7.0 - WARRANTY
The warranty conditions agreed with the manufacturer at the time of the supply apply.
For damage caused by:
• Improper use of the device;
• Failure to observe the requirements described in this document;
• Failure to observe the regulations pertaining to installation;
• Tampering, modification and use of non-original spare parts;
are not covered by the rights of the warranty or compensation for damage.
The warranty also excludes maintenance work, the assembly of devices of other manufacturers, making changes to the device
and natural wear.
8.0 - RATING PLATE DATA
The rating plate data (see example provided here) includes the following:
• Manufacturer’s name/logo and address (possible distributor name/logo)
• Mod.:
= device name/model followed
by the connection diameter
• CE-51AR1070
= certification pin number
• EN 126
= Product reference regulation
• Max PS
= Maximum pressure at which product operation is guaranteed
• Filtering
= Filtering
• (-40...+70) °C
= Temperature range within which product operation is guaranteed
•
= Compliance with (EU) Regulation 2016/426 followed by Notified Body No.
•
= In compliance with PED directive followed by the no. of the Notified Body
• year
= Year of manufacture
• Lot
= Product serial number (see explanation below)
• U1812
= Lot issued in year 2018 in the 12th week
• 7634
= progressive job order number for the indicated year
• 00001
= progressive number referring to the quantity of the lot
Mod.: FM DN 200
CE-51AR1070 - EN 126
PS max: 6 bar
Filtering: 10 micron
(-40...+70) °C
year: 2018 Lot:U1812 7634/00001
0051
0497
9.0 - FILTER SIZING EXAMPLE
Usage data
Q
n
= 1210 [Nm
3
/h] Methane
P
i
= 1.2 [bar]
To use the diagram, you have to convert the usage
data to the diagram conditions (P
1
=0) and vice versa.
• Conversion to the flow rate at the diagram conditions:
• Choosing the filter diameter:
• Identify the Q
d
flow rate on the Gas line used and go up with a vertical line until you cross the straight line for the selected diameter
(see example diagram on page 48);
• From this newly identified point, move left until you cross the graph axis and read the ∆P
d
• Converting the ΔP
d
measured on the diagram at the system conditions:
Q
d
[Nm
3
/h] =
=
= 550 [m
3
/h]
Q
n
[Nm
3
/h]
1210
[Nm
3
/h]
P
i
+ 1 [bar]
1.2 + 1 [bar]
Maximum flow rates in m
3
/h of methane gas considering a max flow speed through the pipes of 20 m/s
DN 65
DN 80
DN 100
DN 125
DN 150
DN 200
DN 250
DN 300
244
m
3
/h
370
m
3
/h
578
m
3
/h
903
m
3
/h
1300
m
3
/h
2312
m
3
/h
3613
m
3
/h
5203
m
3
/h
∆P
r
[mbar] = ∆P
d
[mbar] x (P
i
+ 1) [bar] = 6.5 [mbar] x (1.2 + 1) [bar] = 14.3 [mbar]
• Follow the same procedure in the diagrams on pages 49, 50 and 51 to calculate the pressure drop of the filters to the various
filtering points (50 µm -20 µm -10 µm).
KEY
Q
n
: Usage flow rate
[Nm
3
/h]
Q
d
: Flow rate at the diagram conditions
[m
3
/h]
P
i
: System pressure
∆P
d
: ∆P measured on the diagram
∆P
r
: ∆P normalised to the system condition
P
1
: Diagram tracing pressure