MACH-3 Installation and Configuration Manual

WARNING: 

Before you begin any of the 

procedures in this section, read the 

safety 

and regulatory information

 that is shipped 

with your system. For additional best practices 
information, go to 

www.machfu.com/

regulatory_compliance

WARNING: 

The MACH-3 Gateway must 

be installed by knowledgeable and skilled 
personnel familiar with local and/or 
international electrical statutes and regulations. 

WARNING:

 The MACH-3 Gateway is not 

designed for use in wet environments. If the 
MACH-3 Gateway is to be installed in a wet 
environment, depending on the location and 
environment, it must be installed in a panel 
box or enclosure with an Ingress Protection (IP) 
rating of IP54, IP65, or higher. 

WARNING: 

To reduce the risk of electric shock, 

power to the DC+ and DC- terminals must be 
provided by a power supply or transformer/
rectifier circuit that is designed with double-
insulation. The power supply or power circuit 
source must comply with local codes and 
regulations; for example, in the USA, NEC Class 
2 (SELV/limited energy circuit, or LPS circuitry). If 
powered by a battery, double-insulation is not 
required. 

WARNING:

 Ensure that the power source 

providing power to the MACH-3 Gateway is 
reliably grounded and filtered such that the 
peak-to-peak ripple component is less than 10 
percent of the input DC voltage. 

WARNING:

 When installing the MACH-3 

Gateway, use a cable appropriate for the 
load currents: 3-core cable rated 5 A at 
90°C (194°F) minimum, which conform to 
either IEC 60227 or IEC 60245. The system 
accepts cables from 0.8 mm to 2 mm. The 
maximum operating temperature of the 
MACH-3 Gateway is 80°C (176 °F). Do not 
exceed this maximum temperature while 
operating the MACH-3 Gateway inside an 
enclosure. Internal heating of the MACH-3 
Gateway electronics, other electronics, and 

!

!

!

!

!

!

2.  Installing your MACH-3 Gateway

the lack of ventilation inside an enclosure 
can cause the operating temperature 
of the MACH-3 Gateway to be greater 
than the outside ambient temperature. 
Continuous operation of the MACH-3 
Gateway at temperatures greater than 
80°C(176°F) may result in an increased 
failure rate and a reduction of the product 
life. Ensure that the maximum operating 
temperature of the MACH-3 Gateway when 
placed inside an enclosure is 80°C (176 °F) 
or less. 

WARNING: 

The       symbol indicates hot surface 

or adjacent hot surface that can cause a burn. 
Allow equipment to cool or use protective gloves 
when handling to reduce risk of a burn.

WARNING: 

Always ensure that the available 

power source matches the required input power 
of the MACH-3 Gateway. Check the input power 
markings next to power connector(s) before 
making connections. The 9-60 VDC power 
source must be compliant with local Electrical 
Codes and Regulations. 

WARNING: 

To ensure the protection provided 

by the MACH-3 Gateway is not impaired, do not 
use or install the system in any manner other 
than what is specified in this manual. 

WARNING: 

If a battery is included as part of the 

system or network, the battery must be installed 
within an appropriate enclosure in accordance 
with local fire and electrical codes and laws. 

WARNING:

 The system is for installation 

in a suitable industrial enclosure with tool-
removable cover or door only.

WARNING:

 The system is for installation in 

Class I, Division 2, Groups A, B, C, D hazardous 
locations or non-hazardous locations only.

WARNING:

 EXPLOSION HAZARD: DO NOT 

CONNECT OR DISCONNECT EQUIPMENT 
WHEN ENERGIZED. Perform connections or 
disconnections to equipment only when not 
energized or the area is known to be non-
hazardous.

!

!

!

!

!

!

!

2  Installing your MACH-3 Gateway

!

Содержание MACH-3

Страница 1: ...Simplifying IoT from edge to enterprise January 31 2019 Revision 5 0 MACH 3 Installation and Configuration Manual...

Страница 2: ...duct CAUTION A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the problem WARNING A WARNING indicates a potential for property damage personal injury...

Страница 3: ...ON INSTRUCTIONS 5 2 1 1 Installation Personnel 5 2 1 2 Installation Location 5 2 1 3 External Antenna 5 2 2 GATEWAY MOUNTING OPTIONS 5 2 3 SETTING UP MACH 3 GATEWAY 6 3 Gateway Configuration 8 3 1 OVE...

Страница 4: ...5 1 Bridge 20 3 5 2 VPN 20 3 5 3 Open VPN 22 3 5 4 Port Forwarding 22 3 5 5 Source Network Address Translation 24 3 5 6 Routes 25 3 6 SETTINGS 26 3 6 1 Profile 26 3 6 2 Users Roles 26 3 6 3 Reset Use...

Страница 5: ...ration Manual Simplifying IoT from edge to enterprise Revision History Revision Description Date 1 0 Initial release 1 4 2017 2 0 Revision 1 5 2018 3 0 Revision 8 1 2018 4 0 Revision 10 3 2018 5 0 Rev...

Страница 6: ...ices used in the electric grid oil gas manufacturing and other applications The MACH 3 Gateway has a low power architecture which is capable of supporting industrial automation workloads while remaini...

Страница 7: ...3 Installation and Configuration Manual Simplifying IoT from edge to enterprise 1 Overview 1 1 2 Right Side SIM Door View 1 1 3 Bottom View 3 39 1 66 1 22 0 97 Maximum length 1 25 6 32 mounting screw...

Страница 8: ...temperature while operating the MACH 3 Gateway inside an enclosure Internal heating of the MACH 3 Gateway electronics other electronics and 2 Installing your MACH 3 Gateway the lack of ventilation in...

Страница 9: ...antennae Non approved antennae may produce spurious or excessive RF transmitting power which may lead to a violation of FCC IC limits 2 2 Gateway Mounting Options 2 2 1 Bottom Mount 2 2 2 Din Rail Mou...

Страница 10: ...ro SIM card in the SIM Card slot as shown in Figure 2 SIM Card Installation before turning on the MACH 3 gateway 4 The gateway power connector is a Molex Microfit 3 0 four pin connector wired as shown...

Страница 11: ...0 VDC Switch in GND Switch in Figure 3 Power connector pinout Figure 2 SIM Card Installation Unscrew and remove the SIM door Replace and screw in the SIM door Slide SIM card into holder through openin...

Страница 12: ...s seen in the navigation bar on the left side of the interface Each tab may contain multiple sections and each web based management page is used to configure a specific aspect of the Gateway DASHBOARD...

Страница 13: ...lements of the Gateway It provides a high level view of the device and network interfaces as well as the GPS information 3 2 1 General Information Device name Classification of the MACH Gateway Device...

Страница 14: ...curacy GPS readings accuracy GPS Fix Time Last fix from the GPS satellites 3 2 3 Cellular Information Status Indicates if the Cellular link is Enabled or Disabled PPP UP DOWN Indicates if the Cellular...

Страница 15: ...Indicates if the Ethernet connection is Enabled or Disabled Link UP DOWN Indicates if the Ethernet link is UP or DOWN Link Speed Data rate on the Ethernet 1 eth0 Interface MAC Address MAC address of...

Страница 16: ...e Ethernet is acting as STATIC IP DHCP Server or Bridge Tx Bytes Number of bytes transmitted since boot up Rx Bytes Number of bytes received since boot up 3 2 7 Wi Fi Client Status Indicates if the Wi...

Страница 17: ...or SSID Service Set Identifier used to identify the WLAN Link UP DOWN Indicates if the Wi Fi link is UP or DOWN MAC Address MAC Address of the Wi Fi Access Point IP Address IP Address of the Wi Fi Ac...

Страница 18: ...re used to configure the Wi Fi and Cellular radios on the MACH Gateway 3 3 1 Wi Fi Client In the Client mode the following configurations are seen Set the Enable button to use the Wi Fi in the Client...

Страница 19: ...e the Wi Fi in the access point mode SSID Specify the wireless network name or SSID Service Set Identifier used to identify the WLAN Set the Broadcast SSID button if you want the SSID to be visible En...

Страница 20: ...cellular network ICCID The Integrated Circuit Card Identifier ICCID is a 19 digit identification number for SIM Manufacturer The manufacturer of cellular modem in the MACH Gateway Model The model of c...

