Flex EM/EX HazLoc System Instruction Manual
June 2019
Page 39 of 62
4.2.4
Dipswitch Settings
4.2.4.1 Interlocked Functions for EM Systems
Interlocked means the two adjacent pushbuttons cannot be activated simultaneously
as they will cancel each other out. Interlocked settings usually apply to a crane’s
forward and reverse motions.
Each dipswitch on the decoder/relay board corresponds to four (4) pushbuttons on
the transmitter handset or four (4) output relays on the decoder/relay board (
see
Fig. 13
and
Fig. 14
).
•
dip positions 1 - 4 correspond to PB1 and PB2 or PB5 and PB6 or PB9 and
PB10 on the transmitter handset or K1 and K2 or K5 and K6 or K9 and K10 on
the decoder/relay board
•
dip positions 5 - 8 correspond to PB3 and PB4 or PB7 and PB8 or PB11 and
PB12 on the transmitter handset or K3 and K4 or K7 and K8 or K11 and K12 on
the decoder/relay board
Fig. 13
Fig. 14
Manufacture preset
Dip
Settings
Function Descriptions
(left button/right button)
# of Relays
Used
0000
Normal/Normal
2
0001
ON/OFF
2
0010
Toggled/Toggled
2
0011
Normal/ FUNC (0 second)
2
0100
Normal/ FUNC (0.5 second)
2
0101
Normal/ FUNC (1.0 second)
2
0110
Normal/ FUNC (1.5 seconds)
2
0111
Normal/ FUNC (2.0 seconds)
2
RELAY FUNCTIONS
PB1~PB4
PB5~PB8
PB9~PB12
RELAY FUNCTIONS
PB1~PB4
PB5~PB8
PB9~PB12
JP7
JP6
JP5
JP4
JP3
JP2
JP1
SYSTEM FUNCTIONS TEST