Macurco
TM
DVP-1200 Manual
REV – 1.3.1
[34-8708-4770-7 ]
7
|
P a g e
2.4
Features
•
LCD display showing the status of each transducer and relay
•
External keypad for user selection of the transducer/alarm display and setting the configuration (password protected)
•
Three RS-485 digital input channels – 192 addressable sensors
•
Up to 8 control zones can be defined
•
Each zone can be controlled based on transducer signals and/or time of day
•
Comes standard with four onboard 10A, 240 VAC SPDT Dry Contact relays
•
Up to four optional onboard expansion relays available
•
Up to 2 additional remote relays available
•
Each relay is configurable with a delay before activation and minimum on time
•
Fail-safe operation can be implemented
•
Lockable NEMA 4X type enclosure
•
Modular input and output connectors
•
Ethernet connection for BACnet output (BACnet IP)
•
USB connection
•
Compatible with Macurco Commercial 6-Series gas detectors, MRS-485 adapter, Horn & Strobe Combo
•
Four 24VDC Drivers for external Horn and Strobe
•
Three 4-20mA output
•
ETL Listed to UL 2017
2.5
Specifications
•
Size:
13.0” x 10.0” x 2.75”
•
Weight:
12.4 lb. (5.6 kg)
•
Enclosure:
NEMA 4X rated
•
Operating Temperature:
32° to 104°F (0° to 40°C)
•
Operating Humidity:
0% to 95% RH non-condensing
•
Power Input:
100 – 240 VAC, 1 Amp, 50/60 Hz, single phase
•
Relay Rating (4):
SPDT, 120/240 VAC, 10 A Max (resistive)
•
LCD Display:
320 x 240 Pixels Graphic LCD Display with backlight
•
Status Indicators (LED):
Power/Trouble, Hush, Warning/ALARM, and Relay
•
Audible indicator:
Internal buzzer, 90 dBA at 1ft
•
External Drivers (4):
24VDC, maximum 250 mA
•
Relay on Delay:
0 – 99 minutes in 1 second increments
•
Relay Minimum Run Time:
0 – 99minutes in 1 second increments
Содержание DVP-1200
Страница 2: ......
Страница 5: ...MacurcoTM DVP 1200 Manual REV 1 3 1 34 8708 4770 7 4 P a g e ...
Страница 60: ......
Страница 67: ......