IMPULSE®•G+/VG+ Series 4 Analog Input Installation Manual - August 2011
1-20
6. Related Parameters
The parameters outlined in the following sections are used to set up the drive for operation with the
option. Set parameters as needed. Parameter setting methods can be found in the drive Quick Start
Guide or Instruction Manual.
Parameter F2-01
Set parameter F2-01 to select between separate input channels or combined inputs on the option.
Setting 0: Separate Input Channels (default)
This setting replaces drive analog inputs A1, A2, and A3 with higher resolution signals in terminals
V1, V2, and V3 on the option.
H3-XX parameters set the function, gain, and bias for V1, V2, and V3. Refer to the drive Instruction
Manual for details on setting these parameters.
NOTE:
1. When F2-01 = 0, the option cannot be selected as frequency reference source. Setting
b3-01 to 3 (Option PCB as Frequency Reference Selection) when F2-01 is set to 0 will
trigger an oPE05 error.
2. When F2-01 is set to 0, the drive automatically detects the selected signal level for each
input. Parameters H3-01, H3-05, and H3-09 do not need to be set, and the previous
settings for these parameters are disregarded.
Figure 13: Using the Option for Multi-Function Analog Inputs