recharge the system with refrigerant .

4) Low efficiency of compressor

Analysis of Trouble Low efficiency of a refrigerating compressor refers to the actual 

reduction  of  gas  discharge  capacity  ,and  hence  the  corresponding  reduction  of 

refrigerating  capacity  ,under  the  condition  that  the  refrigerant  in  the  system  is 

unchanged .This phenomenon occurs mostly when the compressor has been used for 

quite a long time ,its moving parts have worn to a considerable degree ,fit clearance 

between  various  parts  have  increased  and  sealing  property  of  its  gas  valve  has 

deteriorated ,resulting in an decrease in its actual gas discharge capacity . Methods of 

Judgment Measure the high and low pressures with pressure gauges to see whether 

they are normal .If an abnormal sound comes from the compressor or the temperature 

of its causing is too high ,Cut the discharge port open and operate the compressor ,feel 

it if there is pressure at the discharge port with your finger (For a normal compressor ,its 

discharge port is difficult to be blocked with your finger if you just apply a little effort).

5) Too thick frost layer formed on evaporator

Analysis of Trouble If a direct cooling refrigerator is to be used for a prolonged period 

of time ,be sure to defrost its evaporator regularly ;if you fail to do so ,the frost layer on 

the evaporator tubing will become thicker and thicker .Heat conduction will be severely 

affected when the whole tubing is wrapped with a transparent ice layer ,and finally the 

temperature in the refrigerator cannot drop down to the prescribed range . Remedy 

Turn the refrigerator off ,and make preparations for defrosting ,open the refrigerator 

door to let the air come in ,or use a fan to speed up air flowing so as to shorten the time 

needed for defrosting .Never strike the frost layer with any iron tools or wood stick in 

order to avoid damage to the evaporator tubing .

6) Refrigerating oil left in evaporator tubing

Analysis of Trouble During the process of refrigerating cycles ,a little refrigerating oil 

may remain in the evaporator tubing ,and after a longer time of operation ,if there is 

considerable refrigerating oil left in the evaporator ,the heat conduction effect will be 

severer leak point ,charge the system with nitrogen and detect leak points with the 

commonly adopted method ,repair them ,evacuate ,charge the system with refrigerant 

,and then turn on the refrigerator to make a test run .

2) Too much refrigerant charged into the system

Analysis of Trouble

a)  In  case  the  amount  of  refrigerant  charged  into  the  system  exceeds  its  nominal 

capacity ,the superfluous refrigerant will of course take some  space of the evaporator 

,thus reducing its heat-dissipation area and hencethe refrigerating efficiency of the 

system .The abnormal phenomena caused by this reason are as follows :the gas suction 

and exhaust pressures are generally higher than their respective normal values ,the 

temperature of its condenser is higher and the electric current of the compressor rises 

,loose frost forms on the evaporator ,the refrigerator temperature drops slowly ,and 

frost appears on the gas return tube .

b) In case excessive refrigerant has been charged ,the liquid refrigerant that cannot 

evaporates in the evaporator will return to the compressor ,and thus a phenomenon 

of  «liquid  striking»  will  occur  .The  liquid  refrigerant  evaporates  and  effervesces  as 

soon as it flows into the refrigerating oil at the bottom of compressor .If the condition 

is severe ,foams will fill all over inside the compressor housing and be sucked by the 

piston ,causing damage to the components of compressor . Remedy According to the 

operating procedures ,it is mandatory to turn the machine off ,and several minutes later 

,open the refrigerant charging tube and et the refrigerant escape from it ,replace the dry 

filter ,recharge refrigerant after evacuating ,and then seal the charging port .

3) There is air left in the refrigerating system

Analysis of Trouble Residual air in the refrigerating system will reduce its refrigerating 

efficiency .The prominent phenomena are the increase in its gas suction and exhaust 

pressures (however ,the gas exhaust pressure will not exceed its rated value ),obvious 

increase in temperature in the segment from the compressor outlet to the condenser 

inlet .Because there is air in the system ,both the gas exhaust pressure and temperature 

will rise ,and moreover ,the gas flowing sound is intermittent and obviously louder . 

Remedy After shut down for several minutes ,open the tubing ,evacuate it and then 

Содержание MCSF-5585BSS

Страница 1: ...Please read the following instructions completely before operating this appliance INSTRUCTION MANUAL REFRIGERATOR MCSR 6085W MCSR 6085B MCSR 6085BSS MCSR 5585W MCSR 5283W MCSF 5585BSS ...

Страница 2: ...ricefromsurfacesoftherefrigeratorand orfreezercompartment Doingsocouldpuncturethecoolingcoil causingtheunittoloseitsabilitytomaintaincoldtemperaturesandvoidingthewarranty SeetheCareandCleaningsectionforinstructionsondefrostingtherefrigeratorand or freezercompartment ...

Страница 3: ...ECTRICITY 4 operationinstruction 5 ControlSettings 5 Abouttherefrigeratorfeatures 6 Careandcleaningoftherefrigerator 6 Careandcleaningoftherefrigerator 6 Careandcleaningoftherefrigerator 7 Preparingtoinstalltherefrigerator 8 Troubleshootingtips 10 Safetyprecautions 12 ...

Страница 4: ...sibility andobligationtohaveitreplacedwithaproperlygrounded3 prongwalloutlet The refrigerator should always be plugged into its own individual electrical outlet whichhasavoltageratingthatmatchestheratingplate SafetyInstructions IMPORTANTSAFETYINFORMATION READALLINSTRUCTIONSBEFOREUSING UsethisapplianceonlyforitsintendedpurposeasdescribedinthisOwner sManual SAFETYPRECAUTIONS Whenusingelectricalappli...

Страница 5: ...hemilktest Placeacontainerofmilkonashelfandcheckitadaylater Ifthemilkis toowarmortoocold adjustthetemperaturecontrol Afterchangingthecontrol allow This provides the best performance and also prevents overloading house wiring circuitswhichcouldcauseafirehazardfromoverheatedwires Never unplug your refrigerator by pulling on the power cord Always grip plug firmlyandpullstraightoutfromtheoutlet Repair...

Страница 6: ...nside To help prevent odors leave an open box of baking soda in the refrigerator Unplug the refrigerator before cleaning If this is not practical wring excess moisture out of sponge or cloth when cleaning around the control Use warm water and baking soda solution aboutatablespoon 15ml ofbakingsodatoaquart 1liter ofwater Thisbothcleans andneutralizesodors Rinseandwipedry Otherpartsoftherefrigerator...

Страница 7: ...er unscrew the lens and pull horizontally until the lens is removed Gently unscrew the light bulb and replace with a bulb of 15 watts orless Careandcleaningoftherefrigerator Defrosting Defrost whenever frost on the wall of the Freezer compartment becomes 164 4 mm thick Never use a sharp or metallic instrument to remove frost as it may damage the cooling coils A punctured cooling coil will cause se...

Страница 8: ...lyandcarefully RefrigeratorLocation Do not install the refrigerator where the temperature will go below 50 F 10 C becauseitwillnotrunoftenenoughtomaintainpropertemperatures Installitonafloorstrongenoughtosupportitfullyloaded Donotinstallitcloserthan5 13cm nexttoarange Donotinstallitinarecessedarea Donotbuildintherefrigerator Clearances Allowthefollowingclearancesforeaseofinstallationandproper airc...

Страница 9: ...gerator 12 Re install the adjustable legs Insure that the smaller leg is on the same side as the bottomhinge 13 Placethefreshfooddooronthebottomhinge 14 Place the bottom peg of the middle hinge in the fresh food door Re install middle hinge Make sure the fresh food door is aligned with the refrigerator cabinet before tighteningscrews 15 Place the freezer door on the top peg of the middle hinge Pla...

Страница 10: ...10 Troubleshootingtips Savetimeandmoney ...

Страница 11: ...Safety precautions ...

Страница 12: ...12 Safetyprecautions ...

Страница 13: ...n Thickinsulationforenergyefficiency SystemFlowChart 1 SchematicdiagramofSystemFlowChart 2BriefDescriptionofSystemFlowChart Allmodelsareadirectcoolingsingle systemrefrigeratororfreezer Whenthe refrigeratororfreezerisjustpoweredon therefrigerantflowsinthesequence 1 2 3 4 5 1 ...

Страница 14: ...ooting 1 Nocooling CircuitDiagram 1SchematicCircuitDiagram BriefDescriptionofControlPrinciple Amechanicaltypeofallthecontrolisgenerallyadopted Thethermostatdirectlycontrolsthestartandstopofcompressor and hencetherefrigeratortemperature ...

Страница 15: ...15 3Coolingcapacityisinsufficient 2Thecompressordoesn tstop ...

Страница 16: ...ststoppedrunning arumblingsoundcanbeheardfrominsideits evaporator Thisisasoundcausedbytheflowingofrefrigerantintheevaporatortubing Because the pressure difference is still greater after the compressor has just stopped running the refrigerant will flow for a certain time therefore this sound is a normal phenomenon 2 Aclicksoundcanoftenbeheardfromtherefrigerator Thisisa normalsoundproducedbythepull ...

Страница 17: ... inside the compressor this means that some moving parts have loosened note to differentiate this sound from thoseformedduringstartingorstoppingthecompressor 4 For the direct cooling refrigerator a kind of irregular crack sound can be often heard when the compressor is running for a certain period of time or has just stopped its running Thissoundiscausedbythestressreliefduetoexpansionandcontractio...

Страница 18: ...tothosepartsthatareliableto leak check main connection points for oil seepage and tubing for cracks If there is no b ListentothesoundcausedbytheflowingofgasintheevaporatorOpentherefrigerator doorwhilethecompressorisinoperation inclineyourearandlistenattentivelythegas flow sound inside the evaporator If it sounds like gentle whistling accompanied by a sound similar to water flowing this is the soun...

Страница 19: ...or the heat conduction effect will be severer leak point charge the system with nitrogen and detect leak points with the commonlyadoptedmethod repairthem evacuate chargethesystemwithrefrigerant andthenturnontherefrigeratortomakeatestrun 2 Toomuchrefrigerantchargedintothesystem AnalysisofTrouble a In case the amount of refrigerant charged into the system exceeds its nominal capacity the superfluous...

Страница 20: ...ently sometimes therefrigeratorworkswell andsometimesnotwell Inorder todeterminewhetheritiscloggedwithice heatthesuspiciouspointswithhotwaterto make ice melt and after a while if a gas flowing sound resulting from an abrupt gush is heard and the gas suction pressure rises as well itcan be confirmed that the trouble is severelyaffected thuscausingapoorrefrigeratingeffect RemedyItisquitedifficultto ...

Страница 21: ...he system with a properquantityofrefrigerant b Air left in the system Analysis of Trouble The residual air in the system will circulate togetherwiththerefrigerantinthesystem Themajorsymptomscausedbythisresidual causedbyiceclogging RemedyIfthereistoomuchmoistureintherefrigeratingsystem itisadvisabletoreleasetherefrigerant purgethetubingwithnitrogen andthencharge the system with the filtered refrige...

Страница 22: ...due to the leakage of temperature airishighergasdischargepressure higherdischargedgastemperature thegasdischarge tubing is considerably hot when you feel it with your hand and poorer refrigerating effect Furthermore the gas discharge pressure will exceed its normal value when the compressor has run for a period not too long thus making the protective relay actuate andbringtoastoppage RemedyCheckup...

Страница 23: ...rationtemperatureinthesystemistoo high thetemperaturesensingagentinthetemperaturesensorisalsohotter therefore sensing agent from the temperature sensor Remedy Remove the relay cover to check up its contacts if they are open this means that the original setting is not properly set ortemperaturesensingagenthasleakedoutofthetemperaturesensor Trytoturnthe adjusting stem of this value in the direction ...

Страница 24: ...ndthattherefrigerantinthesystemisinsufficientinquantity recharge it with refrigerant In case clogging occurs disassemble the part where it is blocked If the evaporation temperature is too high settle this problem with an appropriatequantityofrefrigerant 3 No stoppage of compressor due to damaged heat insulation layer inside case body and ordoorsealAnalysisofTroubleWhentheheat insulationlayerinside...

Страница 25: ...25 ...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...28 ...

Страница 29: ...29 ...

Страница 30: ...30 ...

Страница 31: ...31 ...

Страница 32: ......

Отзывы: