background image

1. Specifications

2.Functional Description(TIC)

7) LBA Control lamp: It will be on when Control Loop Disconnection alarm appears.

8) Mode set key: Press it more than 2sec., the system will be changed to parameter set.

9) Down key(remainning time display key):Press it, set value decreases; Press more than 2sec, set
value decreases consecutively. Press it for several sec. during timer ON, remaining time will be
flickered.

10) Up key(Time ON/OFF key): If you press it, the set value goes up one by one; if you pres it more
than 2sec, the set value goes up consecutively. If you press it during controlling, you can turn on/off
the timer.

11) Auto Tuning Key: After parameter set, press AT more than 2sec., AT lamp(5times) will be
flickered and calculating PID automatically.

1) Displays processing value(PV) : Displays processing value in controlling and each kind of
parameters in parameter set

2) Displays set value and parameter set(SV) : Displays set value in controlling and parameter value in
parameter set.  Press key No.9, then displays the remaining time.

3) Lamp of output control(OUT)

4) Warning lamp of highest and lowest(ALM)

5) Auto-tuning lamp(AT) :Press key No.11, then it starts PID auto-tuning with flikering of the lamp
and the lamp turns off when it is finish.

6) Timer lamp: Press No.10 key of the Timer during controlling, then lamp will be flickered. After a
set time, the light will be on; at a time, tENd will be appeared on SV. To back to the initial stage,
press Up key more than 2 sec.

Electrical supply

AC220V 50/60㎐ or AC110V 50/60㎐

Weight (㎏)

2.1

2.8

3.5

Internal

Stainless steel

Dimensions

186 x 232 x 120mm 242 x 256 x 120mm 322 x 256 x 120mm

MODEL

Dry block heater

DMB-1

DMB-2

Controller

Digital PID auto-tuning

Timer

Material

Block

Anodizing Aluminum

DMB-3

Type

1

2

3

Temperature

Range

A5℃ ~ 200℃

Accuracy

±0.5℃

99hr 59min

Heater power

250W

350W

450W

PV

SV

AT

ALM

OUT

MD

AT

3

4

9

5

8

2

7

11

10

1

6

Содержание DMB-1

Страница 1: ...avoid electrical shock always 1 Use a properly grounded electrical outlet of correct voltage and current handling capacity 2 Disconnectfrom power supply before servicing To avoid personal injury 1 Do not use in the presence of flammable or combustible materials fire or explosion may result This item contains components which may ignite such materials 2 Keep the item clean Use non abrasive cleaner ...

Страница 2: ...parameters in parameter set 2 Displays set value and parameter set SV Displays set value in controlling and parameter value in parameter set Press key No 9 then displays the remaining time 3 Lamp of output control OUT 4 Warning lamp of highest and lowest ALM 5 Auto tuning lamp AT Press key No 11 then it starts PID auto tuning with flikering of the lamp and the lamp turns off when it is finish 6 Ti...

Страница 3: ...maticall y set for Auto Tuning 7 I Intergral time Possible to set a 1sec unit within 5 9998 sec range 8 5 ALL Low alarm It sets the lowest alarm limit 0 It is absolute value 4 ALH High alarm It sets the heighest Alarm limit 0 It is absolute value Up key can modulate ON OFF The Timer begins working after current temp reaches set temp After a set time reaches it stops ending Control output The TIMER...

Страница 4: ...e 1 Use without auto tuning but do it in case of a big temperature difference 2 Press No 11 key then it starts with switching on and off 3 Temperature error could be happened on auto tuning but it is controlled correctly when auto tuning is finished 4 Temperature go higher than the setting value first time but it is returned to normal condition immediately Over shoot condition 5 In case that tempe...

Страница 5: ... a few second and keep the constant speed by arithmetic logic unit Smooth start function 4 In initial operating if the motor does not run give the motor output fast and make it run until speed is arrive at 10rpm so that the motor runs When Err are shown on display Check if the temperature sensor is coneected corretly Check if the wire of the temperature sensor is not down Check if the tempereture ...

Отзывы: