Page 10 of 21
507858-01
Issue 1922
Model
Gas Heating
Indoor
Blower
Speed
0.1 “w.c.
0.2 “w.c.
0.3 “w.c.
0.4 “w.c.
0.5 “w.c.
Rise
Range
(F°)
Mid
Rise
(F°)
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
SCFM
W
atts
Temp
Rise
2 T
on
15MGE4-1
1-241*P
15-45
30
TAP 1
(FAN)
450
49
---
400
52
---
345
56
---
285
59
---
235
65
---
TAP 2
(COOL)†
815
206
---
780
210
---
750
215
---
720
219
---
690
224
---
TAP 3
(COOL)
910
273
---
880
278
---
850
283
---
820
287
---
785
286
---
TAP 4
(HEAT)*
370
36
30
320
38
35
250
42
45
N/A
N/A N/A
N/A
N/A N/A
TAP 5
(HEAT)
N/A
N/A N/A
N/A
N/A N/A
465
82
24
420
85
26
370
90
30
24MGE4-1
1-241*P
25-55
40
TAP 1
(FAN)
450
49
---
400
52
---
345
56
---
285
59
---
235
65
---
TAP 2
(COOL)†
815
206
---
780
210
---
750
215
---
720
219
---
690
224
---
TAP 3
(COOL)
910
273
---
880
278
---
850
283
---
820
287
---
785
286
---
TAP 4
(HEAT)*
450
49
40
400
52
45
345
56
52
N/A
N/A N/A
N/A
N/A N/A
TAP 5
(HEAT)
N/A
N/A N/A
N/A
N/A N/A
530
99
34
490
103
37
450
107
40
36MGE4-1
1-241*P
30-60
45
TAP 1
(FAN)
450
49
---
400
52
---
345
56
---
285
59
---
235
65
---
TAP 2
(COOL)†
815
206
---
780
210
---
750
215
---
720
219
---
690
224
---
TAP 3
(COOL)
910
273
---
880
278
---
850
283
---
820
287
---
785
286
---
TAP 4
(HEAT)*
600
89
45
560
93
48
520
96
52
485
100
56
N/A
N/A N/A
TAP 5
(HEAT)
N/A
N/A N/A
700
148
38
665
153
40
635
157
42
600
162
45
48MGE4-1
1-241*P
35-65
50
TAP 1
(FAN)
450
49
---
400
52
---
345
56
---
285
59
---
235
65
---
TAP 2
(COOL)†
815
206
---
780
210
---
750
215
---
720
219
---
690
224
---
TAP 3
(COOL)
910
273
---
880
278
---
850
283
---
820
287
---
785
286
---
TAP 4
(HEAT)*
720
145
50
675
151
53
635
157
56
595
164
60
N/A
N/A N/A
TAP 5
(HEAT)
N/A
N/A N/A
820
223
44
780
232
46
745
238
48
710
246
50
60MGE4-1
1-241*P
40-70
55
TAP 1
(FAN)
450
49
---
400
52
---
345
56
---
285
59
---
235
65
---
TAP 2
(COOL)†
815
206
---
780
210
---
750
215
---
720
219
---
690
224
---
TAP 3
(COOL)
910
273
---
880
278
---
850
283
---
820
287
---
785
286
---
TAP 4
(HEAT)*
810
182
55
775
186
58
745
191
60
710
195
63
680
200
66
TAP 5
(HEAT)
910
248
49
885
253
51
860
258
52
830
265
54
800
270
56
N/A: Do not operate unit using this blower speed at this external static pressure.
† As shipped speed for Cooling operation. Blower speed must be field adjusted to speed Tap 3 for higher duct static applications.
* As shipped speed for Heating operation. Blower speed must be field adjusted to Speed Tap 5 for higher duct static applications.
Table 4.
Blower Performance (208V or 230V)