Страница 21: ...and Ethernet 2 eth1 To configure Ethernet or Serial interface click the WIRED Tab on the left panel 3 4 1 Ethernet The two Ethernet ports have identical configuration elements The help guide applies t...

Страница 22: ...he interface to other communication means such as Wi Fi etc select the BRIDGE in the MODE dialog box There is no IP address associated in this mode of operation 3 4 1 6 Firewall Group Under Advanced O...

Страница 23: ...and can be one bit or two bits Set the STOP BITS switch to 1 to send one stop bit or set it to 2 to send two stop bits 3 4 2 7 Flow Control This setting informs the data receiver on how to process th...

Страница 24: ...PN can be configured through Ethernet or Cellular 3 5 2 1 1 L2TP Ethernet To configure the VPN through Ethernet Set the L2TP TYPE switch to L2TP ETHERNET Enter the public IP address of the IPSEC serve...

Страница 25: ...lic IP address of the L2TP Network Server in the L2TP LNS IP dialog box Enter the private IP address for the MACH Gateway in the L2TP LOCAL IP dialog box Enter the port number of the L2TP Network Serv...

Страница 26: ...pdown list Set the COMPRESSION switch to ON to enable compression or set it to OFF to disable it Select TLS Security Type from the dropdown list and paste the TLS authentication or crypt key in PEM fo...

Страница 27: ...s The default value is ANY PORT In display mode it shows the port number of the original destination In edit mode a dialog box is shown with the existing value of the original destination port number...

Страница 28: ...E In display mode it shows if the particular rule row is enabled or disabled In edit mode it shows a dropdown list with values enabled or disabled The default value is enabled INTERFACE In display mod...

Страница 29: ...AN The routing rules are represented in a tabular format The principle of adding changing deleting rules and refresh tables are the same as Port forwarding 3 5 6 1 Table Columns Fields ACTIONS It cont...

Страница 30: ...add new users delete existing users and reset users password 3 6 2 1 Show All Users The users table displays all the other users of the MACH Gateway The table columns fields include ACTION It contain...

Страница 31: ...of the user Type the password of the user The password must be six characters or more Select the preferred role for the user The selections are Admin OEM Users and Customer Click the Add button to re...

Страница 32: ...he deletion was successful or not If the action was successful the user s row is removed from the table 3 6 3 Reset User s Password To reset the password of a user follow the steps below Click the Res...

Страница 33: ...s The Roles table has two columns fields ROLES It displays the acceptable roles for the MACH Gateway USERS It displays users of the MACH Gateway based on their assigned role 3 7 SYSTEM The SYSTEM tab...

Страница 34: ...lect the Image verification certificate The oem user should upload an OEM certificate while the customer user should upload a Customer certificate The admin user can upload either an OEM certificate o...

Страница 35: ...set the Remote Support option follow the steps below Set the ENABLED button to ON to enable remote support or set it to OFF to disable it A pop up dialog appears and it warns the user about the inten...

Страница 36: ...the applications table Machfu Apps These apps services can be uninstalled or closed from the table 3 7 3 2 Table Columns Fields ACTION This contains the delete icon for Machfu Apps This column appears...

Страница 37: ...up dialog appears and it informs the user if the app has been uninstalled successfully or not The table refreshes automatically to show that the app has been removed uninstalled 3 7 4 Start Stop App T...

Страница 38: ...34 Simplifying IoT from edge to enterprise MACH 3 Installation and Configuration Manual 3 Gateway Configuration The table refreshes automatically to show that the updated status of app...

Страница 39: ...with antenna installation instructions and consider removing the no collocation statement This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 thi...

Страница 40: ...greater than the maximum gain indicated for that type are strictly prohibited for use with this device Le pr sent metteur radio with model Mach3 Gateway a t approuv par Industrie Canada pour fonction...

Страница 41: ...acement antenna NOTE Modifications to the device or use of unauthorized antennae as not expressly approved by Machfu is the sole responsibility of the user configurator or operator who must reassess t...

Страница 42: ...38 Simplifying IoT from edge to enterprise MACH 3 Installation and Configuration Manual 5 3 Contacting Machfu For technical assistance or customer service issues please contact support machfu com...

Отзывы: