Figure 4-37 –
Following additional fail-safe settings are available for Remote Relay Configuration.
•
FAIL SAFE ACTIVE/NOT ACTIVE
With this setting one can either enable (FAIL SAFE ACTIVE) or disable (FAIL SAFE NOT ACTIVE) fail safe operation for
corresponding remote relay.
•
FAIL SAFE STATE ON or OFF
This setting defines the state of the relay during fail safe condition if fail-safe settings is active or enabled.
•
FAIL SAFE TIMEOUT (s)
This is the time (in seconds) that the remote relay must wait for communication from the DVP-1200 before going into
fail-safe mode if fail-safe setting is active (ON). Valid entries are 10 to 3600 seconds.
To change corresponding setting, highlight the line and hit Enter. Select the desired settings and hit Enter again. Once the
desired configuration is selected for all fail-safe settings hit SAVE to save the settings and transfer the settings to remote relay.
Repeat the assignment procedure for second remote relay.
To configure Relays 9 to 12 for regular settings (delay, minimum run time etc.) use CONFIGURE RELAY? menu. Once remote
relay is discovered and assigned then only corresponding relay number (9,10,11 and 12) will be valid entries for CONFIGURE
RELAY menu.
4.6.3.3
CONFIGURE H/S
Menu path: Main Menu-->CONFIGURE SYSTEM? -->MANUAL CONFIGURE? -->CONFIGURE RELAYS, H/S, BUZZER? -->CONFIGURE
H/S?
To configure a horn/strobe, follow the menu as shown in the images below. With “HORN/STROBE(S):” selected, press ENTER.
Then input the horn/strobe number to configure (H/S 1 is shown in the example below) and press ENTER.