W5VS

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the front of the unit.

 EXTERNAL DIMENSIONS  unit: mm (inch) 

 

 

 

 

 CONNECTION DIAGRAM

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.

For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 

following.

5

4

3

2

1

11

10

9

8

7

6

94 (3.70)

45 (1.77)

41 (1.61)

[3.3 (.13)]

• When mounting, no extra space is needed between units

.

DIN RAIL

35mm wide

5–M3.5 SCREW

7.4 (.29)

6–M3 SCREW

6 (.24)

3 (.12)

U(+)

V(–)

POWER

10

11

+

OUTPUT 1

6

7

+

8

9

OUTPUT 2

4

5

+

INPUT

The section enclosed by broken line is only with 
2nd output option.
DO NOT connect to the terminals 1 – 2 – 3.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce

-

dure 1) – 3).

5)  Go through the same procedure for the output 2.
  Calibration for the output 1 affects the output 2.  Check 

the output 2 whenever the output 1 is adjusted.

Note: Remove the sealing label for /VN option.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-

MENT PROCEDURE” explained earlier.

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание W5 Series

Страница 1: ...oltage See INPUT SPECIFICATIONS CE not available Power suffix code M R2 P only 01 Specify voltage See INPUT SPECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available Power suffix code M R2 P only 2 OUTPUT 1 Current A 4 20 mA DC Load resistance 550 Ω max B 2 10 mA DC Load resistance 1100 Ω max C 1 5 mA DC Load resistance 2200 Ω max D 0 20 ...

Страница 2: ...t code 0 Not CE Voltage range 300 300 V DC Minimum span 100 mV Offset Max 1 5 times span Input code 01 CE Voltage range 70 70 V DC Minimum span 100 mV Offset Max 1 5 times span Input code 02 Not CE Voltage range 100 100 mV DC Minimum span 5 mV Offset Max 1 5 times span OUTPUT SPECIFICATIONS DC Current 0 20 mA DC Minimum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC V...

Страница 3: ...U V POWER 10 11 Input shunt resistor attached for current input Remark 1 The section enclosed by broken line is only with 2nd output option Remark 2 DO NOT connect to the terminals 1 2 3 INPUT OUTPUT 1 Isolation S Z Output Driver S Z Output Driver OUTPUT 2 6 7 8 9 Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox...

Страница 4: ...ot install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind...

Страница 5: ...output 2 whenever the output 1 is adjusted Note Remove the sealing label for VN option MAINTENANCE Regular calibration procedure is explained below CALIBRATION Warm up the unit for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the output signal for the respective input signal remains within accu racy described in the data sheet When the output is out of tolerance recalibrate...

Отзывы: