SIGNAL TRANSMITTER

MODEL

W5VS

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Signal conditioner ......................................................... (1)
  Sealing label (option /VN) ............................................ (1)

 MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  85 – 264V AC rating: 85 – 264V, 47 – 66 Hz, approx. 4 – 6VA
  24V DC rating: 24V ±10%, approx. 3W
  11 – 27V DC rating: 11 – 27V, approx. 3W
  110V DC rating: 85 – 150V, approx. 3W

 GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 0 to 90% RH 

in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close to noise sources (relay drive cable, high frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup

-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom.

 MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook at the rear side of unit on the DIN 

rail.

B) Push in the lower in keeping pressing the unit to the 

DIN rail.

 REMOVING THE UNIT

A) Push down the DIN rail adaptor using a minus screw-

driver.

B) Pull out the lower part of the unit.

C) Remove the upper part from the DIN rail.

• Output 2    

Span Adj.

Zero Adj.

• Output 1    

    Span Adj.

Zero Adj.

Body

Spec. Marking

A

B

DIN Rail

C

A

B

Spring Loaded

DIN Rail Adaptor

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание W5 Series

Страница 1: ...oltage See INPUT SPECIFICATIONS CE not available Power suffix code M R2 P only 01 Specify voltage See INPUT SPECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available Power suffix code M R2 P only 2 OUTPUT 1 Current A 4 20 mA DC Load resistance 550 Ω max B 2 10 mA DC Load resistance 1100 Ω max C 1 5 mA DC Load resistance 2200 Ω max D 0 20 ...

Страница 2: ...t code 0 Not CE Voltage range 300 300 V DC Minimum span 100 mV Offset Max 1 5 times span Input code 01 CE Voltage range 70 70 V DC Minimum span 100 mV Offset Max 1 5 times span Input code 02 Not CE Voltage range 100 100 mV DC Minimum span 5 mV Offset Max 1 5 times span OUTPUT SPECIFICATIONS DC Current 0 20 mA DC Minimum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC V...

Страница 3: ...U V POWER 10 11 Input shunt resistor attached for current input Remark 1 The section enclosed by broken line is only with 2nd output option Remark 2 DO NOT connect to the terminals 1 2 3 INPUT OUTPUT 1 Isolation S Z Output Driver S Z Output Driver OUTPUT 2 6 7 8 9 Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox...

Страница 4: ...ot install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind...

Страница 5: ...output 2 whenever the output 1 is adjusted Note Remove the sealing label for VN option MAINTENANCE Regular calibration procedure is explained below CALIBRATION Warm up the unit for at least 10 minutes Apply 0 25 50 75 and 100 input signal Check that the output signal for the respective input signal remains within accu racy described in the data sheet When the output is out of tolerance recalibrate...

Отзывы: