background image

035-000049-001 

Page 6 

HCA IOM 1.1 8-28-2017 

UNIT SUSPENSION 

Ceiling  Suspension:  Acceptable  forms  of  unit 
suspension are shown in Fig. 3, 4 and 5. Figure 
3 shows suspension rods run through the knock-
outs in top and bottom of the unit.  Use strut ma-
terial  and  hardware  at  bottom  as  shown  in  the 
details.    Figure  4  shows  field-supplied  platform 
mount. Units can also be supported by suspend-
ing  the  unit  from  crossbeams  at  the  front  and 
rear (Figure 5).   

Size  suspension  rods  to  support  the  weight.  
Size any beam members to insure that they are 
adequate  for  a  safe  installation.    Ensure  that 
suspension rods are secured to adequately sup-

port the unit and that the rods extend entirely 
through their associated fasteners. 

It is recommended that framing be construct-
ed from structural steel or formed-strut mate-
rials.   

With  Mixing  Boxes:    HCA  units  sizes  30-40 
with  mixing  boxes  should  be  supported  with 
crossbeams at each end of the unit and at the 
duct connection side of the mixing box.  Sizes 
04-20 with mixing box—no additional support 
is required.   

WARNING!  INSURE  THAT  UNIT  IS  ADE-
QUATELY  SUPPORTED  FROM  STRUC-
TURE  TO  PREVENT  DAMAGE  OR  INJURY 
CAUSED BY FALLING EQUIPMENT!  If un-
certain about how to connect to the struc-
ture,  consult  a  qualified  structural  engi-
neer.   

Fig. 3 

Ceiling Suspension—

Rods Through Unit

NOTES: 
1.  INSTALLATION MATERIALS 

ARE FIELD-SUPPLIED AND 
INSTALLED.   

2.  INSURE BUILDING STRUCTURE IS ADEQUATE FOR 

SUPPORTING THE EQUIPMENT.   

3.  INSURE AT LEAST 3 FULL THREADS ARE EXPOSED 

THROUGH EACH NUT WHEN LEVELING THE AHU.   

4.  USE NUT, WASHER, AND LOCK WASHER.  ALTER-

NATE:  NYLOCK NUT MAY BE USED INSTAD OF 
STANDARD NUT AND LOCK WASHER.  

WARNING!  

DO NOT OMIT LOCK WASHER OR NYLOCK NUT!  

Содержание HCA Series

Страница 1: ...ARNING Hazardous voltage Discon nect and Lock Out all incoming power sources before servicing or installing unit ELECTRIC SHOCK CAN CAUSE DEATH WARNING This equipment may be in stalled well above fini...

Страница 2: ...035 000049 001 Page 2 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 3: ...G Remove Shipping Screws 4 PREINSTALLATION 5 Rigging 5 Unit Weight Calculation 5 INSTALLATION 6 18 Unit Suspension 6 7 External Vibration Isolators 7 Ductwork 8 Electrical 9 11 Service Clearance 12 Co...

Страница 4: ...ampers until their operators are disconnected BE SURE that fans are properly grounded before working on them Failure to follow these warnings could result in personal injury or equipment damage DANGER...

Страница 5: ...l Code IMC section 307 2 3 requires the use of auxiliary drain pans Many municipalities have adopted this code Magic Aire holds that this practice represents the standard for professional installation...

Страница 6: ...ming be construct ed from structural steel or formed strut mate rials With Mixing Boxes HCA units sizes 30 40 with mixing boxes should be supported with crossbeams at each end of the unit and at the d...

Страница 7: ...JURY CAUSED BY FALLING EQUIPMENT If uncertain about how to connect to the structure consult a qualified structural engineer Floor mounting Unit may be mounted on a housekeeping pad floor or platform C...

Страница 8: ...side of a field provided flexible duct to the fan discharge duct collar on the front of the unit Attach the other side to the supply ductwork Seal the connec tions using duct mastic or HVAC tape Refe...

Страница 9: ...WARNING For use with copper conductors only INSTALLATION ELECTRICAL INSTALLATION ELECTRICAL Typical wiring diagrams are shown on the fol lowing pages FOR REFERENCE Always re fer to the wiring diagram...

Страница 10: ...circuit protection and wiring 6 To start the fan connect R and G1 or G2 or G3 to energize fan at each respective speed Add connection to terminal FLO4 on the control board EVOECM 4SPD to enable a four...

Страница 11: ...components is the responsibility of the in staller including branch circuit protection and wiring 6 To start the fan apply 2 0VDC to plus and minus terminals Fan speed is variable from 2 0VDC minimum...

Страница 12: ...S MAY BE ON ONE SIDE OR ON BOTH SIDES 4 REFER TO INSTALLATION INSTRUCTIONS FOR UNIT HANGING SUSPENSION REQUIREMENTS 5 COIL DRAINPAN OR BLOWER REPLACEMETN REQUIRES UNIT TO BE REMOVED TO FLOOR FOR SAFE...

Страница 13: ...vent losing seal when starting up the unit After the fan is running with the design fan inlet negative pressure the elevation of the water on the unit side of the trap will be 1 below the drain invert...

Страница 14: ...nto the condensate line between the trap and the gate valve instead of open to the atmosphere Figure 9 illustrates the typical piping at the end of every steam supply main Omitting this causes many fi...

Страница 15: ...with a bucket trap or any trap which has provision for passing air The great majority of high pressure return mains terminate in hot wells or deaerators which vent the air Fig 10 Multiple Coil High P...

Страница 16: ...s length The outer tubes are expanded into plate fins The completed assembly includes the supply and condensate header and side casings which are built to slant the fin tube bundle back to ward the co...

Страница 17: ...ions The lower split of face split coils should be first on last off Fig 13 Row split coils utilize special intertwined circuits either split of these row split coils can be first on last off SUCTION...

Страница 18: ...o use drop solenoid valve control as illustrated above and let the suction cutoff unloaders ride with the load The second is to use drop solenoid valve control as illustrated above with electric un lo...

Страница 19: ...tachometer to confirm operating speed access doors must be closed to apply correct external static pressure to the fan 3 Check direction of rotation see Fig 15 4 Check vibration If excessive vibration...

Страница 20: ...use any aggressive paint solvent cleaning agents when cleaning 5 Never use a high pressure cleaner or water spray for cleaning particularly when the fan is running WARNING Wet cleaning under volt age...

Страница 21: ...prevent the formation and build up of acids There are additional precautions and control strate gies as found in various catalogues and in the ASHRAE Fundamentals Handbook when the enter ing air tempe...

Страница 22: ...clear space 3 Remove the flat coil stubout panel Refer to Figure 16 and 17 Note that there is another coil access panel on the opposite side of the unit SERVICE Coil Drainpan Removal and Reinstallatio...

Страница 23: ...il panel Figure 23 and 24 8 Remove coils from unit along with drainpan Drainpan will slide out of unit Figure 25 or 26 To remove coils and drainpan top will need to be lifted up as shown in Figure 21...

Страница 24: ...nation up to 24 hours after sampling A low pH and high alkalinity cause system problems even when both values are within ranges shown The term pH refers to the acidity basicity or neutrality of the wa...

Страница 25: ...mary Auxiliary cu in note 2 Hot Water 1 row gal Hot Water 2 row gal Coil Face Area Pre Filter 12 x 24 16 x 32 3 Not all combinations equaling 10 rows are allowed Please refer to New Magic 4 Software f...

Страница 26: ...035 000049 001 Page 26 HCA IOM 1 1 8 28 2017...

Страница 27: ...necessary for proper condensate drainage Is properly sized condensate trap present Is the condensate disposal system operating correctly Is auxiliary external condensate drain pan installed as recomm...

Страница 28: ...035 000049 001 Page 28 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 29: ...035 000049 001 Page 29 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 30: ...035 000049 001 Page 30 HCA IOM 1 1 8 28 2017 HCA Series Air Handler Installation Operation and Maintenance Manual...

Отзывы: