are used up, however ideally every 2 years,
- checking and documenting water chemistry with regards to pH values and conductivity during
maintenance and consulting us if the values strongly deviate from our recommendations,
- clear documentation of maintenance work, e.g. on our maintenance form,

The success of electrochemical treatment can be measured. You should have the water checked once a year and record the
following values: If you would like to check whether the HWR 50/100 plus is actually providing corrosion protection, you can
check this by means of certain water parameters. Just have the heating water analysed once a year for pH value, conductivity,
hardness and dissolved metals. This will provide you with a long-term statistic and you can determine the corrosion protection
function by means of the improved values. The regular water analysis also serves as a warning system if problems occur.

7. Maintenance 

7.1 Functional check - flow rate

The even and constant throughflow of the HWR 50/100 plus is of fundamental importance. The flow should be at maximum
10l/min. Check and correct the water flow as part of maintenance.

• The supply line to the device must be at least 1”. A smaller line cross section can lead to insufficient water throughflow as 
well as problems with impurities.
• The supply line must not be regulated, the control valves must be open.
• Is the flow regulated by means of a Y-type valve or is the control valve opened by means of a flow regulator?

Содержание HWR 50 plus

Страница 1: ...magnetic heating water regulator HWR 50 100 plus Operating manual magnetic einfach besser Anodenstrom...

Страница 2: ...heim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade Register HRA 571362 Registered c...

Страница 3: ...operating instructions 1 8 Conformity declaration 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator 2 2 Estimating the system volume 2 3 Water content of buffe...

Страница 4: ...ring 7 Maintenance 7 1 Functional check flow rate 7 2 Functional check Anode function 7 3 Backwashing desludging container cleaning 7 4 Monitoring water quality 7 5 Anode replacement 8 Troubleshooting...

Страница 5: ...l may be used for this purpose This operating manual must always be available at the place of operation 1 2 Area of application The magnetic Heating Water Regulator is used for the electrochemical tre...

Страница 6: ...e system from the water pressure or supply network Damaged systems should be decommis sioned immediately Faulty or damaged reaction vessels should only be repaired by specialist personnel authorised b...

Страница 7: ...to good engineering practice A leakage and original pressure inspection is carried out 2 Layout of the electrochemical water treatment 2 1 Layout of the Heating Water Regulator The magnetic Heating W...

Страница 8: ...mp The advantage is that the treated water ends up directly in other system parts too Due to increasing the return flow temperature it is not suitable for condensing boiler techno logy System group re...

Страница 9: ...low before buffer Installation in main return flow before the buffer tanks if oxygenation is likely or circulating impu rities are present Anodenstrom Anodenstrom Anodenstrom Notes on bypass installat...

Страница 10: ...al residue Strongly contaminated old systems in particular those which have been pretreated using chemicals must be rinsed completely prior to installing an HWR For this purpose we recommend using our...

Страница 11: ...lling water in conjunction with an HWR A residual conductivity of 50 100 S cm must be retained When using a heating water regulator the filling water should not be softened using ion exchange 4 4 Use...

Страница 12: ...ntrol and document flow by means of the water metre provided 6 Success monitoring In order to guarantee the successful function of the regulator one should pay particular attention to the following po...

Страница 13: ...up however ideally every 2 years checking and documenting water chemistry with regards to pH values and conductivity during maintenance and consulting us if the values strongly deviate from our recom...

Страница 14: ...es mA on the display signalises how hard the HWR is working The display allows the following interpretations The display indicator is between 10 and 100 This is the normal operating range The lower th...

Страница 15: ...he device After the rinse process close the ball valve 3 and fill the HWR with water 6 After rinsing is concluded lower the magnet on the chain again Open the ball valve 1 on the supply line to the HW...

Страница 16: ...e layer is covering the anode which is preventing it from working Clean the anode with a wire brush then it should function again Otherwise check the display func tion using a 1 5V If it doesn t react...

Страница 17: ...sulation the automatic quick bleeder is faulty In this case it needs to be replaced the water metre is not turning Check if the pumps are working and all the valves are open If the water metre is stil...

Страница 18: ...ductivity upon initial operation Serial number Date Colour of rinsing water Water residue free yes no Metre reading if available Conductivity S cm pH value mA metre Anode replace ment yes no Executor...

Страница 19: ...Floor Centre outflow 745 5 895 5 F Depth incl ball valve 460 460 G Minimum distance 1000 1000 Inflow below outflow top 1 1 Performance data System water content 15000 l 35000 l Flow rate max 600l h m...

Страница 20: ...term nkheim Tel 49 7944 94199 0 Fax 49 7944 94199 19 info magnetic online de www magnetic online de Managing director Shareholder Michael Bader VAT ID No DE 255 018 730 Trade register HRA 571362 Regis...

Отзывы: