background image

507390-01

Page 3 of 5

Issue 1733

Installing without a Wall Sleeve

Provide an opening in an outside wall with minimum 

dimensions 28” side and 43-1/4” high (see Figure 1). Local 

ordinances may require a steel lintel to support the wall 

above the opening. This opening must be square in all 

corners.

Provide support under the unit, inside the building. Make 

sure that the inside support does not block the return air. 

The unit should be installed level or pitched slightly to the 

outside of the building so that rain water will drain from the 

unit.

The use of resilient cork or rubber material between the 

unit and the supports is recommended to minimize any 

transmission of noise or vibration.

Seal the space between the unit and the building opening 

using a non-hardening caulking compound. The seal must 

be weather-tight to prevent entrance of moisture and water 

into the building. Make sure that the drain holes in the base 

are not plugged with caulking.

Installing with a Wall Sleeve

Install the wall sleeve in accordance with instructions 

furnished with the sleeve.

Make sure that the gaskets attached to the sleeve are not 

damaged.

Seal the space between the wall sleeve and the building 

opening using non-hardening caulking compound. This 

seal must be watertight.

Assure that the unit is completely seated against the 

gaskets on the wall sleeve.

Slide the unit into the sleeve. When properly nested, the 

angle on top of the unit should line up with the top flange of 

the sleeve and should almost touch. Fasten the unit to the 

sleeve with five screws furnished with the sleeve.

The sleeve is not intended as the sole support for the 

unit. An additional support must be provided near the 

return opening on the unit for adequate support. The 

use of vibration isolation material between the unit and 

the support is recommended.

 CAUTION

Condensate Drain

To install the condensate line, connect one end of the 

plastic tube over the 5/8” O.D. fitting in the center of the 

condensate pan. Connect the other end to the drain tube 

running to the open trap (see Figure 2).

The drain line should pitch gradually downward at least 1” 

per 10 feet of horizontal run to the open drain trap.

Be certain that the plastic drain tube has free drainage and 

is not crimped or flattened at any bend.

Test drainage by pouring water into the drain pan under the 

evaporator and see that it is removed rapidly through the 

drain tubing.

The plastic drain connection is provided so that it may 

be disconnected from the permanent drain tubing in 

the building without unsoldering in the event it become 

necessary to remove the refrigeration chassis assembly.

Figure 2. EWC Drain Installation

Drain Pan

Open Drain Trap

Return 

Air Duct

To Open 

Drain Trap

Alternative 

Method

5/8

" I.D.

Plastic Tube

(Supplied)

Top of Drain Tube

Must be Below

Bottom of Drain Pan

Drain Tube - Pitch 1" 

for every 10 ft.

(Field Supplied)

Electrical Connections

All supply wiring should be done in accordance with 

the National Electric Code, or with local codes, where 

they prevail. Any alternation of internal wiring will void 

certification and warranty.

NOTE: 

Units are factory wired for a 230-volt power supply. 

If power supply is 208 volts, it will be necessary to change 

a wire connection on unit transformer from 240V terminal 

to 208V terminal as shown on the wiring diagram.

The rating plate indicates the operating voltage, phase, 

ampacity, and maximum circuit protection. Minimum 

operating voltage of the 208-230 volt model is 197 volts. 

Units must never be installed where voltage exceeds 10% 

of voltage indicated on the rating plate.

Failure of the compressor as a result of operation on 

improper voltage voids the compressor replacement 

warranty.

A separate electric line for each circuit should be run 

through a separate fused disconnect, from the main house 

panel to the supply terminal block located in the unit.

Thermostat

Install the thermostat according to directions furnished 

with it. Select a location which will measure true air 

temperature. Locate on an inside wall, away from drafts, in 

a room having the greatest exposure.

Connect the wires to the terminal block on the unit following 

the wiring diagram attached to the unit.