Magic-Pak V Series Скачать руководство пользователя страница 9

Page 9 of 21

507389-01

Issue 1504

x

 

3600

 

x

=

Cubic Feet Per Revolution

BTU/HR

 INPUT

 # Seconds Per Revolution

Heating

Value

Supply and Return Duct(s)

Provide duct(s) sized sufficiently to handle the larger of the air 

volumes for heating or cooling provided by this model.

Connect the supply duct to the top of the unit using canvas 

connections or other flexible connections to prevent noise 

transmission into the duct system.

To connect the return duct to the system, use a straight piece 

of duct 22” wide by 6” deep. Insert the duct into the return 

opening in the bottom of the unit and flange the duct over the 

existing flanges around the opening inside the unit. Make sure 

that all sides of the duct are flanged over to permit removal of 

the cooling chassis if required. Use a flexible connection to attach 

the remainder of the return duct. The return duct should be 

sealed to the unit casing and  must terminate outside the space 

containing the furnace.

Adjustments – Heating Section

Temperature Rise

At time of installation, the temperature rise must be adjusted to 

be within the range specified on the unit rating plate. See Table 2.

Pressure Regulator

The gas input must not exceed the figures shown on the rating 

plate.  The  unit  is  equipped  for  rated  inputs  with  manifold 

pressures of: 

3.5”  W.C.  for  natural  gas  and  10.0”  W.C.  for 

propane.

The manifold pressure can be measured by removing the pipe 

plug in the automatic gas valve. Connect a water manometer and 

measure the pressure.

Only small variations in gas input may be made by adjusting the 

regulator. 

In no case should the final manifold pressure vary 

more than 0.3” W.C. for natural gas or 0.7” W.C. for propane.

To adjust the regulator, turn the adjusting screw on the regulator 

clockwise to increase pressure and input or counterclockwise to 

decrease pressure and input.

For natural gas installations, check the burner rate by observing 

the gas meter (making sure that all other gas appliances are 

turned off). The test hand on the meter should be timed for 

at least one revolution. Note the number of seconds for one 

revolution.

Adjustments – Cooling Section (HWC models)

No adjustments are required or should be attempted regarding 

any of the components of the cooling chassis. The chassis should 

be checked to see that none of the wiring is loose or missing.

Cooling chassis is charged with R410A refrigerant.

 

Model

Number

Filter Area

(sq. in.)

HWC9-12

300

HWC9-18

480

HWC9-24

480

HWC9-30

480

Minimum Required Surface Area

for Disposable Filters

Table 1

Thermostat

Install the thermostat according to the directions furnished with 

it.  The thermostat must be located on an inside wall where it will 

not be affected by drafts, sunlight, or any other heat producing 

appliances.  Connect the thermostat wires to the low voltage 

leads on top of the unit following the wiring diagram attached 

to the unit.  The heat anticipator setting is 0.50 amp.

Air Filter

All indoor return air must be filtered. A permanent-type filter is 

furnished with the unit, located directly behind the access panel.  

Removing the panel permits access to the filter. See Figure 5.

If an installation is made in which it is more desirable to mount the 

filter exterior to the unit, in the return duct work or elsewhere, the 

permanent filter can be used or replaced with a disposable filter.  

If a disposable filter is used, refer to the information provided in 

Table 1 when sizing the disposable filter.

Содержание V Series

Страница 1: ...not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Installati...

Страница 2: ...nit must be permanently installed per these installation instructions A room thermostat must control the furnace The use of fixed jumpers that will provide continuous heating is not allowed The return...

Страница 3: ...s must be installed in the system and must be maintained during construction Air filters must be replaced upon construction completion The input rate and temperature rise must be set per the furnace r...

Страница 4: ...Be certain that the plastic drain tube has free drainage and is not crimped or flattened at any bend Installing Without a Wall Sleeve Refer to the following directions and Figure 1 for guidance in in...

Страница 5: ...ent weld piping to street elbow Furnace condensate drain component locations Side exit Condensate Trap Side panel Upper Drain hose From Collector box Lower drain hose To drain fitting reposition and r...

Страница 6: ...ecuring the drain fitting to the division panel 3 Remove the drain fitting and rotate it so that it faces the front of the furnace 4 Replace the securing screw 5 Disconnect lower drain hose from drain...

Страница 7: ...ps for each appliance connected to the common venting system 7 After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined...

Страница 8: ...dition for installations in Canada See rating plate for correct wire ampacity for the cooling chassis required and size wire accordingly The furnace must be isolated from the gas supply piping system...

Страница 9: ...sure vary more than 0 3 W C for natural gas or 0 7 W C for propane To adjust the regulator turn the adjusting screw on the regulator clockwise to increase pressure and input or counterclockwise to dec...

Страница 10: ...835 34 TAP 4 COOL 208 or 230 800 775 755 735 TAP 5 COOL 208 or 230 880 860 835 815 TAP 1 HEAT 208 or 230 645 59 615 62 590 65 565 N A TAP 2 HEAT 208 or 230 780 49 755 51 730 52 710 54 TAP 3 HEAT 208 o...

Страница 11: ...could result in safety shutdown of the burners 1 Adjust to the highest achievable temperature rise within the rise and static pressure ranges specified on the rating plate Depending on specific model...

Страница 12: ...nce will try again Blower Control The blower will start approximately 30 seconds after the burners ignite and will stop approximately 120 seconds after the thermostat is satisfied The time delay is pr...

Страница 13: ...rnace be inspected annually by a qualified service person Inducer prover switch Ignition Control board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Gas Manifold R...

Страница 14: ...efer to Figure 8 Remove the two screws on the burner assembly that secure it to the mounting brackets The mounting brackets contain pins to locate the assembly and hold it in place after the screws ar...

Страница 15: ...Page 15 of 21 507389 01 Issue 1504 BURNER MANIFOLD ASSEMBLY REMOVAL Step 7 Mounting Brackets Step 8 Step 9 Step 10 Burner Manifold Assembly Figure 8...

Страница 16: ...t without removing any other components To remove the rollout switch 1 Disconnect electrical service and turn off gas to the appliance 2 Disconnect the orange leads at the rollout switch 3 Remove the...

Страница 17: ...Page 17 of 21 507389 01 Issue 1504 Ignition board Bracket removal Tabs on Cold End Header box Figure 9 Press down on locking tab then slide bracket Slots on ignition board bracket...

Страница 18: ...e unit carefully pry the round portion of the orifice from the inducer inlet 3 Remove the indicator tab from the inducer mounting foot Model Orifice color HWC9N22 Blue HWC9N33 Black HWC9N44 Gray HWC9N...

Страница 19: ...assis normally requires no maintenance since it is a closed self contained system System is charged with R410A refrigerant Periodic maintenance is limited to Cleaning the air filter Follow directions...

Страница 20: ...Page 20 of 21 507389 01 Issue 1504 Figure 11...

Страница 21: ...Page 21 of 21 507389 01 Issue 1504 NOTES...

Отзывы: