INSTALLATION AND COMMISSIONING

09/15

6.

ELECTRICAL CONNECTION

4.

FIRE DAMPER 

– CONSTRUCTION SUPPORT ATTACHMENT 

5.

CONNECTION TO AIR DUCTS

FMC-EIS-120-MA+PIF

FMC-EIS-120-M7F...V

1

2

3

1

2

3

CONSTRUCTION SUPPORT

SAND AND CEMENT MORTAR

FMC-EIS-120

•  Set the damper filling with sand and cement mortar the space between the damper and the 

opening.
• Check that the damper blade is not trapped against the housing.
• Avoid projecting mortar moving parts of damper (blade, actuator, manual device).
• Once dry the damper-to-wall assembly, open and close the damper to
check for proper operation.

•Take precautions to ensure that flow of air to get uniformly to the damper and prevent their 
installation in the presence of vibrations.
• The inner dimension of the air ducts can not be smaller than inside dimension of the casing.
•Open and close the damper to check that the blade does not touch the duct.

*SWITCHES NORMALLY 

CLOSED CONTACTS

COM

NF

NO

COM

NF

NO

FC

DC

Closed damper

signal

Open damper

signal

CONTACT "FC"

COM

NO

NF

B.  OPEN DAMPER

A.  CLOSED DAMPER

CONTACT "DC"

CONTACT "FC"

CONTACT "DC"

COM

COM

COM

NO

NF

NO

NF

NO

NF

-5º

45º

90º

STOP

1

2

3

3

4

S1

S2

S3

S4

S5

S6

(SIEMENS GNA 326.1E, GGA 326.1E)

(SIEMENS GNA 126.1E, GGA 126.1E)

MOTOR 230V CA  

MOTOR 24V CA/24...48V CC

1

2

MEANING

COLOR

Switch  A Input

Switch  B Input

Switch  A Normally  closed

Switch  A Normally  open

Switch  B Normally  closed

Switch  B Normally  open

grey/ red

grey/ blue

grey/ pink

black/  red

black/  blue

black/  pink

MEANING

COLOR

Potential system  24VAC/  24

…48VCC

Zero of the system

black

red

blue

brown

COLOR

MEANING

Potentiel 230V

Neutral

1. Connection  cable  for auxiliary  switches

2. Connection  cable  for thermal  fuse

3. Connection  cable  for power

A. CLOSED DAMPER

B. OPEN DAMPER

CONTACT 

“B”

CONTACT 

“A”

CONTACT 

“B”

•Contact A    5º

•Contact B    80º

S1

S2

S3

S4

S5

S6

S1

S2

S3

S4

S5

S6

CONTACT 

“A”

Содержание FMC-EIS-120

Страница 1: ...when reaches that temperature Reset is manual except for motorized dampers The fire dampers FMC EIS 120 work as a separator between two sectors of fire and ensure the same fire resistance that the str...

Страница 2: ...S 500Pa Rigid wall Brick wall 110 mm Built in 0 360 EI 120 ve i o S 500Pa Rigid floor Reinforced concrete 150 mm Built in 0 360 EI 120 ho i o S 500Pa Sensing element load bearing capacity Sensing ele...

Страница 3: ...n 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 125 Dn 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 1 Casing 2 Rubber sealing ring 3...

Страница 4: ...rd Internal and external thermoelectrical fuse 72 C Automatic resetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Po...

Страница 5: ...ction of wall floor Placement in wall floor Device position Wall Floor Device position 0 360 The minimum distance between fire dampers and construction elements will be 75mm The minimum distance betwe...

Страница 6: ...ION SUPPORT Place the damper next the construction support indicated line which is painted on the label The arrows show the construction support direction B TEST MEASUREMENTS After placing the damper...

Страница 7: ...ing Open and close the damper to check that the blade does not touch the duct SWITCHES NORMALLY CLOSED CONTACTS COM NF NO COM NF NO FC DC Closed damper signal Open damper signal CONTACT FC COM NO NF B...

Страница 8: ...to European Standard series FMC EIS 120 M7F230V diam Operated by means of a servomotor at 230V M7F230 with closed switches Circular dampers made from galvanized steel and non combustible board Therma...

Страница 9: ...125 0 008 76 382 150 0 0125 113 564 160 0 0146 129 646 200 0 0244 207 1034 250 0 0403 329 1645 300 0 0601 480 2398 315 0 0668 530 2651 PRESSURE DROP AND SOUND POWER LEVEL Pa Pa 20 200 2000 2 3 4 5 6...

Отзывы: