18
ES
FR
EN
IT
FRG/2MBC(Z-F-R-M) - FRG/2MB(Z-F-R-M)
Madas Technical Manual
- 5|5.1b - REV. 0 of 15
th
Feb 2019
10.0 - WARRANTY
The warranty conditions agreed with the manufacturer at the time of the supply apply.
Damage caused by:
• Improper use of the device;
• Failure to observe the requirements described in this document;
• Failure to observe the regulations pertaining to installation;
• Tampering, modification and use of non-original spare parts;
is not covered by the rights of the warranty or compensation for damage.
The warranty also excludes maintenance work, the assembly of parts or non-original spare parts, making changes to the
device and natural wear.
11.0 - RATING PLATE DATA
The rating plate data (see examples above) includes the following:
• Manufacturer’s name/logo and address (possible distributor name/logo)
• Mod.:
= name/model of the device followed by the connection diameter
• PS =
Allowable pressure
• Pe =
Maximum pressure or inlet pressure range that product operation is guaranteed at
• (-20...+60) °C
= Temperature range that product operation is guaranteed within
• Pa
= Outlet pressure range
• Wdso =
OPSO calibration range that can be achieved with the spring provided (without replacing any part)
• CE-51BT3739 (if it is present) = certification pin number
• AC
= Accuracy class Pa
• SG =
Closing pressure class
• AG =
Overpressure shut off accuracy unit
• EN 88-2
= Product reference regulation
• Wdsu =
UPSO calibration range that can be achieved with the spring provided (without replacing any part)
• DfRv
= Differential relief valve range with respect to Pa
• year
= Year of manufacture
• Lot
= Product serial number (see explanation below)
• U1823
= Lot issued in year 2018 in the 23
rd
week
• 14216
= progressive job order number for the indicated year
• 00001
= progressive number referring to the quantity of the lot
•
= In compliance with ATEX Dir. followed by the protection mode
•
(if it is present)
= Compliance with (EU) Regulation 2016/426 followed by the no. of the Notified Body
•
= In compliance with PED directive followed by the no. of the Notified Body
Mod.: FRG/2MBZ DN 25
PS=Pe:0,5-5 bar
(-20...+60)°C
Pa: 20-30 mbar Wdso:40-90 mbar
CE-51BT3739 AC10 SG30 AG10 EN 88-2
Wdsu:10-30 mbar DfRv:10-60 mbar
year: 2018 Lot:U1823 14216/00001
Via Moratello, 5/7 - 37045
Legnago (VR) - Italy
www.madas.it
0051
0497
II2G
II2D