RS232 communication ports (EIA/TIA-232 and V.28/V.24 compatible)
Two general purpose RS232 ports available on the C350 pro unit both are compliant with
the EIA/TIA-232 standard. Serial port 1 cannot use handshaking, but on serial port 2 all
control signals are present.
Serial port 1 / programming port.
This port can be used as general-purpose RS232 serial port or as a C350 pro
programming port. In order to use the port for programming, the RS-DET pin must be
connected to SGND. When using the port as general-purpose RS232, the RS-DET pin
must be left unconnected. Further details on the programming cable are available in the
M2M Control IDE online help.
X1: SER1 connector overview (6-pin TYCO Mate-n-Lock)
Pin
Name
Description
1
TXD
Transmit data from serial port 1, RS232 compatible
4
RXD
Receive data for serial port 1, RS232 compatible
2
RS-DET
Programming cable detect, normally unconnected
(
if programming cable, connect to SGND
)
5 SGND Signal
ground
6 SGND Signal
ground