1) All refrigerant in the system has leaked out Analysis of Trouble Leak points in the 

refrigerating system have not been found and repaired timely ,thus resulting in the 

total escape of refrigerant .There are two kinds of leakage :I) slow leakage for instance 

,when we want to use a refrigerator that has been put out of quite a long time ,we 

find the leakage of refrigerant ,or in the course of its operation ,we have found that 

the refrigerator is gradually becoming not so cold and finally no refrigerating cab be 

achieved ; ii) fast leakage in that case ,all the refrigerant will escape swiftly due to abrupt 

rupture of system tubing . Symptoms of total leakage of refrigerant are mainly asfollows 

: the compressor can be started easily (if there is no damage to the compressor parts) 

and its operating current becomes low ,its gas suction pressure is high and discharge 

pressure is lower ,the gas discharge tube feels rather cold ,no sound of gas eruption 

from the liquid in the evaporator can be heard ,and no will gush out of the process 

tube if you cut it open after shutdown . Remedy Check the whole machine , particularly 

those locations which are liable to leak .After leak points have been found ,repair them 

or replace them with new parts according to specific circumstances ,then evacuate the 

system and finally charge refrigerant.

2) Refrigerating system has been clogged

a) Clogged with Ice

Analysis of Trouble The dryness treatment for the major parts in the refrigerating system 

has been performed improperly, the effect of air purging for the whole system is not 

good ,or the water content in the refrigerant is out of standard ,all these will cause the 

expansion valve to be clogged with ice .The symptom for this trouble are as follows 

:the refrigerator sometimes can refrigerate and sometimes cannot :the refrigerator 

compartment works normally at the beginning ,but after working for a certain period of 

time ,frosting begins at the clogged position ,evaporation temperature reaches below 

0°C , water will accumulate at the narrow part of the capillary and clog it gradually ,then 

frost begins to melt at the evaporator ,no gas flowing sound can be heard ,and the gas 

suction pressure assumes a state of vacuum .Note that these phenomena will appear 

intermittently ; sometimes ,the refrigerator works well ,and sometimes not well .In order 

to determine whether it is clogged with ice ,heat the suspicious points with hot water to 

make ice melt ,and after a while if a gas flowing sound resulting from an abrupt gush is 

heard and the gas suction pressure rises as well ,itcan be confirmed that the trouble is 

severely affected ,thus causing a poor refrigerating effect . Remedy It is quite difficult to 

determine whether this trouble is caused by the refrigerating oil left in the evaporator 

tubing ,because this kind of phenomenon and other several trouble are tends to be 

confused .Generally speaking ,you can make a judgment based on the frost formed on 

the evaporator .If the frost does not cover the evaporator , and moreover ,it is loosely 

formed ,you can make a judgment that the deterioration of refrigerating effect isdue 

to the accumulation of refrigerating oil left in the evaporator tubing in case no other 

troubles have been found . To clear off refrigerating oil left in the evaporator ,dismantle 

the evaporator ,purge it thoroughly and then dry it .In case it is difficult to dismantle it 

,charge refrigerant from the evaporator inlet to wash it several times ,then purge and 

dry it with nitrogen .

7) Flowing obstructed in refrigerating system

Analysis  of  Trouble  Because  the  refrigerating  system  was  originally  not  purged 

thoroughly ,some of the filter screen meshes have been clogged by dirt accumulated 

in the filter after using it for a certain time of period ,thus resulting in a decrease in flow 

rate ,and hence a poorer refrigerating effect . The abnormal phenomena caused by this 

kind of slight clogging in the system are as follows: the gas discharge pressure is lower 

,the temperature of discharged gas drops down ,the position clogged has a temperature 

lower than that in normal conditions ,and for a severe clogging ,even dew condensation 

as frosting may appear . Remedy Purge the tubing ,and after replacing the dry filter with 

a new one or clearing it thoroughly ,recharge the system with refrigerant and seal the 

charging port .

B. No Refrigerating

The phenomenon that the compressor runs normally ,but no frost (or only a little frost 

) appears on the evaporator ,and the refrigerator temperature does not drop down 

is called «no refrigerating». There are many causes for this trouble and it is relatively 

complicated  ,  too  .  In  servicing  ,special  attention  to  finding  direct  causes  for  this 

phenomenon .Three main potential causes for this trouble are analyzed

below :

Содержание MCSF-5585BSS

Страница 1: ...Please read the following instructions completely before operating this appliance INSTRUCTION MANUAL REFRIGERATOR MCSR 6085W MCSR 6085B MCSR 6085BSS MCSR 5585W MCSR 5283W MCSF 5585BSS ...

Страница 2: ...ricefromsurfacesoftherefrigeratorand orfreezercompartment Doingsocouldpuncturethecoolingcoil causingtheunittoloseitsabilitytomaintaincoldtemperaturesandvoidingthewarranty SeetheCareandCleaningsectionforinstructionsondefrostingtherefrigeratorand or freezercompartment ...

Страница 3: ...ECTRICITY 4 operationinstruction 5 ControlSettings 5 Abouttherefrigeratorfeatures 6 Careandcleaningoftherefrigerator 6 Careandcleaningoftherefrigerator 6 Careandcleaningoftherefrigerator 7 Preparingtoinstalltherefrigerator 8 Troubleshootingtips 10 Safetyprecautions 12 ...

Страница 4: ...sibility andobligationtohaveitreplacedwithaproperlygrounded3 prongwalloutlet The refrigerator should always be plugged into its own individual electrical outlet whichhasavoltageratingthatmatchestheratingplate SafetyInstructions IMPORTANTSAFETYINFORMATION READALLINSTRUCTIONSBEFOREUSING UsethisapplianceonlyforitsintendedpurposeasdescribedinthisOwner sManual SAFETYPRECAUTIONS Whenusingelectricalappli...

Страница 5: ...hemilktest Placeacontainerofmilkonashelfandcheckitadaylater Ifthemilkis toowarmortoocold adjustthetemperaturecontrol Afterchangingthecontrol allow This provides the best performance and also prevents overloading house wiring circuitswhichcouldcauseafirehazardfromoverheatedwires Never unplug your refrigerator by pulling on the power cord Always grip plug firmlyandpullstraightoutfromtheoutlet Repair...

Страница 6: ...nside To help prevent odors leave an open box of baking soda in the refrigerator Unplug the refrigerator before cleaning If this is not practical wring excess moisture out of sponge or cloth when cleaning around the control Use warm water and baking soda solution aboutatablespoon 15ml ofbakingsodatoaquart 1liter ofwater Thisbothcleans andneutralizesodors Rinseandwipedry Otherpartsoftherefrigerator...

Страница 7: ...er unscrew the lens and pull horizontally until the lens is removed Gently unscrew the light bulb and replace with a bulb of 15 watts orless Careandcleaningoftherefrigerator Defrosting Defrost whenever frost on the wall of the Freezer compartment becomes 164 4 mm thick Never use a sharp or metallic instrument to remove frost as it may damage the cooling coils A punctured cooling coil will cause se...

Страница 8: ...lyandcarefully RefrigeratorLocation Do not install the refrigerator where the temperature will go below 50 F 10 C becauseitwillnotrunoftenenoughtomaintainpropertemperatures Installitonafloorstrongenoughtosupportitfullyloaded Donotinstallitcloserthan5 13cm nexttoarange Donotinstallitinarecessedarea Donotbuildintherefrigerator Clearances Allowthefollowingclearancesforeaseofinstallationandproper airc...

Страница 9: ...gerator 12 Re install the adjustable legs Insure that the smaller leg is on the same side as the bottomhinge 13 Placethefreshfooddooronthebottomhinge 14 Place the bottom peg of the middle hinge in the fresh food door Re install middle hinge Make sure the fresh food door is aligned with the refrigerator cabinet before tighteningscrews 15 Place the freezer door on the top peg of the middle hinge Pla...

Страница 10: ...10 Troubleshootingtips Savetimeandmoney ...

Страница 11: ...Safety precautions ...

Страница 12: ...12 Safetyprecautions ...

Страница 13: ...n Thickinsulationforenergyefficiency SystemFlowChart 1 SchematicdiagramofSystemFlowChart 2BriefDescriptionofSystemFlowChart Allmodelsareadirectcoolingsingle systemrefrigeratororfreezer Whenthe refrigeratororfreezerisjustpoweredon therefrigerantflowsinthesequence 1 2 3 4 5 1 ...

