Installation

Installation shall be made in accordance with local utility 

requirements and any other authorities having jurisdiction.

General

The EWC V-Series™ unit is a self-contained electric 

heating and cooling unit. This unit has been examined for 

compliance with Canadian Standards Association CAN/

CSA-C22.2 No. 236 (latest edition) and Underwriters 

Laboratories UL 1995. This unit is also in compliance 

with A.M.R.I. Performance Standard 390 and Canadian 

Standard CAN/CSA-C656 (latest edition) Performance 

Standard in effect at the time of manufacture. Any 

alterations of internal wiring will void these listings and 

warranties.

Inspection

This unit is shipped in one package, completely assembled 

and wired. The drain tubing is in the cooling compartment 

behind the filter access panel.

If any damage is found, proper notation should be made 

on the carrier’s freight bill. Damage claims should be filed 

with the carrier at once. Check the rating plate to confirm 

heating and cooling capacities.

NOTE: 

Be sure to remove the chassis hold down brackets 

from the outdoor side of unit before installation. These 

brackets are located below the louver panels.

Location

The unit is approved for indoor installation only. It must not 

be installed completely outside. Duct connections as well 

as service access must be inside the building. The interior 

portions of the unit may be surrounded by a closet with 

clearances to combustible material held to 0” at sides, 2” 

top, and 0” front and plenum. The floor may be combustible.

The  grille  side  of  the  unit  may  be  flush  with,  or  extend 

beyond, the face of the exterior wall, but should not be 

recessed more than 2” from the face of the building and 

should not be obstructed with trees, landscape materials, 

or building structure.

If the unit is to be enclosed, provisions should be made 

allowing access to the indoor side of the unit for changing 

filters and for inspection. At least 29” of unobstructed space 

should be provided in front of the indoor side, whether 

enclosed or not, to permit removal of the cooling chassis 

should repairs or inspection be required.