background image

W2CA / W2CE

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5537  Rev.8  P. 3 / 3

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

   Be sure to short the secondary side of CT or turn off the 

current at its primary side for preventing the CT from 

burning when the cables are to be disconnected from in-

put terminals.

   Be sure that the input waveform is sinusoidal to obtain 

proper accuracy for model W2CA.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

5) Go through the same procedure for the Output 2.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Отзывы: