MACH-3 Installation and Configuration Manual
WARNING:
Before you begin any of the
procedures in this section, read the
safety
and regulatory information
that is shipped
with your system. For additional best practices
information, go to
www.machfu.com/
regulatory_compliance
.
WARNING:
The MACH-3 Gateway must
be installed by knowledgeable and skilled
personnel familiar with local and/or
international electrical statutes and regulations.
WARNING:
The MACH-3 Gateway is not
designed for use in wet environments. If the
MACH-3 Gateway is to be installed in a wet
environment, depending on the location and
environment, it must be installed in a panel
box or enclosure with an Ingress Protection (IP)
rating of IP54, IP65, or higher.
WARNING:
To reduce the risk of electric shock,
power to the DC+ and DC- terminals must be
provided by a power supply or transformer/
rectifier circuit that is designed with double-
insulation. The power supply or power circuit
source must comply with local codes and
regulations; for example, in the USA, NEC Class
2 (SELV/limited energy circuit, or LPS circuitry). If
powered by a battery, double-insulation is not
required.
WARNING:
Ensure that the power source
providing power to the MACH-3 Gateway is
reliably grounded and filtered such that the
peak-to-peak ripple component is less than 10
percent of the input DC voltage.
WARNING:
When installing the MACH-3
Gateway, use a cable appropriate for the
load currents: 3-core cable rated 5 A at
90°C (194°F) minimum, which conform to
either IEC 60227 or IEC 60245. The system
accepts cables from 0.8 mm to 2 mm. The
maximum operating temperature of the
MACH-3 Gateway is 80°C (176 °F). Do not
exceed this maximum temperature while
operating the MACH-3 Gateway inside an
enclosure. Internal heating of the MACH-3
Gateway electronics, other electronics, and
!
!
!
!
!
!
2. Installing your MACH-3 Gateway
the lack of ventilation inside an enclosure
can cause the operating temperature
of the MACH-3 Gateway to be greater
than the outside ambient temperature.
Continuous operation of the MACH-3
Gateway at temperatures greater than
80°C(176°F) may result in an increased
failure rate and a reduction of the product
life. Ensure that the maximum operating
temperature of the MACH-3 Gateway when
placed inside an enclosure is 80°C (176 °F)
or less.
WARNING:
The symbol indicates hot surface
or adjacent hot surface that can cause a burn.
Allow equipment to cool or use protective gloves
when handling to reduce risk of a burn.
WARNING:
Always ensure that the available
power source matches the required input power
of the MACH-3 Gateway. Check the input power
markings next to power connector(s) before
making connections. The 9-60 VDC power
source must be compliant with local Electrical
Codes and Regulations.
WARNING:
To ensure the protection provided
by the MACH-3 Gateway is not impaired, do not
use or install the system in any manner other
than what is specified in this manual.
WARNING:
If a battery is included as part of the
system or network, the battery must be installed
within an appropriate enclosure in accordance
with local fire and electrical codes and laws.
WARNING:
The system is for installation
in a suitable industrial enclosure with tool-
removable cover or door only.
WARNING:
The system is for installation in
Class I, Division 2, Groups A, B, C, D hazardous
locations or non-hazardous locations only.
WARNING:
EXPLOSION HAZARD: DO NOT
CONNECT OR DISCONNECT EQUIPMENT
WHEN ENERGIZED. Perform connections or
disconnections to equipment only when not
energized or the area is known to be non-
hazardous.
!
!
!
!
!
!
!
2 Installing your MACH-3 Gateway
!