Страница 14: ...ooting 1 Nocooling CircuitDiagram 1SchematicCircuitDiagram BriefDescriptionofControlPrinciple Amechanicaltypeofallthecontrolisgenerallyadopted Thethermostatdirectlycontrolsthestartandstopofcompressor and hencetherefrigeratortemperature ...

Страница 15: ...15 3Coolingcapacityisinsufficient 2Thecompressordoesn tstop ...

Страница 16: ...ststoppedrunning arumblingsoundcanbeheardfrominsideits evaporator Thisisasoundcausedbytheflowingofrefrigerantintheevaporatortubing Because the pressure difference is still greater after the compressor has just stopped running the refrigerant will flow for a certain time therefore this sound is a normal phenomenon 2 Aclicksoundcanoftenbeheardfromtherefrigerator Thisisa normalsoundproducedbythepull ...

Страница 17: ... inside the compressor this means that some moving parts have loosened note to differentiate this sound from thoseformedduringstartingorstoppingthecompressor 4 For the direct cooling refrigerator a kind of irregular crack sound can be often heard when the compressor is running for a certain period of time or has just stopped its running Thissoundiscausedbythestressreliefduetoexpansionandcontractio...

Страница 18: ...tothosepartsthatareliableto leak check main connection points for oil seepage and tubing for cracks If there is no b ListentothesoundcausedbytheflowingofgasintheevaporatorOpentherefrigerator doorwhilethecompressorisinoperation inclineyourearandlistenattentivelythegas flow sound inside the evaporator If it sounds like gentle whistling accompanied by a sound similar to water flowing this is the soun...

Страница 19: ...or the heat conduction effect will be severer leak point charge the system with nitrogen and detect leak points with the commonlyadoptedmethod repairthem evacuate chargethesystemwithrefrigerant andthenturnontherefrigeratortomakeatestrun 2 Toomuchrefrigerantchargedintothesystem AnalysisofTrouble a In case the amount of refrigerant charged into the system exceeds its nominal capacity the superfluous...

Страница 20: ...ently sometimes therefrigeratorworkswell andsometimesnotwell Inorder todeterminewhetheritiscloggedwithice heatthesuspiciouspointswithhotwaterto make ice melt and after a while if a gas flowing sound resulting from an abrupt gush is heard and the gas suction pressure rises as well itcan be confirmed that the trouble is severelyaffected thuscausingapoorrefrigeratingeffect RemedyItisquitedifficultto ...

Страница 21: ...he system with a properquantityofrefrigerant b Air left in the system Analysis of Trouble The residual air in the system will circulate togetherwiththerefrigerantinthesystem Themajorsymptomscausedbythisresidual causedbyiceclogging RemedyIfthereistoomuchmoistureintherefrigeratingsystem itisadvisabletoreleasetherefrigerant purgethetubingwithnitrogen andthencharge the system with the filtered refrige...

Страница 22: ...due to the leakage of temperature airishighergasdischargepressure higherdischargedgastemperature thegasdischarge tubing is considerably hot when you feel it with your hand and poorer refrigerating effect Furthermore the gas discharge pressure will exceed its normal value when the compressor has run for a period not too long thus making the protective relay actuate andbringtoastoppage RemedyCheckup...

Страница 23: ...rationtemperatureinthesystemistoo high thetemperaturesensingagentinthetemperaturesensorisalsohotter therefore sensing agent from the temperature sensor Remedy Remove the relay cover to check up its contacts if they are open this means that the original setting is not properly set ortemperaturesensingagenthasleakedoutofthetemperaturesensor Trytoturnthe adjusting stem of this value in the direction ...

Страница 24: ...ndthattherefrigerantinthesystemisinsufficientinquantity recharge it with refrigerant In case clogging occurs disassemble the part where it is blocked If the evaporation temperature is too high settle this problem with an appropriatequantityofrefrigerant 3 No stoppage of compressor due to damaged heat insulation layer inside case body and ordoorsealAnalysisofTroubleWhentheheat insulationlayerinside...

Страница 25: ...25 ...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...28 ...

Страница 29: ...29 ...

Страница 30: ...30 ...

Страница 31: ...31 ...

Страница 32: ......

Отзывы: